A walk-in centre fills its waiting room with patients who arrived with no appointment, and the fire rules for the building follow the rooms behind each leaf. The entrance, reception and the waiting room take FD30, and the treatment rooms, the drugs store, the staff office and the plant room take FD60, because the rooms behind the front hold the care, the medicines, the records and the plant, and those rooms ask for a longer hold than the route out.
FD carries a number that counts minutes, and the minutes come from EN 1634-1, which runs from 30 to 120. A leaf marked E held flame on its own, a leaf marked EW held flame with some of the heat, and a leaf marked EI held flame with the heat as well, so the number counts the minutes and the letter says what stayed back.
A walk-in centre follows the same fire rules as any other building where patients move slowly and no one knows the way out, and the period on each leaf follows what sits behind it and how fast the people behind it can move. The fire door regulations GP surgeries guide covers the fire rules for a surgery that books its patients in, and the fire door regulations pharmacies guide covers the rooms of a building that holds a counter and a dispensary, while a walk-in centre sets its leaves by the waiting room and the treatment rooms behind them.
- FD30 / FD60Fire periods to EN 1634-1
- Waiting roomWhere FD30 holds the room clear
- Sa / S200Smoke ratings to BS EN 1634-3
- One listEvery centre door named
Seven rooms in a walk-in centre: the period each leaf takes
Seven rooms make up a walk-in centre, and the period follows what each room holds. Patients come in through the entrance, give their names at reception, wait in the waiting room, and the treatment rooms hold the examination and the care, the drugs store holds the medicines, the staff office holds the records, and the plant room keeps the building running.
FD60 sits on the treatment rooms, the drugs store, the staff office and the plant room, because the care, the medicines, the records and the boards behind those leaves need sixty minutes before flame reaches them. FD30 sits on the entrance, reception and the waiting room, because the people on that route reach the street in far less than thirty minutes.
Each opening is written on its own line of the order, with the leaf and the period beside it, so no leaf is hung on guesswork. The table sets out the seven rooms with the period each one takes and the grade beside the period, so the fitter matches each leaf to its own line as it is hung.
| Room | Period | Grade | What to check |
|---|---|---|---|
| Entrance | FD30 | B3 | Leaf, glass, closer |
| Reception | FD30 | B3 | Leaf, glass, closer |
| Waiting room | FD30 | B3 | Leaf, glass, closer |
| Treatment rooms | FD60 | C5 | Leaf, lock, seals |
| Drugs store | FD60 | D10 | Leaf, lock, seals |
| Staff office | FD60 | C5 | Leaf, lock, seals |
| Plant room | FD60 | C5 | Leaf, lock, seals |
What the two periods hold back in a walk-in centre
A fire period counts the minutes the doorset earned in its test, and the doorset means the leaf, the frame, the fixings and the lock proved as one. The order writes that period beside the leaf. The fire door certification guide names what the report behind a period must hold.
One doorset in the centre can carry the fire proof and the forced entry proof in a single report. The fire minutes come from EN 1634-1, the forced entry grade in B3, C5 and D10 comes from LPS 1175 Issue 8.2 of September 2024, and the fire and security doors dual certification guide shows the pair proved on the same leaf.
FD60 on the treatment rooms, drugs store, staff office and plant room
Behind the treatment room leaf sits a patient mid-treatment, so the leaf takes FD60 and stays shut whenever the clinician is working inside. Sixty minutes is the hold the room asks for, because flame that reaches it takes the patient and the care with it.
The plant room holds the boards and the equipment that keep the lights, the heating and the air moving, and its leaf takes FD60 because the boards behind it feed the whole centre. The plant room fire doors guide covers the leaves of a plant room in full.
Behind the drugs store leaf sit the medicines, so the leaf takes FD60 and stays shut and locked whenever no one is working inside. The staff office leaf takes FD60 as well, because the patient records behind it cannot be remade once flame reaches them. The leaf on each room is shut each time the last person leaves, because an open leaf holds back no flame at all.
The waiting room: FD30 to hold the room clear
Patients in the waiting room move slowly when the alarm sounds, because some of them are unwell, some lean on a stick and some have never used the building, so the waiting room leaf takes FD30 to hold the room clear while staff reach the seats. Thirty minutes is more than staff need to clear a room of waiting patients, and the leaf gives them that time with the room still clear of flame.
Staff see the waiting room through a glazed panel in the leaf, so the leaf stays shut while the patients are watched. The panel goes through the test with the leaf round it, so the report names the glass, the bead and the fixings together. Which panels a fire leaf may carry is named in the fire door vision panels guide, and the steel vs timber fire doors guide puts the two leaf materials beside each other.
The waiting room leaf carries FD30 beside the grade the room demands, and its hardware was proved with the leaf, so no fitting fitted later takes the period off it.
What the waiting room leaf holds back while the queue leaves
People arrive at a walk-in centre without an appointment, and none of them knows the building. The waiting room leaf holds FD30, and that half hour is what the staff need to bring a full room out in order, seat by seat, with no crush at the leaf. The leaf is shut whenever the room is full, and it opens only for the patients who are called through. While the queue leaves through one side, flame is held on the other, and the room stays clear of flame until the last patient is out.
A glazed panel in the leaf lets staff watch the waiting room without opening it, so the room stays watched and the leaf stays shut. Glass, bead and fixings are proved with the leaf round them, and the report names them together, so a panel fitted afterwards cannot take the period off the leaf. The vision panels guide lists which panels may sit in a fire leaf and what proof they carry.
The reception leaf is worked one-handed, because a patient who leans on a stick has a single hand free. BS 8300 and Approved Document M set the limit at 30 N while the leaf opens through its first 30 degrees, then 22.5 N for the rest of the swing, so a light hand moves the leaf even though it carries FD30. The closer guide lists the sizes a leaf takes when it is opened a hundred times a day.
| Leaf | Period | What it holds |
|---|---|---|
| Waiting room | FD30 | Flame off the queue |
| Reception | FD30 | Flame off the route out |
| Treatment rooms | FD60 | Flame off the care inside |
| Drugs store | FD60 | Flame off the medicines |
The reception leaf is opened one-handed while a patient leans on it
On any route that serves more than 60 people, the leaves on the way out take a BS EN 1125 bar, and it spans at least six tenths of the leaf it sits on. A patient who reaches the leaf with a queue behind opens it in a single push, and the bar needs no supply to work. The panic hardware guide explains what the bar must do when a queue presses against the leaf.
Smoke reaches the patients on their way out ahead of flame, so the leaves they pass carry a smoke rating as well as a fire period. The two ratings sit in BS EN 1634-3: Sa holds smoke at room temperature, S200 holds it at 200 degrees, and a seal guards the route only where it meets the frame without a break. How the route leaves hold smoke back while patients file past is set out in the smoke control guide.
The route to the street is marked at every turn and kept free of anything standing on it, so a patient who has never been in the building finds the way out without stopping. The signage guide follows the signs a first-time patient reads on the way to the street, and the security door enquiry checklist takes the centre list, room by room, with the period beside each leaf.
Entrance and reception: FD30 on the route patients use
Both the reception leaf and the entrance leaf take FD30, because patients pass through them on the way out. Half an hour is more time than the people on that route need to reach the street.
A push bar proved to BS EN 1125 runs across the leaves on the way out wherever the route serves more than 60 people, and the bar covers no less than 60 percent of the leaf width. A patient reaching the leaf with people behind them opens it with one push, and the bar works whether the supply to the building is on or off. The panic hardware guide sets out what the bar must do when people push against the leaf, and the emergency exit doors guide covers the leaves on the way out.
The alarm may sound while patients who have never used the building sit in the waiting room, so the route to the street is signed at every turn. Nothing stands on the route. A leaf on the way out must still open to a push from a patient leaning on a stick, and BS 8300 with Approved Document M puts the push below 30 N through the first 30 degrees of swing and below 22.5 N beyond that.
Smoke in the waiting room: Sa and S200 beside the period
Patients leaving the waiting room meet smoke before flame, so the leaves on the way out carry a smoke rating beside their fire period. The two smoke ratings come from BS EN 1634-3, Sa for smoke at room temperature and S200 for smoke at 200 degrees. How the route leaves keep the smoke back while the patients move past them is worked through in the smoke control doors guide.
A leaf that needs to stand open while the centre is busy is held by a device proved to BS EN 1155, and the device lets the leaf go on its own the moment the alarm sounds. How the leaves hold the line between one part of the centre and the next is named in the fire compartmentation guide, and a wedge under a leaf gives it no period at all while it stands open, so the wedge is never the device that holds a fire leaf.
The closer, the seals and the gaps: what the period rests on
An FD60 leaf gives its hour only when the closer shuts it, the seals meet the frame and the gaps stay narrow, because flame passes through a leaf left ajar in seconds and through a wide gap soon after. The closer carries a proof to BS EN 1154, EN 1 stands as the smallest power size the standard names, and EN 3 is the lowest size a fire door takes.
Heat at the frame makes the seal grow across the gap once the temperature passes 200 degrees and before it reaches 250, and the swollen seal blocks flame and hot gas from slipping past the leaf. Round a hung leaf the gap is 4 mm, and a gauge held against it on the monthly walk shows at once when the gap has opened wider than that figure. The intumescent seals guide covers fitting the seal, the fire door closers guide covers what the closer must do, and the fire door gaps guide covers measuring the gaps.
The hinges on a fire leaf are proved to BS EN 1935, grade 13 through 200,000 cycles under a leaf of 120 kg and grade 14 through 200,000 cycles under a leaf of 160 kg, so the hinge suits the weight of the leaf it carries. What each sign on a fire door must say is named in the fire door signage guide.
The latch wears a little more before the closer pulls the treatment room door shut
A treatment room door in a walk-in centre is opened and shut between every patient through the clinic, so the latch works harder here than on any other door in the building. Each pass takes a little more off the latch, and the closer must still pull the door shut after it. The wear shows first as a door that needs a push to catch, then as a door that will not catch at all.
The treatment rooms take FD60, and that hour is what the care inside needs while the next patient waits outside. A glazed panel in the door lets staff watch the room without opening it, with glass, bead and fixings proved with the door round them. The vision panels guide sets out which panels may sit in a fire door and the proof they carry.
The opening beside a hung door is four millimetres, wide enough for the door to swing clear between patients and tight enough for the seal to shut it. Heat does the work on the seal: intumescent material grows with heat, swelling past 200 degrees and closing the opening beside the door by 250. A strip that has slipped from its groove opens that gap to flame, so the gap is gauged while the latch is checked. The gap guide sets out the figure to check with the gauge against the door.
| Part | Wear through a clinic day | Check between patients |
|---|---|---|
| Latch | Loses its catch a little each pass | Door catches without a push |
| Closer | Pull weakens under constant use | Door meets the frame alone |
| Seal | Strip works free of its groove | Strip seated, unpainted, unbroken |
| Hinge | Works loose under daily use | Door swings free without dragging |
What the latch gives back is a door that will not stay shut
Under BS EN 1154 closer sizes run from EN 1 to EN 7, and EN 3 is the smallest size a fire door is given, so the size is fixed room by room and written on the order beside each door. A closer given too small a size will not pull a treatment room door shut after a hundred openings a day, and a latch that has worn past its catch cannot hold it once it arrives. The two are checked together. The closer guide lists the sizes a door takes when it is opened again and again through the clinic.
Flame is not the first danger for patients on their way out; smoke reaches them ahead of it, so the doors they pass take a smoke rating beside a fire period. Sa holds smoke at room temperature and S200 holds it at 200 degrees under BS EN 1634-3, and the seal is the part that makes either rating hold on the route. The smoke control guide sets out how the route doors hold smoke back, and the maintenance guide names the work that keeps a treatment room door shutting through the year.
The centre list is sent to the enquiry checklist room by room, with the period, the latch and the closer beside each door, so the room that turns patients over all day still shuts between every one of them.
The walk-in centre fire door order: every leaf, its period and its proof
The whole fire door order sits on one list, with a line for every opening that names the leaf, the period, the lock and the closer beside it. One leaf named for the whole centre leaves the fitter to guess.
Each leaf on the order is read before the order is signed, because a closer that arrives after the doorset holds the job up, and a leaf with no line beside it cannot be checked on arrival. What the order must hold for every door is named in the how to specify security doors guide.
The clinician in charge takes the door list round the centre each month and works each leaf in turn. A dragging leaf, a closer that leaves the leaf standing open or a seal that has been painted over is written beside its own door the day it is found, so the fault is put right before the leaf is asked to hold. What to look for on each leaf is set out in the fire door inspection checklist, and the fire door maintenance guide covers the work that keeps the leaves holding.
The period on a walk-in centre leaf follows the room behind it, so the FD60 and FD30 leaves sit on the same list as the grade and the lock for each leaf.
What period should a walk-in centre drugs store door carry?
FD60 to EN 1634-1, because the medicines sit behind the drugs store leaf, and sixty minutes is the hold that room asks for.
What period should a waiting room door carry?
FD30 to EN 1634-1, because the waiting room leaf holds the room clear while staff reach the patients, and half an hour is the hold that room demands.
Can one leaf hold fire and forced entry?
Yes, where a single leaf was proved against fire and against forced entry, so one report names the period and the grade together.
Do walk-in centre fire doors need a smoke rating?
Yes, Sa or S200 to BS EN 1634-3 sits beside the period on the leaves of the way out, because smoke reaches the patients leaving before flame does.
What happens when a fire door will not shut?
A leaf that will not shut goes beside its own door on the list the day the fault is found, and the centre does not wait for the next look round before the leaf is put right.