Smoke Control Doors Explained
Smoke control doors explained: Sa and S200 to BS EN 1634-3, smoke seals against intumescent seals, and the doors that must hold cold smoke back.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
A smoke control door is a fire door with one extra duty: it must stop cold smoke passing around its edges from the moment it closes. Fire kills, but smoke kills first, and cold smoke spreads through a building long before the fire reaches the door. A door that holds flames for 60 minutes and lets smoke through its gaps has failed the people on the other side, because smoke reaches them first.
The difference is a separate test. Fire performance is tested to EN 1634-1, and smoke leakage is tested to BS EN 1634-3, classified to BS EN 13501-2. The two tests ask different questions, and a pass in one says nothing about the other. The S in a rating such as FD30S marks the smoke side, and it must be named in the specification where the fire strategy needs it.
The hardware that makes it work is ordinary: a closer sized to BS EN 1154, hinges to BS EN 1935, a smoke seal that is a brush or a blade, and gaps kept to 4 mm. Our fire door hardware guide sets out the hardware set, and our fire rated steel doors page covers the leaf that most smoke control doors are built on.
- SaSmoke leakage tested at ambient temperature, BS EN 1634-3
- S200Smoke leakage tested at 200 degrees C, BS EN 1634-3
- FD30S30 minutes integrity plus smoke control
- BS EN 1634-3The smoke leakage test standard
Cold smoke travels before the flames arrive
Smoke from a fire is hot at the source, but by the time it reaches a corridor door it has cooled, thinned and spread. It moves along corridors, up stair cores and through gaps around a leaf that looks closed. A person on the far side of the door meets the smoke first, and the smoke takes the air they need before the flames are anywhere near them.
That is why the fire strategy treats smoke as its own problem. A compartment wall that holds fire for 60 minutes is no use if smoke passes its doors in the first minutes, because the escape route fills while the fire is still in the room where it started. The doors on the escape route must hold smoke as well as fire, and the rating must name both.
Intumescent seals cannot do this job. They expand at roughly 200 to 250 degrees, and cold smoke arrives long before the temperature at the door reaches that point. The seal that stops cold smoke is a different strip altogether, fitted and working from the moment the door closes.
Sa and S200: reading the smoke class
BS EN 1634-3 is the test for smoke leakage. A doorset is fitted in a frame, the door is closed, and smoke is drawn past it while the leakage is measured. The test is run at ambient temperature for the Sa class, and at 200 degrees for the S200 class. The classification is given to BS EN 13501-2.
Sa covers smoke at ambient temperature, which is the smoke a person meets in a corridor at the start of a fire. S200 covers smoke at 200 degrees, which is the hotter smoke that reaches a door later, or on a route close to the fire. A doorset classified E30Sa carries 30 minutes of integrity with ambient smoke control. A doorset that also carries S200 has shown it can hold smoke at the higher temperature too.
The class to specify follows the fire strategy, not the catalogue. Corridors and stair cores usually need Sa, because the smoke that reaches them first is cold. A door close to a high-risk room, or on a route where the fire strategy expects hot smoke, may need S200. Ask the fire engineer which class the strategy names for each opening, and specify that class by name.
The S in FD30S: what the suffix proves
In UK trade shorthand the suffix S marks smoke control: FD30S is a 30-minute door with smoke control, and FD60S is a 60-minute door with smoke control. The number is the fire period, the letter S is the smoke class, and both must be proved on the same doorset.
The suffix proves nothing on its own. It is a claim that the doorset was tested to BS EN 1634-3 with the leaf, the frame, the seals and the hardware that will be fitted on site. A door with an S in its name and a different seal fitted on site has left its evidence behind.
Ask for the test report that names the smoke class beside the fire class. The report should state the standard, the class and the construction it was tested on, and the doorset on site should match that construction part for part. If any part is missing from the evidence, the smoke rating is unproven.
FD30S is the normal requirement for a flat entrance door opening onto common parts, self-closing, with smoke seals, under Approved Document B. The period comes from the fire strategy for the building, not from the security rating, and the two never trade against each other.
Smoke seals and fire seals: two strips, two jobs
A smoke seal is a flexible brush or blade fitted around the leaf edge or in the frame. It blocks smoke at normal temperature from the moment the door closes, because it is already touching the frame. It works cold, it works from the first second, and it works every time the door shuts.
An intumescent seal is a strip that expands when heat arrives, closing the gap around the leaf in a fire. It does nothing about cold smoke, because it only expands when the temperature reaches roughly 200 to 250 degrees. By then the smoke has already passed.
Many doors carry a combined fire and smoke seal, with the intumescent strip and the smoke brush in one profile. The two parts sit side by side and each does its own job. The combined profile must be the one named in the test evidence, fitted in the position the evidence names.
A smoke seal replaced with a generic draught strip is a change to the tested assembly. Draught strips are made to stop draughts, not smoke, and they have no test evidence behind them. Replace a worn smoke seal with the same profile, not with whatever is on the shelf.
Where smoke control is needed: corridors, stairs and lobbies
Smoke control is needed where people escape, and where people wait. Corridors are the first place, because every escape route runs along a corridor and the doors off it must hold smoke while the corridor fills with people. A corridor door without smoke control lets smoke into the very route people must use to get out.
Stair cores come next. A stair is the route from every floor to the ground, and smoke in a stair core takes the escape route from the whole building at once. The doors to a stair core need the smoke class the fire strategy names, and the seals must be intact, because a stair door that leaks smoke is a stair that cannot be used.
Lobbies and cross-corridor doors matter for the same reason. A lobby door holds smoke in the room where the fire started and keeps the corridor clear for the people behind it. A cross-corridor door divides a long corridor into parts, so smoke in one part does not reach the other. Our fire door regulations for commercial buildings guide covers the duties behind these doors.
Flats show the rule at its clearest. A flat entrance door opening onto common parts is normally an FD30S doorset, self-closing, with smoke seals, because the stay-put strategy depends on the door holding smoke and flame inside the flat while other residents stay where they are. Our flat entrance doors guide covers that doorset in full.
The closer, the gaps and the door that must shut itself
A smoke seal only works when the door is shut. A door that stands open, or a door that closes but does not latch, has no smoke performance at all, whatever its certificate says. The self-closing device is part of the requirement, not an optional extra, and the door must shut fully from any angle.
The closer must be sized to BS EN 1154 for the leaf, so it closes the leaf and holds the latch every time. A closer sized below the leaf will not close it against air pressure or a draught from a corridor, and a closer that has been adjusted by hand, or taken off because it was too stiff, will leave the leaf standing open. Our fire door closers guide sets out the power sizes and how to read them.
The gaps around the leaf are kept to 4 mm, because the seals can only close a gap they were tested with. A leaf that has dropped on its hinges, or a frame that has moved, leaves a gap the smoke seal cannot bridge. A gap gauge is a small tool and a quick check, and it belongs in the hand of whoever walks the building.
Hold-open devices need care too. A door held open during the day needs a hold-open device to BS EN 1155 that releases the door when the alarm sounds. A wedge, a chair or a hook on the wall has no such release, and a door held open by one of those will stand open in a fire, smoke and all.
A smoke door that stands open is no smoke door
Smoke travels before the flames arrive, and a smoke door only works when it is shut. A door wedged open, a closer that cannot pull the leaf shut or a hold-open device that never releases on the alarm all leave the corridor open to smoke, and the escape route fills while the fire is still in the next room. The closer is the part that decides whether the door shuts, so the closer power size belongs on the schedule beside the fire period, because the two are set together: the period names what the door must hold and the closer names what shuts it.
BS EN 1154 sets closer power sizes from EN 1, for a 750 mm leaf at 20 kg, up to EN 7, for a 1,600 mm leaf at 160 kg, with a minimum of EN 3 on a fire door. A closer set too strong puts the door outside the access rules, because BS 8300 and Approved Document M cap opening force at below 30 N through the first 30 degrees and below 22.5 N beyond that. A closer set too weak leaves the door standing open, and a fire door standing open is a hole in the compartment wall. The power sizes and the adjustments that keep a closer inside the rules are listed in our fire door closers guide.
A corridor door held open during the day needs a hold-open device to BS EN 1155 that releases on the alarm. Put the release on alarm on the schedule beside the door, and test the release on the inspection round, because a hold-open device that never releases has failed its first duty. What the hardware on the leaf must do is covered in our fire door hardware guide.
Seals, gaps and the closer: the three parts that work together
A smoke seal only works where the gaps are right. FD30S pairs 30 minutes of integrity with a smoke seal to BS EN 1634-3, to Sa for ambient temperature smoke and S200 for smoke at 200 degrees Celsius, and the gap around the leaf must stay at 4 mm, because a wider gap lets smoke past the seal whatever the seal itself can do. Intumescent seals expand at roughly 200 to 250 degrees, closing the gap around the leaf as the fire heats the door, and a seal that is missing, painted over or cut short leaves a gap the fire can pass through.
Check the seals on the same visit as the closer, because a door with a working closer and a failed seal still fails its job. A smoke seal that has hardened lets smoke past the leaf, and a leaf that drags on the floor stops latching, so the check looks at the leaf, the gaps, the seals, the closer and the latch together. Our fire ratings guide sets out what each figure covers, and the checks that catch a failing leaf are in our fire door inspection checklist.
| Part | What to check | Failure |
|---|---|---|
| Closer | Power size, self-closing, opening force | Door stands open or too hard to open |
| Smoke seal | Sa or S200, intact, not painted over | Smoke passes the leaf |
| Gaps | 4 mm around the leaf | Seal cannot close a wide gap |
| Hold-open device | Release on alarm to BS EN 1155 | Door never releases |
Put the closer, the seals and the gaps on one line per opening, and record the work the day it is done, so the next inspection starts from the last one and not from scratch.
Checking smoke seals: the failures that make no noise
Smoke seals fail quietly. A brush that has flattened with age, a blade that has torn, or a section missing where a cable was run through the frame, all let smoke through while the door looks closed. Nothing rattles, nothing sticks, and the door still shuts, so the fault is only found by looking along the whole length of the seal.
Check the seals at every inspection, along their whole length, and look for light showing through the gap. If light shows through, the seals cannot work. A flattened brush, a torn blade or a missing section must be replaced with the same profile named in the test evidence.
Check the closer at the same time. A closer that has been disconnected after a delivery, a closer with a leaking body, or a closer adjusted so the leaf takes too long to close, all leave the door open to smoke. The inspection should test that the door closes and latches on its own, from any angle.
Keep the record. The Fire Safety (England) Regulations 2022 ask for checks on communal doors every three months and on flat entrance doors every year, and the record should name the door, the fault, the date it was found and the date it was fixed. Our fire door inspection checklist gives the checks that catch a failing leaf before it matters.
The seal that has slipped: what the check finds first
A smoke seal fails quietly, and the check finds it before the fire does. The seal must meet the frame all round, because smoke moves faster than flame and reaches the corridor before the fire does, so the check runs a finger along the seal at every door, and a seal that has slipped from its groove or come away at a corner is noted against the door on the day it is found.
The gap beside the leaf is part of the seal, because a leaf that drags leaves a gap the smoke passes through. The gap is kept to 4 mm, so the leaf swings free and the seal meets the frame all round, and a leaf that has sunk on its hinges is lifted before the gap grows wider than the seal can close.
Paint laid over a seal stops it swelling when the heat comes, and the check looks for paint on the seal as well as wear. Heat near 200 to 250 degrees makes the intumescent seal swell and close the gap the leaf leaves, so a seal coated in paint is stripped and replaced, not painted over again.
The closer is checked with the seal, because a leaf that does not shut is a smoke door that holds nothing. BS EN 1154 sets EN 3 as the smallest power a fire door closer may take, and the test is simple: open the leaf and watch it shut on its own, and a closer that has lost its pull is adjusted or replaced before the next visit.
The record the check leaves: what the file must hold
Each check leaves a note, and the note lists the seal, the gap and the day for every door the round covered. The note shows which doors were fixed and which still wait, so the repair is booked while the fault is still small, and the next reader of the file can see the state of every door at a glance.
The note stays with the building file, and the file is the one the building shows when the doors are asked about. A door fixed without a note in the file is a door whose proof no one can show, so the note goes in on the day of the repair, not at the end of the month.
| Part | What to check | What breaks it | When |
|---|---|---|---|
| Seal | Meets the frame all round | Slipped from its groove | Each check |
| Gap | 4 mm, leaf swings free | Leaf sunk on its hinges | Each check |
| Paint | None on the seal | Seal coated in paint | Each check |
| Closer | EN 3 minimum, shuts on its own | Closer lost its pull | Each check |
| Record | Door, seal, gap, day | Repair with no note | On the day |
What each visit should cover is set out in the fire door inspection checklist, and the doors that must hold both fire and forced entry are covered in the security door maintenance checklist. The rules for the shared parts of a public building are set out in the fire door regulations commercial buildings guide, and sizes and fitting for closers are worked through in the fire door closers guide.
Ordering a smoke control door: one doorset, one set of evidence
Ordering a smoke control door is a specification exercise. The order should name the fire class and the smoke class together, FD30S or FD60S with Sa or S200, and it should name the leaf, the frame, the seals, the closer and the hardware as one doorset. A leaf ordered on its own, with the seals and hardware to follow, is a doorset with no evidence behind it.
The seals must be listed by name and profile, not as a line that says seals. The smoke seal profile, the intumescent strip, the closer power size to BS EN 1154, the hinges to BS EN 1935 and the handle grade to BS EN 1906 should all appear on the order, with the test report number beside them. Our how to specify security doors guide covers the same discipline for rated security doors.
The security side needs its own evidence where the door must also resist attack. A lock is not a security rating, and a steel leaf is strong but strength is not a rating. Security comes from a separate test, LPS 1175 or PAS 24, on the whole doorset. Our dual certification guide works through how fire and security sit on one doorset, and our fire rated steel doors page covers the leaf that carries both ratings most often.
Order the evidence with the doors. The test report, the classification and the hardware schedule should arrive with the doorset, and the handover pack should name the inspection routine the building will follow. A building that files the evidence on the day the doors arrive has a record it can use for the whole life of the building.
| Door position | Smoke class | What it must do | What to check |
|---|---|---|---|
| Flat entrance door | Sa (FD30S) | Hold smoke and flame inside the flat | Smoke seals, closer, 4 mm gaps |
| Corridor door | Sa | Keep the escape route clear of smoke | Seals along whole length, latch |
| Stair core door | Sa or S200 | Protect the stair while people come down | Smoke seals, closer, latch |
| Lobby and cross-corridor door | Sa | Hold smoke in one part of the corridor | Seals, closer, gaps |
| Plant room door | S200 | Hold hot smoke inside a higher-risk room | Seals, gaps, self-closing |
A fire rating on its own does not prove smoke control. Ask for the smoke class by name.
What is the difference between Sa and S200?
Sa covers smoke leakage at ambient temperature, and S200 covers leakage at 200 degrees, both tested to BS EN 1634-3 and classified to BS EN 13501-2. Sa is the smoke a person meets in a corridor at the start of a fire, and S200 is the hotter smoke that reaches a door later, or close to the fire. The fire strategy names the class for each opening.
Does a fire door need smoke seals?
Only where the fire strategy asks for smoke control, and corridors and stair cores usually do, because smoke reaches people long before flames do. A door that must control smoke carries an S in its rating, FD30S or FD60S. A fire rating on its own does not prove smoke control, so ask for the smoke evidence by name.
What is the difference between a smoke seal and an intumescent seal?
A smoke seal is a flexible brush or blade that blocks cold smoke from the moment the door closes. An intumescent seal expands at roughly 200 to 250 degrees and closes the gap in a fire. One works cold and the other works hot, and many doors carry both in one combined profile.
Why does a smoke control door need a closer?
Because a smoke seal only works when the door is shut. The closer, sized to BS EN 1154 for the leaf, closes the leaf and holds the latch every time. A door that stands open has no smoke performance, whatever its certificate says, and the self-closing device is part of the requirement.
How often should smoke seals be checked?
At every fire door inspection, along their whole length. The Fire Safety (England) Regulations 2022 ask for checks on communal doors every three months and on flat entrance doors every year. A flattened brush, a torn blade or a missing section must be replaced with the same profile named in the test evidence.