Smoke fills a building before the flames reach it, and the people inside need time to leave. A wide opening that cannot take a fire door leaves smoke a way through the building, so the opening takes a curtain that drops and holds the smoke back while people move out.
A smoke curtain is not a fire curtain in a lighter fabric. It is proved to EN 12101-1 for smoke containment, and the proof names the smoke it holds back, not the fire. A curtain ordered as a smoke curtain must carry the proof a smoke curtain needs.
The fire curtains that hold flames back to EN 1634-1 take a different fabric and a different proof, and the opening that needs both takes the proof for both. The smoke control doors guide covers the doors that hold smoke back while people move past them, and the fire door regulations commercial buildings guide sets out the periods for the shared parts of a public building.
- EN 12101-1Smoke containment proof
- Gravity dropThe curtain that falls without power
- Sa / S200Smoke seals to BS EN 1634-3
- One scheduleEvery curtain on one line
Wide openings and the smoke they let through: what a smoke curtain must do
An atrium, a warehouse bay and a shop front each hold an opening no leaf can span, and the opening must stay clear through the day for people, trolleys and forklifts. A smoke curtain hangs above the opening in a box, out of sight while the building is in use, and drops when the alarm sounds.
The curtain must meet the floor and both guides without a gap, because smoke slips through any opening the fabric leaves, and a curtain that stops short of the floor leaves the smoke a way under it. The width, the height and the way the opening is used belong on the order beside the curtain.
The doors that guard the smaller openings are set out in the fire door regulations commercial buildings guide, and the fire rated sliding doors guide covers the doors that close a wide opening another way. A curtain ordered without the fire strategy it belongs to may land in the wrong opening.
Why smoke reaches people first: the case for containment
Smoke travels faster than flames and fills the air people breathe, so a building that holds fire and lets smoke through holds only half the line. Smoke containment gives people the time to leave, and the curtain that holds smoke back is the closure that buys that time.
Fire doors take smoke seals proved to BS EN 1634-3, Sa for smoke at room temperature and S200 for smoke at 200 degrees Celsius, and the curtain follows the same rule: its edge must meet the guides and the floor with no gap the smoke can slip through.
Atriums take smoke curtains because the smoke from a fire below rises into the open space and spreads across every floor. The curtain drops across the opening and holds the smoke on the floor where the fire started, so the floors above stay clear while people leave. The fire door regulations warehouses guide sets out the periods for the shared parts of a warehouse.
The fabric and the seal: what a smoke curtain is proved against
The fabric of a smoke curtain is proved against smoke alone. The test runs smoke at the fabric the way a fire would, and the fabric must hold it back without letting it through the weave or round the edges, because a curtain that leaks smoke holds nothing.
The proof is a figure for smoke containment to EN 12101-1, and the figure belongs on the order beside the curtain, because a curtain proved at one temperature carries a different proof from one proved at another.
The proof covers the curtain as one build, fabric, guides and box together, so a fabric changed after the test leaves the curtain without the proof it was ordered with. The test report names the curtain as it was tested, and the curtain that arrives must match it. The fire rated windows guide covers the windows that share the same wall.
The drop and the release: how a smoke curtain closes
The curtain falls on its own weight when the hold lets go, so no power is needed to close the opening. A magnet or a motor holds the fabric up in its box through the day, and the alarm cuts the hold. The bottom bar carries the fabric down, and the guides at each side keep it on its line.
The fall is slowed by a brake, because a curtain that drops too fast can strike a person below it, while a curtain that drops too slowly leaves the opening open while smoke spreads. The brake is set when the curtain is fitted, to the speed the order names.
The detector that calls the curtain must sit where the smoke will reach it first, and the wiring between the detector and the release belongs on the order beside the curtain. A curtain whose detector sits in clean air hears nothing until the smoke has already passed the opening. The fire rated roller shutters page covers the shutters that drop over a shop front, and a curtain drops over an opening the same way, without the steel leaf.
The way out past a dropped curtain: escape routes that stay open
People leave through the routes the building gives them, and a curtain that has dropped across a route must still let them through. The way out cannot wait for the curtain to rise, so the curtain on a route takes a form that leaves people a way past it, or the route takes no curtain at all.
A staged drop holds the fabric partway down, leaving a gap at the bottom for people to pass under while the smoke above is held back. The height of the gap is set on site, and the floor beside the curtain is marked so people know where to pass.
The doors on the same route take panic bars to BS EN 1125, and each bar must work with the lock beside it, so the leaf opens for a crowd even when the power has gone. The hardware beside the leaf is covered in the fire door hardware guide, and the curtain on the same route is checked on the same round.
Smoke curtains beside fire doors: the two closures on one wall
The curtain and the door on one wall belong to the same fire strategy, so they belong on the same schedule. A wall where the door carries FD60 and the opening beside it carries a curtain proved for smoke only is a wall with a hole in it where fire is concerned, because the fire moves to the weakest part.
Every opening in the wall is named in the fire strategy, with the door or the curtain beside each one, and the dual certification guide works through two proofs on one leaf. The curtain beside that leaf takes the same line on the schedule, with the opening, the closure and the proof on one row. The fire and security doors dual certification guide works through how two proofs share one leaf.
A curtain ordered without the doors beside it may land in the wrong opening, so the curtain, the door and the proof are named together on the order. The choice between leaf materials is worked through in the steel versus timber fire doors guide, and the curtain that guards the opening beside those leaves takes its proof from the same fire load.
Fire and smoke on one opening: when one curtain must hold both
Where one opening must hold both fire and smoke, the order takes a curtain proved for both, or two curtains hung side by side. A fire curtain holds the flames back to EN 1634-1, a smoke curtain holds the smoke back to EN 12101-1, and the opening that needs both takes the proof for both.
The smoke seal on a fire door is proved to BS EN 1634-3, and the curtain takes the same idea: the edge of the fabric must meet the guides and the floor without a gap the smoke can slip through. The roller shutter cost factors guide works through the same kind of climb in price for shutters that drop over a shop front.
Two curtains side by side take two boxes, two releases and two lines on the schedule, so the order names each one beside the opening it closes. A single curtain proved for both takes one box and one line, and the proof it carries names both the fire and the smoke it holds back. The keeping an LPS 1175 rating valid guide sets out what breaks a rating once a door is fitted.
One curtain cannot span the whole opening, so two hang side by side
A wide opening takes more than one curtain, because a single fabric cannot span the whole width and still drop true. Two hang side by side, each in its own box, each with its own guides and its own release, and the two together close the opening the way one closes a narrow one. Each one is proved on its own, and the order names each beside the opening it closes, with the proof it carries, so the drop that arrives matches the opening it guards. Smoke containment to EN 12101-1 gives the figure the order must carry beside each one.
The two must drop together, on the same alarm, because one that drops while its neighbour stays up leaves the opening half open and the smoke passes through the half that stayed up. The wiring for both releases belongs on the order beside the pair, so both hear the same alarm on the same circuit, and the test drops both at once, so the round sees them fall together. Each box sits above its half of the opening, and the fitter checks the boxes sit level, because a box that hangs out of level lets the fabric run down crooked and catch in the guides. Doors that hold smoke back as people move past them are listed in the smoke control doors guide, and shared parts of a public building take the period the fire door regulations guide for commercial buildings states.
| Drop | What it closes | What the round checks |
|---|---|---|
| Left drop | Left half of the opening | Fabric, guides, release |
| Right drop | Right half of the opening | Fabric, guides, release |
| Join in the middle | Gap between the two | Overlap, seal, no gap |
| Both releases | Whole opening at once | Drop together on test |
Test the join the way the smoke would test it
The join in the middle is where the smoke will try first, because any opening the fabric leaves is a way through, and a join with no overlap is an opening the smoke can use. The two fabrics must overlap at the join, or a seal must close it, so the smoke meets fabric all the way across the opening and finds no way through. The overlap is looked at on the round, with the pair down, because a join that looks shut from the floor may stand open at the top, and the bottom bars must meet the floor on the same line, so neither one stops short of the other. A bar that lands crooked is straightened on the spot, because a crooked bar pulls the fabric down out of true. Each visit follows the fire door inspection checklist, and how two proofs share one opening is taken up in the dual certification guide.
Two hold the opening only when the join holds too, and the schedule that names the join beside each one is the schedule the fitter can follow. The fire rated sliding doors guide takes the doors that shut a wide opening in another way, and the periods for warehouse shared parts come from the fire door regulations warehouses guide, so the opening, the pair and the join all sit on one line.
The detector that calls the curtain must hear the smoke first
A smoke curtain drops when the detector calls it, so the detector must sit where the smoke will reach it first. The detector sits above the opening, on the side the fire would start, because smoke rises and spreads across the ceiling, and a detector that sits in clean air hears nothing until the smoke has already passed the opening. The height of the ceiling, the draught from the doors and the machines that stir the air all decide where the detector hears first, and the position is set on the plan before the detector is fitted. A detector that sits too high hears the smoke late, because the smoke cools and spreads before it reaches the ceiling, and a detector that sits too low hears the draught from the doors instead.
A detector that calls too often is soon ignored, and a detector that calls too late is no use at all. The wiring between the detector and the release belongs on the order beside the curtain, because a curtain whose detector sits on a different circuit may never hear the alarm. The smoke control doors guide lists the leaves that keep smoke back as people move past them. The fire door regulations commercial buildings guide states what period a public building’s shared parts must carry.
| Detector position | What it hears | What goes wrong |
|---|---|---|
| Above the opening | Smoke as it rises | Nothing, if the ceiling is clear |
| On the fire side | Smoke before it passes | Nothing, if the side is right |
| In clean air | Smoke too late | Curtain drops after the smoke passes |
| Beside the curtain | Draught, not smoke | False calls, then ignored calls |
A curtain that has dropped once is checked before it rises again
A curtain that has dropped, on a test or on a real alarm, is checked before it rises again. The fabric is looked at for creases, because a crease in the fabric may stop it dropping cleanly next time, and the guides are looked at for damage where the fabric ran down them. The bottom bar must sit straight, because a bar that has bent will not pull the fabric down true, and the release must be set again by the person who fitted it, not by the person who found it down. The guides are cleaned of dust before the curtain rises, because dust in the guides can slow the next drop, and the bottom bar is wiped clean of anything that stuck to it while it sat on the floor.
The check after a drop is written against the opening the same day, with the fabric, the guides and the release each named, and the next round starts from that record, so no curtain is raised and forgotten until the alarm calls it again. The fire door regulations warehouses guide carries the periods for a warehouse’s shared parts, the fire door inspection checklist notes what each visit should look for, and the dual certification guide sets out how two proofs share one leaf, while the fire rated sliding doors guide covers the doors that shut a wide opening another way.
Every curtain on the order: the schedule that names them all
The order for a building’s curtains is one list, and each opening on the building takes a line of its own, with the curtain, the proof and the release named beside it. A list that names one curtain for every opening leaves the fitter to choose, and a curtain chosen on site is a curtain without a proof.
Every line of the quotation is checked against that list before the order goes out, so no curtain, guide or release is missed from the price. A part missed from the price still has to be bought, and fitting it to an opening already in use costs more than ordering it with the building. The columns the list needs are set out in the how to specify security doors guide, and the fire door closers guide covers the sizes and the fitting of closers.
The round that looks after the curtains walks the building in turn, opening by opening, and looks at the fabric, the guides, the box and the release on each one. A fault found on the round is written against the opening it belongs to the same day, and the fire door inspection checklist names what each visit should look for. The security door maintenance checklist covers the doors that must hold both fire and forced entry.
| Position | Curtain | Proof | What to check |
|---|---|---|---|
| Atrium | Smoke curtain | EN 12101-1 | Fabric, guides, drop |
| Warehouse bay | Smoke curtain | EN 12101-1 | Fabric, guides, release |
| Shop front | Smoke curtain | EN 12101-1 | Fabric, guides, bottom bar |
| Corridor | Smoke curtain | EN 12101-1 | Fabric, guides, drop |
| Stair core | Fire and smoke curtain | EN 1634-1 + EN 12101-1 | Release, guides, gap |
A smoke curtain is only as good as the fabric that drops, the guides that hold it and the proof that stands behind it, so the proof, the release and the drop belong on one line of the order.
What is a smoke curtain?
A fabric closure that drops from a box above a wide opening when the alarm sounds, holding smoke back for its proof.
How is a smoke curtain proved?
To EN 12101-1 for smoke containment. The proof names the smoke the curtain holds back.
What is the difference between a smoke curtain and a fire curtain?
Smoke curtains hold smoke back, proved to EN 12101-1, while fire curtains hold fire back, proved to EN 1634-1.
Can a smoke curtain sit on an escape route?
Only when the way out stays open, through a staged drop that leaves a gap at the bottom or a gap beside the curtain for people to pass through.
Who checks the curtains?
The person who runs the building walks the round that covers every opening, and each fault is written against the opening it belongs to before the visit ends.