A fire door holds fire back for its period, and the seal is the part that closes the gap when the heat arrives. The leaf alone cannot hold the line, because the gap round it lets heat and smoke through long before the period runs out. The seal sits in its groove and waits, and when the temperature climbs it swells shut and fills the gap.
A seal that is missing, painted over or fitted in the wrong place leaves the door with no answer to the heat. The test that proved the leaf also proved the seal beside it, so the strip on the order must be the strip the test report names, in the groove the test put it in.
The hardware that sits beside the seal is covered in the fire door hardware guide, and the closer that pulls the leaf shut is set out in the fire door closers guide. A seal ordered without the leaf it belongs to may land in the wrong groove, so the leaf, the frame and the seal are named together on one line of the order.
- Swells at 200-250 degreesIntumescent strip wakes with heat
- FD30SSmoke seal proved to BS EN 1634-3
- 4 mmGap the seal must close
- EN 1634-1Leaf, frame and seal proved together
The strip that wakes with heat: what an intumescent seal does
An intumescent seal is a strip that grows when it gets hot. At room temperature it sits flat in its groove and does nothing, and the gap round the leaf stays open at 4 mm so the door can swing. When fire heats the strip to around 200 to 250 degrees, the material swells many times its own thickness and presses against the frame, closing the gap the leaf alone cannot close.
The swelling is the whole job of the strip. Heat that reaches the door first reaches the seal, and the seal answers by filling the space between the leaf and the frame before flame and hot gas can pass through it. A strip that swells too little leaves part of the gap open, and a strip that swells in the wrong place presses against air instead of the frame.
Once the strip has swollen it does not shrink back. The door that has faced a fire takes a new seal before it goes back into use, because the strip that did its job has spent itself.
The strip in the groove: where a seal sits on the leaf and the frame
The seal lives in a groove cut in the frame or in the edge of the leaf, and the groove decides where the strip can swell. A groove in the frame lets the strip press against the leaf when it grows, while a groove in the leaf edge lets it press against the frame, and the test report says which of the two the doorset was proved with.
A strip fitted outside its groove has no proof behind it. A seal stuck to the face of the frame instead of sitting in the groove may look right from the corridor, yet it swells against nothing when the heat arrives, and the gap stays open.
Some leaves take two strips, one in the frame and one in the leaf edge, and the pair must be the pair the test report names. The steel versus timber fire doors guide works through the choice between leaf materials, and the groove a leaf can carry follows the material it is made from.
FD30 and FD60: the period the seal must match
The period on the door is the period the seal must match. A strip proved for FD30 on a leaf that must hold FD60 runs out before the leaf does, because the seal and the leaf were never proved together for the longer period. The leaf, the frame and the seal were proved together to EN 1634-1, and the period on the order is the period all three were tested to.
Fire resistance is measured in E, EW and EI from 30 to 120 minutes under EN 1634-1, and the letters beside the number say what the doorset held back.
Matching the period starts on the schedule, where the seal is named beside the door it fits. The fire door regulations commercial buildings guide sets out the periods for the shared parts of a public building, and the period for each door on the schedule follows the part of the building it guards.
Smoke seals beside the strip: Sa, S200 and the cold smoke gap
An intumescent strip answers heat, and cold smoke needs a different answer. Smoke at room temperature slips through a 4 mm gap long before the strip wakes, so a door on a smoke path takes FD30S, with the smoke seal proved to BS EN 1634-3, to Sa for smoke at room temperature and S200 for smoke at 200 degrees Celsius.
The smoke seal is a brush or a blade that stays in contact with the leaf while the door is shut, and it holds the cold smoke back while the intumescent strip waits for the heat. The two seals sit beside each other in the same groove or in grooves of their own, and each must be the one the test report names, because a brush from another doorset carries no proof on this leaf.
The smoke control doors guide covers the doors that hold smoke back while people move past them, and the seal that holds the smoke is named on the schedule beside the door.
Seals on escape routes: the strip between the room and the way out
An escape route is only as clear as the doors along it, and the seal on each of those doors holds smoke off the way people leave. A corridor door whose seal has come away lets smoke into the corridor while people are still moving through it, so the strip on an escape route door is checked on every round, not only when the building changes hands.
The closer on an escape route door must pull the leaf shut every time, because a seal in a groove does nothing while the leaf stands open. No fire door takes less than EN 3 to BS EN 1154, and the closer belongs on the order beside the leaf, with the power size chosen for the weight of the leaf it must shut.
People on an escape route must get out without a key, whatever the seal says, because the way out matters more than the way in. A panic bar to BS EN 1125 throws the latch when pushed, and the bar must work with the lock beside it, not against it. The fire door closers guide sets out the sizes and the fitting of closers, and the seal, the closer and the bar all sit on the same line of the order.
Seals on compartment walls: holding the line between rooms
A compartment wall holds fire in one part of a building, and every door in that wall needs a seal that holds the same line. The wall can be sound and the leaf can be proved, yet the fire passes through the gap round the leaf if the strip in the groove is missing or wrong, so the seal is part of the compartment, not only part of the door.
Each opening in the wall takes its own proof. A door that guards a store takes the period the fire load behind it demands, while a door on a stair core takes the period the escape route needs, and the seal on each one matches the period of the door it sits on.
Services that pass through the wall take their own sealing where they cross it, and the door beside them takes a strip that was proved with the leaf. The plant room door requirements guide covers the doors on the rooms that feed a building, and the fire door regulations commercial buildings guide sets out the periods for the shared parts of a public building.
The seal that fails: paint, damage and the strip that has come away
Paint is the quietest way to kill a seal. A strip painted over cannot swell, because the paint holds the material in place while the heat rises, and the gap stays open behind a leaf that looks freshly finished.
Damage finds a seal in other ways. A strip that has hardened with age, cracked where the leaf meets the frame, or come away from its groove leaves part of the gap open, and the part that is open is the part the fire will find. The check is simple: look at the strip on every round, run a finger along it to feel whether it sits in the groove, and write down what is wrong on the same day it is found.
A seal that has done its job in a fire is replaced before the door goes back into use, because a strip that has swollen once cannot swell again. The fire door inspection checklist names what each visit should look for, and the security door maintenance checklist covers the doors that must hold both fire and forced entry.
Paint, polish and the cleaning round wear a strip down over the year
A strip waits in its groove all year, and the year still finds ways to spoil it. When the room is repainted, paint can run onto the strip and pin it flat, so it cannot grow when the heat comes. When the frame is polished, polish can coat the strip, and a cloth can catch its edge and lift it a little out of the groove each time the room is cleaned. Age can harden the strip, so it grows too little to fill the gap, and wetting and drying, time and again, can take the softness out of it.
The round that finds these faults runs a finger along the strip, end to end, to feel whether it sits in its groove, soft and free of paint. The strip on the door must be the one the test report lists, in the groove the test gave it, because a strip from another doorset brings no proof to this door. The strip wakes at around 200 to 250 degrees, and it must be seated in its groove when the heat comes, so one that has gone hard with age is changed before the fire finds it. What each visit should cover is named in the fire door inspection checklist, while the round that holds the seal to its proof is set down in the fire door maintenance guide.
| What the year does | What the round finds | What the answer is |
|---|---|---|
| Paint over the strip | Paint holding the material flat | Strip changed, paint kept off it |
| Polish on the strip | Coating on the surface | Strip wiped or changed, polish kept off |
| Strip hardened with age | A strip that has gone hard | Strip changed for the strip named |
| Knocks from trolleys | Strip torn or cut at the edge | Strip changed, damage noted |
A damaged strip found on the round: repair, replace or take the door out
A strip that is painted, hardened, torn or out of its groove goes on the record the day it is found, with the door named and the fault described. A strip that has only lifted at one end can be pressed back into its groove, if the groove is clean and the strip is still soft, but one that is painted, hardened or torn cannot be mended, and it is changed for the strip the report lists. The groove is cleaned before the new strip goes in, because dust and paint in the groove hold the strip out of its seat, and the new strip is felt along its whole length before the door goes back into use.
A door whose strip cannot be put right that day is taken out of service on the route it guards, because a door with no working seal leaves the gap open to fire and smoke while the proof is argued over. The fire door gaps guide carries the size the gap must hold, and the fire door closers guide lists the power a closer needs, because a closer with no power left leaves the door ajar and the strip waiting for heat that never reaches it. The grades and parts a working fire door needs are named in the fire door hardware guide. The schedule should name the strip and the smoke seal for every door, with the groove beside them, and let the security door enquiry checklist carry what goes with the enquiry.
A replacement strip is proved or it is not a replacement
Once paint covers a strip, the strip cannot swell when the heat arrives, because the paint pins the material flat while the fire grows, and a leaf that looks freshly finished can still leave its gap open. The strip that replaces it must be the strip the test report names, in the groove the test put it in, because a brush from another doorset carries no proof on this leaf, and a strip fitted outside its groove swells against nothing when the heat arrives. Intumescent seals expand at around 200 to 250 degrees, so the strip must be in its groove before the heat arrives, and a strip that has hardened with age swells too little to close the gap it was made for.
Where the strip can swell depends on the groove it sits in. With the groove cut in the frame, the growing strip presses against the leaf, and with the groove cut in the leaf edge, it presses against the frame, and the report names which of the two the doorset was proved with. The gap round the leaf stays at 4 mm so the door can swing, and the fire door gaps guide gives the gap the leaf needs.
| Fault | What the round finds | What the replacement must match |
|---|---|---|
| Painted strip | Paint holding the material | The strip the report names, unpainted |
| Hardened strip | A strip that has gone hard with age | The strip the report names, soft in the groove |
| Strip out of groove | A strip that has come away | The groove the test put it in |
| Smoke seal worn | Brush or blade worn thin | The seal the report names, in contact while shut |
| Wrong strip | A strip from another doorset | The strip, the groove and the period together |
No seal holds a door that stands open
A seal in a groove does nothing while the leaf stands open, so the closer belongs on the order beside the leaf, with the power size chosen for the weight of the leaf it must shut. Every fire door needs at least EN 3 to BS EN 1154, and a closer that has lost its power holds the leaf ajar while the strip waits for heat that never reaches it. The fire door closers guide gives the sizes and the fitting of closers, and the fire door hardware guide gives the grades and the parts a working fire door depends on.
Heat wakes the intumescent strip, while cold smoke slips past it and needs a seal of its own. Cold smoke passes a 4 mm gap well before the strip has woken, so a door on a smoke path takes FD30S, with its smoke seal proved to BS EN 1634-3, to Sa at room temperature and S200 at 200 degrees Celsius. The two seals sit side by side in one groove or in grooves of their own, and each must match the strip the test report names.
Check the strip on every round, run a finger along it to feel whether it sits in the groove, and write down what is wrong on the same day it is found. The fire door inspection checklist spells out what each visit should look at, and the fire door maintenance guide lays down the routine that keeps the seal as it was proved. Name the strip, the smoke seal and the groove beside every door on the schedule, and let the security door enquiry checklist say what goes with the enquiry.
One schedule for the whole building: every seal on one line
Put the seal order together as one list, with a line for every door on the building and the strip, the smoke seal and the groove beside each one, so the seal that arrives matches the seal that was proved. A schedule that names one strip for the whole building leaves the fitter to guess which door takes which seal, and a strip fitted to the wrong door has no proof behind it.
Check every line of each quotation against the schedule before the order goes out, so no seal, groove or smoke strip is left off the price. Anything left off the quotation still has to be bought, and fitting it after the door is in place costs more than ordering it with the door. The security door cost factors guide works through what each step up the scale adds to the price, and the how to specify security doors guide sets out the columns the schedule needs.
The fire rated windows guide covers the windows that share the same wall, the fire rated windows cost factors guide covers what each step adds to the price, and the keeping an LPS 1175 rating valid guide sets out what breaks a rating once a door is fitted.
| Position | Seal | Period | What to check |
|---|---|---|---|
| Corridor | Intumescent strip | FD30 | Strip in groove, unpainted |
| Stair core | Intumescent strip | FD60 | Strip, groove, closer |
| Escape route | Strip and smoke seal | FD30S | Brush, strip, gap |
| Plant room | Intumescent strip | FD60 | Strip, seals, gap |
| Store | Intumescent strip | FD30 | Strip, groove, latch |
A seal holds only as long as the groove it sits in and the test behind it, so the strip, the smoke seal and the period must all sit on the same schedule.
What does an intumescent seal do?
It swells when heated to around 200 to 250 degrees, filling the gap round the leaf so heat and flame cannot pass through it.
Where does the seal sit?
In a groove in the frame or in the edge of the leaf, where the test report put it. A strip outside its groove has no proof behind it.
What is FD30S?
A fire door period with a smoke seal proved to BS EN 1634-3, to Sa for smoke at room temperature and S200 for smoke at 200 degrees Celsius.
Can a seal be painted over?
No. Paint holds the strip in place and stops it swelling, so a painted strip is replaced with the strip the test report names.
Who checks the seals?
The person who runs the building, on the round that walks every door. Each fault is written against the door it belongs to on the same day it is found.