Fire Rated Windows Explained
Fire rated windows in compartment walls and on escape routes: EI30 and EI60, fixed and openable, what the rating covers and what to check before you order.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
A fire rated window is a window tested as part of a wall. The pane, the frame, the beads and the seals were tested together to EN 1634-1, and the rating belongs to that tested assembly, not to the glass on its own. A pane that carries a fire class in one frame carries no rating at all in a different frame, because the test never covered that combination. The window is only as strong as the weakest part of the assembly, and the test report is the document that names every part.
Windows sit in compartment walls, along corridors, around stair cores and beside escape routes. They let light through a wall that must hold fire, and they let people see what is on the other side before a door is opened. A fixed window never opens, so its rating rests on the pane and the frame alone. An openable window has a sash, hinges and a handle, so its rating rests on the moving parts as well, and on whether the sash is closed when fire breaks out. The two types look alike from the corridor, and the specification must tell them apart.
The two periods a specifier meets most often are EI30 and EI60. The number is the minutes the assembly held its rating in the furnace test to EN 1634-1, and the letters say what it held back. Our fire rated glass cost guide works through what drives the cost of the glass, the class, the period, the build-up and the frame, with factors only and no invented prices. Our fire rated glazed doors page covers the same assembly discipline for a leaf that opens every day.
- EI30 and EI60Fire resistance periods tested to EN 1634-1
- E, EW and EIIntegrity, radiated heat limit, insulation
- BS EN 16034Product standard for fire rated windows and doorsets
- 140 and 180 degreesTemperature rise limits on the safe side for EI
A window in a compartment wall is part of the wall
Compartmentation divides a building into parts, and a fire in one part is held there long enough for the rest of the building to empty. The walls do the dividing, and the windows are the weak points in the walls, so a window in a compartment wall has to hold as long as the wall it stands in. A window rated EI60 in a 30 minute wall gives a 30 minute opening, and a window rated EI30 in a 60 minute wall gives a 30 minute opening too. The wall and the window are one decision, and the fire strategy is the place where they meet.
The rating of the window must match the rating of the wall, and the glass must match the rating of the window. A 30 minute pane in a 60 minute window leaves the window at 30 minutes, whatever the frame is rated to. The same rule runs through the whole opening: the pane, the beads, the frame and the seals must all carry the classification and the minutes the strategy names. A window ordered as a pane on its own, with the frame and beads to follow, is an assembly with no evidence behind it.
The frame matters as much as the glass. A heavy EI pane needs a frame that can carry its weight for the whole life of the building, and the beads that hold the pane must be the bead system the test evidence names, with the fixings the evidence names beside it. A bead swapped on site for a neater looking one takes the window outside its evidence, because the rating belongs to the tested assembly. Our fire ratings page sets out the three letters, the periods and how to read a rating, and our fire door regulations for commercial buildings guide covers the Order, the 2022 regulations and Approved Document B in full.
Fixed windows: the pane, the frame and the beads
A fixed window has no moving parts, and that is its strength. The pane sits in the frame, the beads hold it, the seals close the edge, and nothing in the assembly depends on someone remembering to shut it. The rating rests on the build-up of the pane and on the frame that carries it. EI glass needs an interlayer or a gel layer that holds the temperature rise on the safe side to an average of 140 degrees Celsius and a maximum of 180 degrees Celsius above ambient, and that build is thicker and heavier than an E pane of the same size. The frame, the beads and the fixings must carry the extra weight, so the whole window moves with the pane.
Ordinary float glass has no place in a fire wall. It cracks under thermal shock and falls out of its beads early in a fire, leaving an open hole where the wall was meant to hold. Only glass named in the test evidence for that window, held in the tested beads, belongs in a compartment wall. A thicker pane does not always mean a longer rating, because two panes of the same thickness can carry different classes. The make-up of the layers decides the class, and the test report is the proof. Ask for the report that states the standard, the class and the period for the exact glass build being bought.
The size of the pane is set by the test evidence too. The tested aperture is the maximum for that window, and a larger pane needs its own evidence, because a bigger pane heats differently and puts more load on the beads. A fixed window that is ordered bigger than the tested aperture is a window outside its evidence, and no certificate can be written for it. Keep the aperture inside the evidence, and keep the beads, the seals and the frame exactly as the evidence names them.
Openable windows: the sash, the hardware and the closer
An openable window has a sash that moves, and the rating depends on that sash being closed when fire breaks out. Hinges carry the sash, the handle pulls it home, and the closing device holds it shut against the seals. A sash that is left open has no fire performance at all, whatever its certificate says, because the opening is open. The hardware must be the hardware the test evidence names, fitted in the pattern the evidence names, or the window leaves its evidence behind.
A window that is held open for air during the day needs a release that closes it when the alarm sounds. A wedge, a prop or a hook on the wall has no such release, and a sash held open by one of those will stand open in a fire. Fit the right release and the right closing device, so the window can stand open when the building needs it open and still close when it matters. The release must be tested with the window, not added afterwards, because the closing device is part of the tested assembly.
Check the sash at every inspection, and check that it closes and latches on its own. A sash that drags on the frame, a hinge that has dropped, or a handle that no longer pulls the sash home are faults to fix, not to live with. A window that does not close has no rating to check, and the fault should be written down beside the date it was found and the date it was fixed. Our fire door inspection checklist gives the checks that catch a failing leaf before it matters, and the same habit of walking, looking and writing down applies to windows.
EI30 and EI60: reading the letter and the minutes
The letter matters as much as the number. An E window stops flames and hot gases passing through for the stated minutes, but the glass on the safe side can still become hot. An EW window adds a limit on radiated heat, so a person can stand near it without being driven back. An EI window adds insulation, so the temperature rise on the safe side is limited to an average of 140 degrees Celsius and a maximum of 180 degrees Celsius, and the window can be touched. Escape routes and corridors where people pass close to the window usually need EI, because people escape past the window and may need to put a hand near it.
The periods run from E30 to E240, and the number is the minutes the assembly held its rating in the furnace test to EN 1634-1. EI30 and EI60 are the periods a specifier meets most often, because 30 minutes covers most compartment walls and 60 minutes covers the walls that protect longer escape routes and stair cores. The period comes from the building fire strategy, not from the window, so ask the fire engineer for the schedule and specify windows tested to match it. Never order a lower class or a shorter period than the strategy names, and never change the letter or the minutes on site without the fire engineer agreeing.
A higher class or a longer period than the strategy asks for is possible, but the extra build is money spent on performance nobody asked for, and the extra weight has to be carried by the frame and the fixings. The product standard for fire rated windows and doorsets is BS EN 16034, and the test report should state the standard, the class and the period for the exact assembly being bought.
Windows on escape routes: light, sight and the way out
Windows on escape routes do two jobs at once. They let daylight into a corridor or a stair core, and they let people see what is on the other side before they open a door. A corridor window that shows a clear corridor tells a person the route is open, and a stair window that shows smoke on the landing tells them to turn back. The window must hold as long as the door beside it, because a corridor with a 60 minute door and a 30 minute window is a 30 minute corridor. The fire strategy names the period for each opening, and the window and the door on the same route must be read together.
Schools show why this matters. Children escape in groups, teachers lead classes along corridors, and the windows along the route let staff see where the children are and whether the way ahead is clear. A school window needs the same EI rating as the doors on the route, and the same care over seals and gaps, because the corridor is the route every class uses to get out. Our fire door regulations for schools guide covers Building Bulletin 100, FD30 and FD60, and school inspection duties, and our security doors and gates for schools page covers the security side of the same buildings.
Smoke reaches people long before flames do, so a window on an escape route must be judged on smoke as well as fire. A fire rating to EN 1634-1 tests flame and heat, and smoke passes through a cold gap long before heat reaches the seals. Where the fire strategy asks for smoke control, the window needs a smoke rating to BS EN 1634-3, Sa or S200, and the S in a rating such as FD30S marks it. A fire rating on its own does not prove smoke control, so ask for the smoke evidence by name.
Smoke, seals and the gap around the frame
The gap around the frame is the place a window rating is most often lost. The pane can be right, the beads can be right and the frame can be right, and the window can still fail at the edge where the frame meets the wall. That gap must be sealed with the material the test evidence names, fitted in the way the evidence names, or the compartment line is broken at the very point it matters most. A window fitted into a wall with an unsealed gap is a window with a hole beside it.
Intumescent seals close the gap in a fire, expanding at roughly 200 to 250 degrees, and smoke seals close it against cold smoke. Both have to be fitted, intact and unpainted, or the seal is a seal in name only. Paint over an intumescent seal and it cannot expand when heat reaches it, so tell the decorators that the seals are never to be coated.
The frame and the wall must be read together. Check the wall, the head detail and the fixings with the window, and order them as one opening. Our fire rated glazed doors page works through beads, seals and the frame that holds the glass, and the same discipline applies to a window frame.
Windows that must do two jobs: fire and security together
Some windows must hold fire and resist forced entry, and the two jobs need two sets of evidence on one assembly. A fire classification to EN 1634-1 and a forced entry rating to LPS 1175 are separate tests, and each rating needs its own test evidence on the same construction. The glass and the bead fixings sit on both sets of evidence, so a pane that passes the fire test with one bead system and the security test with another has no combined rating at all. Ask for both certificates against one identical specification, and check that the glass, the beads and the frame are the same on both.
The same rule covers a window that must be both fire rated and bullet resistant. The pane carries the layers for both jobs, and the test evidence must name both the fire class and the BR class from EN 1063 on the same build. Our bullet resistant windows page covers the BR classes, and our dual certification guide works through how fire and security sit on one assembly.
Security ratings are read the same way as fire ratings: from the test, not from the label. LPS 1175 runs from A1 to H20, with B3, C5 and D10 as the tool examples a specifier meets most often, and EN 1627 runs from RC1 to RC6. PAS 24 covers doorsets for dwellings, and Secured by Design is a scheme, not a rating, so a window that names the scheme without naming the test has proved nothing.
Writing the order: one window, one set of evidence
Ordering fire rated windows is a specification exercise, not a shopping exercise. The order should name the rating in full, EI30 or EI60 with the letter and the smoke rating where the strategy asks for it, and it should name the pane, the frame, the beads, the seals and the hardware as one assembly. Our how to specify security doors guide covers the same discipline for rated security doors, and our types of security doors guide sets out the range of openings a building may need.
Order the evidence with the windows. The test report, the classification and the hardware schedule should arrive with the assembly, and the handover pack should name the inspection routine the building will follow. A building that files the evidence on the day the windows arrive has a record it can use for the whole life of the building. Our fire rated sliding doors guide sets out the same discipline for a leaf on a track, where the evidence travels with the assembly too.
Finally, check the windows on delivery, before they are fitted. Check the pane against the order, the beads against the evidence, the seals against the schedule, and the hardware against the test report. A window that arrives wrong and is fitted anyway is a window that has to be taken out again, and a window that arrives right and is fitted with the wrong beads is a window outside its evidence.
| Window position | Period | What it must do | What to check |
|---|---|---|---|
| Compartment wall, fixed | EI60 | Hold the wall as a fire line, let light through | Pane class, beads, frame to wall seal |
| Corridor window | EI30 | Let staff see the corridor, hold the escape route | Glass class, seals, frame fixings |
| Stair core window | EI60 | Protect the stair while people come down | Smoke seals, frame seal, pane class |
| Escape route window | EI30 or EI60 | Show the way ahead is clear, hold as long as the door | Rating matches the door, seals, gaps |
| Plant room window | EI60 | Hold a higher-risk fire inside its own compartment | Seals, gaps, self-closing sash |
A window with no test evidence behind it is ordinary glass in a fire wall.
What is the difference between E and EI for a window?
E covers integrity only: the window stops flames and hot gases passing through for the stated minutes. EI adds an insulation limit on temperature rise on the safe side, an average of 140 degrees Celsius and a maximum of 180 degrees Celsius above ambient. Compartment walls and escape routes usually specify EI, because people pass close to the window and may need to put a hand near it.
Can a fire rated window open?
Yes, where the openable sash was tested with the window. The sash, the hinges, the handle and the closing device must be the hardware the test evidence names, and the sash must close and latch on its own. A window that is held open during the day needs a release that closes it when the alarm sounds. A sash left open has no fire performance, whatever its certificate says.
Does a window need the same rating as the wall it stands in?
Yes. The window is the weak point in the wall, so a 30 minute pane in a 60 minute wall gives a 30 minute opening, and a 60 minute window in a 30 minute wall gives a 30 minute opening too. The wall and the window are one decision, and the fire strategy names the period for each opening. Never order a lower class or a shorter period than the strategy names.
Can one window be fire rated and bullet resistant?
Yes, with combined evidence. The pane carries the layers for both jobs, and the test evidence must name both the fire class and the BR class from EN 1063 on the same build. Ask for both certificates against one identical specification, and check that the glass, the beads and the frame are the same on both. A bullet resistant window without a fire test is not a fire window.
What paperwork proves a fire rated window?
The EN 1634-1 test report for the exact assembly, stating the classification and the minutes, plus third-party certification under the LPS 1056 scheme where the strategy calls for it. Go through the submittal part by part and confirm each matches the report: the pane, the beads, the frame, the seals and the hardware. If any part is missing from the evidence, the rating is unproven.
What a fire rated window rating does not prove
A rating on a fire rated window proves one thing: the tested assembly held its rating in the test. It proves nothing else. Treat the certificate as a narrow statement, and ask what it leaves out before the order is placed.
It does not prove the glass suits the frame. A pane that carries a fire class in one frame carries no rating at all in a different frame, because the test never covered that combination.
It does not prove the window holds as long as the wall. A window rated EI60 in a 30 minute wall gives a 30 minute opening, and a window rated EI30 in a 60 minute wall gives a 30 minute opening too. The wall and the window are one decision, and the fire strategy names the period for each opening. EI adds an insulation limit on temperature rise on the safe side, an average of 140 degrees Celsius and a maximum of 180 degrees Celsius, and escape routes usually need EI because people pass close to the window.
It does not prove smoke is controlled. A fire rating to EN 1634-1 tests flame and heat, and smoke passes through a cold gap long before heat reaches the seals. Where the fire strategy asks for smoke control, the window needs a smoke rating to BS EN 1634-3, Sa or S200, and the S in a rating such as FD30S marks it. A fire rating on its own does not prove smoke control, so ask for the smoke evidence by name.
It does not prove the sash will close. An openable window has a sash, hinges and a handle, so its rating rests on the sash being closed when fire breaks out. A sash that is left open has no fire performance at all, whatever its certificate says. A window held open for air needs a release that closes it when the alarm sounds.
Mistakes that break a fire rated window order
Most fire rated window orders fail in small ways. Each mistake below has the same result: a window that looks right and cannot be proved.
| Mistake | Why it fails | What to do instead |
|---|---|---|
| Pane ordered without the frame | The rating belongs to the tested assembly, not the glass alone. | Order pane, frame, beads and seals as one assembly. |
| Beads swapped on site | A neater bead takes the window outside its evidence. | Fit only the bead system the test evidence names. |
| Gap around the frame left unsealed | The compartment line is broken beside the window. | Seal the gap with the material the evidence names. |
| Paint over the intumescent seals | The seals cannot expand when heat reaches them. | Tell the decorators the seals are never to be coated. |
| Sash held open with a wedge | A sash left open has no fire performance at all. | Fit a release that closes the sash when the alarm sounds. |
Keep the evidence with the windows. The test report, the classification and the hardware schedule should travel with the assembly. For the glass behind the order, see our fire rated glass cost guide, and for how fire and security sit on one assembly, see our dual certification guide.