Panic Hardware

Panic hardware for escape routes: bars and push pads to BS EN 1125, opening force limits, the closer beside the bar, and the monthly check on every door.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

A crowded room needs a door that opens for everyone at once, and panic hardware is the part that makes it open. A bar across the leaf, pushed by anyone in the crowd, throws the latch and lets the door swing, and it works for a child, an older person or someone carrying a bag, because it asks for a push and nothing more.

The hardware sits on the escape routes, where the building empties in a fire. Stands, halls, schools, hospitals and shops all fill with people who do not know the building, and the bar is the part they find without being told. A door without it on a crowded route is a door that holds the crowd inside.

The rules a panic bar must meet are set out in the fire door regulations stadiums guide, and the Martyn’s Law guide for premises sets out the duties a venue carries by the number of people it holds.

  • BS EN 1125Panic hardware for escape routes
  • 60% of leaf widthMinimum bar width
  • 30 N / 22.5 NOpening force limits
  • FD30 / FD60Fire resistance periods tested to EN 1634-1

The bar across the leaf: how panic hardware opens a door

A panic bar runs across the leaf, and the standard behind it is BS EN 1125, which asks for a bar that covers at least 60 percent of the leaf width. The bar belongs on the doors of rooms that hold more than 60 people, because a crowd that cannot open the door in a fire is a crowd held inside. Push the bar anywhere along its length and the latch throws, so the crowd opens the door by leaning on it.

The bar works because it is simple. There is no key, no code and no card between the crowd and the street, and the door opens for the first person who reaches it. A bar that needs a firm grip or a twist to work is not panic hardware, and it should not sit on an escape route.

Fit the bar at a height every person in the crowd can reach, and check that it runs free along its full length. A bar that catches on the frame or drags on the floor will not throw the latch when the crowd leans on it, and the fire door hardware guide covers the grades and the parts behind a working fire door.

Push pads and touch bars: the hardware for smaller rooms

A room that holds fewer people takes a push pad or a touch bar instead of a full panic bar. The pad sits where a hand falls naturally, and a push on it throws the latch, so the door opens for one person at a time without the length of a bar across the leaf.

Push pads suit the doors on offices, shops and corridors, where the traffic is steady but the crowd is small. They take less room than a bar, they suit a narrower leaf, and they still open without a key, a code or a card, which is what an escape route needs.

Choose the hardware for the room, not for the door. A pad on a stand door would leave a crowd pushing at a small target, and a bar on a store room door would waste a leaf that only one person uses at a time. The commercial buildings fire door regulations guide sets out the periods for the shared parts of a public building.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

Opening force: the push a child or an older person can make

A bar is only as good as the push it asks for. The limit is 30 N for the first 30 degrees of travel and 22.5 N beyond, under BS 8300 and Approved Document M, and the limit is set so that a child or an older person can open the door with one hand. A bar that takes more force than that leaves the weakest people in the crowd behind.

Check the force with a gauge on the round, and check it on the door as it stands, with the closer fitted and the seals in place. A door that opens easily on its own can grow stiff once the closer is adjusted, and a closer that is too strong turns a bar that should open with a push into a bar that needs a shove.

The force belongs on the order beside the bar, and it should be written on the schedule line for each door. A bar ordered without a force limit leaves the fitter to guess, and a door that takes too much force to open is a door that holds the people who need it most. The fire door regulations schools guide works through the periods for a school, where the force matters most.

Panic hardware beside the closer: the door that shuts and releases

A panic bar and a closer share the same leaf, and they must work together. The closer pulls the leaf shut after the crowd has passed, and the bar must still throw the latch the moment someone pushes it, even while the closer holds the leaf against the frame.

Closers on a fire door need a power size of EN 3 or above to BS EN 1154, with the size chosen for the leaf fitted. A closer that is too strong fights the bar, and a closer that is too weak leaves the leaf standing open. The fire door closers guide covers the sizes and the fitting.

Doors that stay open through the day take a hold-open device to BS EN 1155, which releases the leaf the moment the alarm sounds. A wedge under the leaf does the same job badly, because it holds the door open when the alarm sounds and no one is there to kick it away. Test the release on the round by sounding the alarm and watching the leaf shut.

The bar that answers every hand: the push that opens the leaf

A panic bar runs across the leaf so the hand that reaches it in the dark finds it without looking, and one push throws the latch. Under BS EN 1125 the bar runs across at least 60 percent of the leaf, so the bar is found by a shoulder, an elbow or a hip as well as a hand, and the leaf opens for the person who reaches it however they reach it.

The push must work for a child, an older person and a person with bags in both hands, so the opening force sits below 30 N through the first 30 degrees and below 22.5 N beyond that, to BS 8300 and Approved Document M. A bar that needs a hard shove fails the people who must pass through it in a hurry, and the force is checked at handover.

The bar belongs where more than 60 people gather on the far side of the leaf, because a crowd reaches the door together and the leaf must open for all of them at once. Halls, stands and crowded rooms take the bar, and the leaf beside them takes the closer that brings it home after the crowd has passed.

The bar and the closer work as a pair, because the closer shuts the leaf and the bar releases it, and a closer set too strong fights the bar. The leaf is checked by opening it and letting it go, then pressing the bar and watching the latch throw, so the pair is proved together on every round.

The latch that must throw: the strike, the bar and the leaf that will not open

The latch must throw fully into the strike every time the leaf shuts, because a latch that catches only halfway leaves the leaf free to swing open when the fire comes. The strike is set so the latch sits fully in it, and a leaf that has dropped on its hinges shows first as a latch that will not throw, so the hinges are put right before the strike is moved.

A push pad suits the smaller room, where fewer people pass and the leaf is narrower, because the pad is pressed by the hand that reaches it and a bar would take more of the leaf than the room needs. The pad is set at hand height on the side the people leave from, where it is found without looking, and it throws the same latch the bar would throw.

A bar on a fire door keeps its proof only where the bar, the leaf and the frame were proved together, because the fire test proves the doorset as one assembly. A bar swapped on site for one never tested in the leaf breaks the proof the doorset was ordered with, and the replacement should match the model the test report names, with the same fixings and the same bar.

Each month the bars and pads are tried in turn, a few leaves each visit, so none goes untried for long. A bar that sticks, a pad that has worked loose or a latch that will not throw is written against its door on the day it is found, with the part and the date beside it, and the repair is booked while the fault is still small.

Part What to check What breaks it When
Bar Runs 60 percent of leaf Too short to find At handover
Pad At hand height, firm Works loose Each round
Latch Throws fully into strike Leaf dropped Each round
Strike Set for full throw Set too far out At handover
Closer Shuts leaf, bar releases Set too strong Each round

What the lock the key turns must do is named in the fire door hardware guide, and the sizes and fitting for closers are worked through in the fire door closers guide. Readers, releases and wiring beside a leaf are covered in the door entry systems guide, and what each visit should look for is set out in the fire door inspection checklist.

Where panic hardware belongs: stands, halls and crowded rooms

Panic hardware belongs on every door on an escape route that serves a crowd. Stands, sports halls, school halls, hospital corridors and shop floors all fill with people who do not know the building, and each of those rooms needs a door that opens for a push.

Venues carry duties under Martyn’s Law by the number of people they hold: a standard tier from 200 to 799 people, and an enhanced tier at 800 and above. A stadium sits in the enhanced tier, and its fire strategy must show the routes the crowd takes and the doors that release them. The fire door regulations leisure centres guide covers the doors in a centre that holds crowds every day.

Rooms that fill for the evening need the bar most. A hall that holds a concert, a restaurant that fills for dinner and a school hall that fills for assembly each put a crowd against the door, and the fire door regulations restaurants guide covers the doors in a restaurant where the crowd sits down to eat.

Panic hardware on a fire door: the proof that must stay together

A panic bar on a fire door must be the bar the test report names, because the leaf, the frame, the seals and the bar were proved together to EN 1634-1. A bar swapped for another after the test leaves the doorset different from the one tested, and a doorset that differs from the test has no proof.

The period follows the fire load behind the door, with FD30 for most rooms and FD60 where the load is heaviest, and the letters E, EW or EI name what the furnace measured. A door on a smoke path takes FD30S, with the seal proved to BS EN 1634-3, to Sa for smoke at room temperature and S200 for smoke at 200 degrees Celsius.

Smoke must not pass the door while the crowd moves through it, so the seal must be the one the test report names, and the gap round the leaf must stay at 4 mm. The smoke control doors guide covers the doors that hold smoke back while people move past them, and the fire and security doors dual certification guide works through how the two proofs share one leaf.

The monthly check: what to test on every bar and pad

Test every bar and pad once a month, on the same walk that checks the doors. Push the bar along its full length and feel whether it runs free, watch the latch throw, and check that the leaf swings open without catching on the frame or the floor.

Check the fixings that hold the bar to the leaf, because a bar that works loose will not throw the latch when the crowd leans on it. Tighten what has worked loose, and swap any part that has cracked or bent, with the same part the test report names, so the doorset stays as it was tested.

Write down what the check found, with the door named and the date noted, so the next walk starts from a record that is complete. The fire door inspection checklist names what each round should look for, and the security door maintenance checklist covers the doors that must hold both fire and forced entry.

The hardware order: bars, pads and the doors they sit on

Put the hardware order together as one list, with a line for every door on the escape routes and the bar or pad each one takes beside it. A list that names the doors but not the hardware leaves the fitter to guess, and a guess is not a plan. The how to specify security doors guide sets out the columns a schedule needs, and the hardware belongs on one of them.

Check each quote against the schedule before ordering, so every bar, pad and closer on the list is priced on the quote. A bar left off the quote still has to be bought, and fitting it to a door that is already in place costs more than ordering it with the door. The security door cost factors guide works through what each step up the scale adds to the build.

Keep the test reports with the doors from the day they arrive, so the proof is never far from the leaf it belongs to. The keeping an LPS 1175 rating valid guide sets out what breaks a rating once a door is fitted, and the steel versus timber fire doors guide works through the choice between leaf materials.

Position Hardware Proof What to check
Stand exit Panic bar BS EN 1125 Opening force Release, bar, closer
School hall Panic bar BS EN 1125 Opening force Bar, latch, seals
Office corridor Push pad Release Pad, latch, closer
Shop floor Push pad Release Pad, latch, gap
Hospital corridor Touch bar Release on alarm Bar, seals, closer

Panic hardware must open for a push from anyone in the crowd, so the bar, the force and the release must all sit on the same schedule.

What is panic hardware?

A bar or pad that throws the latch when pushed, so the door opens for a crowd without a key, a code or a card. Panic bars to BS EN 1125 cover at least 60 percent of the leaf width and suit rooms that hold more than 60 people.

When is panic hardware needed?

On every door on an escape route that serves a crowd: stands, sports halls, school halls, hospital corridors and shop floors, where the people inside do not know the building.

What opening force should a panic bar need?

Below 30 N for the first 30 degrees of travel and below 22.5 N beyond, under BS 8300 and Approved Document M, so a child or an older person can open the door with one hand.

Can panic hardware sit on a fire door?

Yes, where it is the bar the test report names. The leaf, the frame, the seals and the bar were proved together to EN 1634-1, and a bar swapped for another after the test leaves the doorset different from the one tested.

Who checks panic hardware?

The person who runs the building, on the monthly walk that checks the doors. Push every bar along its full length, watch the latch throw, and write down what the check found with the door named and the date noted.

Specifying panic hardware for a crowded building?Send the door schedule and the rooms each door serves for a tested door quotation.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →