Smoke Control Doors Explained

Smoke control doors explained: Sa and S200 to BS EN 1634-3, smoke seals against intumescent seals, and the doors that must hold cold smoke back.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

A smoke control door is a fire door with one extra duty: it must stop cold smoke passing around its edges from the moment it closes. Fire kills, but smoke kills first, and cold smoke spreads through a building long before the fire reaches the door. A door that holds flames for 60 minutes and lets smoke through its gaps has failed the people on the other side, because smoke reaches them first.

The difference is a separate test. Fire performance is tested to EN 1634-1, and smoke leakage is tested to BS EN 1634-3, classified to BS EN 13501-2. The two tests ask different questions, and a pass in one says nothing about the other. The S in a rating such as FD30S marks the smoke side, and it must be named in the specification where the fire strategy needs it.

The hardware that makes it work is ordinary: a closer sized to BS EN 1154, hinges to BS EN 1935, a smoke seal that is a brush or a blade, and gaps kept to 4 mm. Our fire door hardware guide sets out the hardware set, and our fire rated steel doors page covers the leaf that most smoke control doors are built on.

  • SaSmoke leakage tested at ambient temperature, BS EN 1634-3
  • S200Smoke leakage tested at 200 degrees C, BS EN 1634-3
  • FD30S30 minutes integrity plus smoke control
  • BS EN 1634-3The smoke leakage test standard

Cold smoke travels before the flames arrive

Smoke from a fire is hot at the source, but by the time it reaches a corridor door it has cooled, thinned and spread. It moves along corridors, up stair cores and through gaps around a leaf that looks closed. A person on the far side of the door meets the smoke first, and the smoke takes the air they need before the flames are anywhere near them.

That is why the fire strategy treats smoke as its own problem. A compartment wall that holds fire for 60 minutes is no use if smoke passes its doors in the first minutes, because the escape route fills while the fire is still in the room where it started. The doors on the escape route must hold smoke as well as fire, and the rating must name both.

Intumescent seals cannot do this job. They expand at roughly 200 to 250 degrees, and cold smoke arrives long before the temperature at the door reaches that point. The seal that stops cold smoke is a different strip altogether, fitted and working from the moment the door closes.

Sa and S200: reading the smoke class

BS EN 1634-3 is the test for smoke leakage. A doorset is fitted in a frame, the door is closed, and smoke is drawn past it while the leakage is measured. The test is run at ambient temperature for the Sa class, and at 200 degrees for the S200 class. The classification is given to BS EN 13501-2.

Sa covers smoke at ambient temperature, which is the smoke a person meets in a corridor at the start of a fire. S200 covers smoke at 200 degrees, which is the hotter smoke that reaches a door later, or on a route close to the fire. A doorset classified E30Sa carries 30 minutes of integrity with ambient smoke control. A doorset that also carries S200 has shown it can hold smoke at the higher temperature too.

The class to specify follows the fire strategy, not the catalogue. Corridors and stair cores usually need Sa, because the smoke that reaches them first is cold. A door close to a high-risk room, or on a route where the fire strategy expects hot smoke, may need S200. Ask the fire engineer which class the strategy names for each opening, and specify that class by name.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

The S in FD30S: what the suffix proves

In UK trade shorthand the suffix S marks smoke control: FD30S is a 30-minute door with smoke control, and FD60S is a 60-minute door with smoke control. The number is the fire period, the letter S is the smoke class, and both must be proved on the same doorset.

The suffix proves nothing on its own. It is a claim that the doorset was tested to BS EN 1634-3 with the leaf, the frame, the seals and the hardware that will be fitted on site. A door with an S in its name and a different seal fitted on site has left its evidence behind.

Ask for the test report that names the smoke class beside the fire class. The report should state the standard, the class and the construction it was tested on, and the doorset on site should match that construction part for part. If any part is missing from the evidence, the smoke rating is unproven.

FD30S is the normal requirement for a flat entrance door opening onto common parts, self-closing, with smoke seals, under Approved Document B. The period comes from the fire strategy for the building, not from the security rating, and the two never trade against each other.

Smoke seals and fire seals: two strips, two jobs

A smoke seal is a flexible brush or blade fitted around the leaf edge or in the frame. It blocks smoke at normal temperature from the moment the door closes, because it is already touching the frame. It works cold, it works from the first second, and it works every time the door shuts.

An intumescent seal is a strip that expands when heat arrives, closing the gap around the leaf in a fire. It does nothing about cold smoke, because it only expands when the temperature reaches roughly 200 to 250 degrees. By then the smoke has already passed.

Many doors carry a combined fire and smoke seal, with the intumescent strip and the smoke brush in one profile. The two parts sit side by side and each does its own job. The combined profile must be the one named in the test evidence, fitted in the position the evidence names.

A smoke seal replaced with a generic draught strip is a change to the tested assembly. Draught strips are made to stop draughts, not smoke, and they have no test evidence behind them. Replace a worn smoke seal with the same profile, not with whatever is on the shelf.

Where smoke control is needed: corridors, stairs and lobbies

Smoke control is needed where people escape, and where people wait. Corridors are the first place, because every escape route runs along a corridor and the doors off it must hold smoke while the corridor fills with people. A corridor door without smoke control lets smoke into the very route people must use to get out.

Stair cores come next. A stair is the route from every floor to the ground, and smoke in a stair core takes the escape route from the whole building at once. The doors to a stair core need the smoke class the fire strategy names, and the seals must be intact, because a stair door that leaks smoke is a stair that cannot be used.

Lobbies and cross-corridor doors matter for the same reason. A lobby door holds smoke in the room where the fire started and keeps the corridor clear for the people behind it. A cross-corridor door divides a long corridor into parts, so smoke in one part does not reach the other. Our fire door regulations for commercial buildings guide covers the duties behind these doors.

Flats show the rule at its clearest. A flat entrance door opening onto common parts is normally an FD30S doorset, self-closing, with smoke seals, because the stay-put strategy depends on the door holding smoke and flame inside the flat while other residents stay where they are. Our flat entrance doors guide covers that doorset in full.

The closer, the gaps and the door that must shut itself

A smoke seal only works when the door is shut. A door that stands open, or a door that closes but does not latch, has no smoke performance at all, whatever its certificate says. The self-closing device is part of the requirement, not an optional extra, and the door must shut fully from any angle.

The closer must be sized to BS EN 1154 for the leaf, so it closes the leaf and holds the latch every time. A closer sized below the leaf will not close it against air pressure or a draught from a corridor, and a closer that has been adjusted by hand, or taken off because it was too stiff, will leave the leaf standing open. Our fire door closers guide sets out the power sizes and how to read them.

The gaps around the leaf are kept to 4 mm, because the seals can only close a gap they were tested with. A leaf that has dropped on its hinges, or a frame that has moved, leaves a gap the smoke seal cannot bridge. A gap gauge is a small tool and a quick check, and it belongs in the hand of whoever walks the building.

Hold-open devices need care too. A door held open during the day needs a hold-open device to BS EN 1155 that releases the door when the alarm sounds. A wedge, a chair or a hook on the wall has no such release, and a door held open by one of those will stand open in a fire, smoke and all.

A smoke door that stands open is no smoke door

Smoke travels before the flames arrive, and a smoke door only works when it is shut. A door wedged open, a closer that cannot pull the leaf shut or a hold-open device that never releases on the alarm all leave the corridor open to smoke, and the escape route fills while the fire is still in the next room. The closer is the part that decides whether the door shuts, so the closer power size belongs on the schedule beside the fire period, because the two are set together: the period names what the door must hold and the closer names what shuts it.

BS EN 1154 sets closer power sizes from EN 1, for a 750 mm leaf at 20 kg, up to EN 7, for a 1,600 mm leaf at 160 kg, with a minimum of EN 3 on a fire door. A closer set too strong puts the door outside the access rules, because BS 8300 and Approved Document M cap opening force at below 30 N through the first 30 degrees and below 22.5 N beyond that. A closer set too weak leaves the door standing open, and a fire door standing open is a hole in the compartment wall. The power sizes and the adjustments that keep a closer inside the rules are listed in our fire door closers guide.

A corridor door held open during the day needs a hold-open device to BS EN 1155 that releases on the alarm. Put the release on alarm on the schedule beside the door, and test the release on the inspection round, because a hold-open device that never releases has failed its first duty. What the hardware on the leaf must do is covered in our fire door hardware guide.

Seals, gaps and the closer: the three parts that work together

A smoke seal only works where the gaps are right. FD30S pairs 30 minutes of integrity with a smoke seal to BS EN 1634-3, to Sa for ambient temperature smoke and S200 for smoke at 200 degrees Celsius, and the gap around the leaf must stay at 4 mm, because a wider gap lets smoke past the seal whatever the seal itself can do. Intumescent seals expand at roughly 200 to 250 degrees, closing the gap around the leaf as the fire heats the door, and a seal that is missing, painted over or cut short leaves a gap the fire can pass through.

Check the seals on the same visit as the closer, because a door with a working closer and a failed seal still fails its job. A smoke seal that has hardened lets smoke past the leaf, and a leaf that drags on the floor stops latching, so the check looks at the leaf, the gaps, the seals, the closer and the latch together. Our fire ratings guide sets out what each figure covers, and the checks that catch a failing leaf are in our fire door inspection checklist.

Part What to check Failure
Closer Power size, self-closing, opening force Door stands open or too hard to open
Smoke seal Sa or S200, intact, not painted over Smoke passes the leaf
Gaps 4 mm around the leaf Seal cannot close a wide gap
Hold-open device Release on alarm to BS EN 1155 Door never releases

Put the closer, the seals and the gaps on one line per opening, and record the work the day it is done, so the next inspection starts from the last one and not from scratch.

Checking smoke seals: the failures that make no noise

Smoke seals fail quietly. A brush that has flattened with age, a blade that has torn, or a section missing where a cable was run through the frame, all let smoke through while the door looks closed. Nothing rattles, nothing sticks, and the door still shuts, so the fault is only found by looking along the whole length of the seal.

Check the seals at every inspection, along their whole length, and look for light showing through the gap. If light shows through, the seals cannot work. A flattened brush, a torn blade or a missing section must be replaced with the same profile named in the test evidence.

Check the closer at the same time. A closer that has been disconnected after a delivery, a closer with a leaking body, or a closer adjusted so the leaf takes too long to close, all leave the door open to smoke. The inspection should test that the door closes and latches on its own, from any angle.

Keep the record. The Fire Safety (England) Regulations 2022 ask for checks on communal doors every three months and on flat entrance doors every year, and the record should name the door, the fault, the date it was found and the date it was fixed. Our fire door inspection checklist gives the checks that catch a failing leaf before it matters.

The seal that has slipped: what the check finds first

A smoke seal fails quietly, and the check finds it before the fire does. The seal must meet the frame all round, because smoke moves faster than flame and reaches the corridor before the fire does, so the check runs a finger along the seal at every door, and a seal that has slipped from its groove or come away at a corner is noted against the door on the day it is found.

The gap beside the leaf is part of the seal, because a leaf that drags leaves a gap the smoke passes through. The gap is kept to 4 mm, so the leaf swings free and the seal meets the frame all round, and a leaf that has sunk on its hinges is lifted before the gap grows wider than the seal can close.

Paint laid over a seal stops it swelling when the heat comes, and the check looks for paint on the seal as well as wear. Heat near 200 to 250 degrees makes the intumescent seal swell and close the gap the leaf leaves, so a seal coated in paint is stripped and replaced, not painted over again.

The closer is checked with the seal, because a leaf that does not shut is a smoke door that holds nothing. BS EN 1154 sets EN 3 as the smallest power a fire door closer may take, and the test is simple: open the leaf and watch it shut on its own, and a closer that has lost its pull is adjusted or replaced before the next visit.

The record the check leaves: what the file must hold

Each check leaves a note, and the note lists the seal, the gap and the day for every door the round covered. The note shows which doors were fixed and which still wait, so the repair is booked while the fault is still small, and the next reader of the file can see the state of every door at a glance.

The note stays with the building file, and the file is the one the building shows when the doors are asked about. A door fixed without a note in the file is a door whose proof no one can show, so the note goes in on the day of the repair, not at the end of the month.

Part What to check What breaks it When
Seal Meets the frame all round Slipped from its groove Each check
Gap 4 mm, leaf swings free Leaf sunk on its hinges Each check
Paint None on the seal Seal coated in paint Each check
Closer EN 3 minimum, shuts on its own Closer lost its pull Each check
Record Door, seal, gap, day Repair with no note On the day

What each visit should cover is set out in the fire door inspection checklist, and the doors that must hold both fire and forced entry are covered in the security door maintenance checklist. The rules for the shared parts of a public building are set out in the fire door regulations commercial buildings guide, and sizes and fitting for closers are worked through in the fire door closers guide.

Ordering a smoke control door: one doorset, one set of evidence

Ordering a smoke control door is a specification exercise. The order should name the fire class and the smoke class together, FD30S or FD60S with Sa or S200, and it should name the leaf, the frame, the seals, the closer and the hardware as one doorset. A leaf ordered on its own, with the seals and hardware to follow, is a doorset with no evidence behind it.

The seals must be listed by name and profile, not as a line that says seals. The smoke seal profile, the intumescent strip, the closer power size to BS EN 1154, the hinges to BS EN 1935 and the handle grade to BS EN 1906 should all appear on the order, with the test report number beside them. Our how to specify security doors guide covers the same discipline for rated security doors.

The security side needs its own evidence where the door must also resist attack. A lock is not a security rating, and a steel leaf is strong but strength is not a rating. Security comes from a separate test, LPS 1175 or PAS 24, on the whole doorset. Our dual certification guide works through how fire and security sit on one doorset, and our fire rated steel doors page covers the leaf that carries both ratings most often.

Order the evidence with the doors. The test report, the classification and the hardware schedule should arrive with the doorset, and the handover pack should name the inspection routine the building will follow. A building that files the evidence on the day the doors arrive has a record it can use for the whole life of the building.

Door position Smoke class What it must do What to check
Flat entrance door Sa (FD30S) Hold smoke and flame inside the flat Smoke seals, closer, 4 mm gaps
Corridor door Sa Keep the escape route clear of smoke Seals along whole length, latch
Stair core door Sa or S200 Protect the stair while people come down Smoke seals, closer, latch
Lobby and cross-corridor door Sa Hold smoke in one part of the corridor Seals, closer, gaps
Plant room door S200 Hold hot smoke inside a higher-risk room Seals, gaps, self-closing

A fire rating on its own does not prove smoke control. Ask for the smoke class by name.

What is the difference between Sa and S200?

Sa covers smoke leakage at ambient temperature, and S200 covers leakage at 200 degrees, both tested to BS EN 1634-3 and classified to BS EN 13501-2. Sa is the smoke a person meets in a corridor at the start of a fire, and S200 is the hotter smoke that reaches a door later, or close to the fire. The fire strategy names the class for each opening.

Does a fire door need smoke seals?

Only where the fire strategy asks for smoke control, and corridors and stair cores usually do, because smoke reaches people long before flames do. A door that must control smoke carries an S in its rating, FD30S or FD60S. A fire rating on its own does not prove smoke control, so ask for the smoke evidence by name.

What is the difference between a smoke seal and an intumescent seal?

A smoke seal is a flexible brush or blade that blocks cold smoke from the moment the door closes. An intumescent seal expands at roughly 200 to 250 degrees and closes the gap in a fire. One works cold and the other works hot, and many doors carry both in one combined profile.

Why does a smoke control door need a closer?

Because a smoke seal only works when the door is shut. The closer, sized to BS EN 1154 for the leaf, closes the leaf and holds the latch every time. A door that stands open has no smoke performance, whatever its certificate says, and the self-closing device is part of the requirement.

How often should smoke seals be checked?

At every fire door inspection, along their whole length. The Fire Safety (England) Regulations 2022 ask for checks on communal doors every three months and on flat entrance doors every year. A flattened brush, a torn blade or a missing section must be replaced with the same profile named in the test evidence.

Specifying a smoke control door?Send the door schedule and the fire strategy for a tested doorset quotation.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →