Fire Door Rules for UK Hospices

A hospice holds people who cannot move quickly beside rooms that hold drugs and plant, so each door takes the fire period that its room demands.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

A hospice is a building of bedrooms, a reception and a drugs store behind one entrance, and the fire rules for the building follow the rooms behind each leaf. The bedrooms hold people who cannot move quickly, the drugs store holds the controlled drugs, and the staff office and the plant room hold the keys and the boards.

EN 1634-1 is the test that counts the fire minutes on a hospice leaf. FD30 means thirty minutes and FD60 means sixty, and the letter beside the minutes says what the leaf held back: E for flames alone, EW for flames with some heat held back and EI for flames with the heat held back.

A hospice follows the same rules as any other building where the people inside cannot move quickly. The fire door regulations care homes guide covers the fire rules for a home where residents live for years, and the care-home detail is not repeated here, while the fire door regulations hospitals guide covers the rooms behind a hospital ward.

  • FD30 / FD60Fire periods to EN 1634-1
  • BedroomsWhere the slow move out starts
  • Sa / S200Smoke ratings to BS EN 1634-3
  • One listEvery hospice door named

Five hospice rooms and the period that protects each one

Five parts make up a hospice, and the period follows what each part holds. The entrance and the reception hold the families coming in, the drugs store holds the controlled drugs, the staff office holds the keys and the rotas, and the plant room keeps the building running.

FD60 sits on the drugs store, the staff office and the plant room, because those rooms need sixty minutes before the fire reaches them. FD30 sits on the entrance and the reception, because the families on that route can move to the street in far less than thirty minutes.

Every opening in the hospice gets a line of its own on the order, with the leaf and the period written beside it, so no leaf is hung on guesswork. The fire door regulations hospitals guide covers the fire rules for a building where patients also move slowly, and the fire door regulations GP surgeries guide covers the rooms behind a surgery waiting room.

Position Leaf Period What to check
Drugs store Steel leaf FD60 Leaf, lock, seals
Staff office Steel leaf FD60 Leaf, lock, seals
Plant room Steel leaf FD60 Leaf, lock, seals
Reception Glazed leaf FD30 Leaf, glass, closer
Entrance Glazed leaf FD30 Leaf, glass, closer

What FD30 and FD60 hold back in a hospice

The minutes on a leaf come from the test, and the doorset that earns them is the leaf, the frame, the fixings and the lock proved as one. What the report states is what the order writes beside the leaf, so the leaf that arrives is the leaf the room asked for.

Some leaves in the hospice must hold fire as well as forced entry, and one doorset carries both proofs in one report. The fire minutes come from EN 1634-1 and the forced entry grade from LPS 1175 Issue 8.2 of September 2024, in B3, C5 and D10, and the fire and security doors dual certification guide shows how the two proofs sit on the same leaf. How the letters and the minutes go together is set out on the fire ratings standard page.

Smoke reaches the people on the way out before flame does, so the leaves on the route carry a smoke rating beside their fire period. BS EN 1634-3 names the two ratings, Sa for smoke at room temperature and S200 for smoke at 200 degrees, and the smoke control doors guide works through how the route leaves keep the smoke back while families move past them.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

The drugs store, the staff office and the plant room: FD60 behind shut leaves

Behind the drugs store leaf sit the controlled drugs the hospice runs on, so the leaf takes FD60 and stays shut when no one is drawing up a dose. Sixty minutes is the hold the room asks for, because the drugs behind it cannot be replaced.

The staff office holds the keys, the rotas and the papers, and its leaf takes FD60 for the same reason, because the keys behind it are what the hospice opens with each day. A leaf that stands open through the night holds nothing back, so the staff office leaf is shut each time the last person leaves the room.

The plant room holds the boards and the equipment that keep the lights and the heating running, and its leaf takes FD60 because the boards behind it feed the whole hospice. The plant room fire doors guide takes the leaves of a plant room in full, and the plant room door requirements guide takes the doors that guard the plant.

Bedroom doors in a hospice: the leaf beside the bed

A hospice bedroom is where a person spends their last days, so the leaf on it must shut on its own and hold fire for thirty minutes while help reaches the bed. The bedroom leaf takes FD30, because the person inside cannot move quickly and the leaf must hold the corridor clear long enough for help to arrive.

The lock on a bedroom leaf takes a thumb turn on the bedroom side, so the person inside can leave without a key, and a key on the corridor side, so staff can open the leaf from the corridor. A glazed panel in the leaf lets a nurse look in without opening it, and the panel is proved with the leaf round it. The fire door vision panels guide covers the panels a fire leaf may carry.

Bedroom leaves are opened and shut through the night as nurses check on the people inside, so a leaf that is wedged open holds nothing back when the alarm sounds. Only a hold-open device proved to BS EN 1155 may hold a bedroom leaf open, because it lets the leaf shut on its own when the alarm sounds, and a wedge is not a hold-open device.

The entrance and reception: FD30 on the route visitors use

Families stand at the reception desk and move to the street through the entrance, so both leaves take FD30. Thirty minutes is more than the families need to leave, and the route behind the leaves is short.

Where the route serves a crowd, a bar proved to BS EN 1125 sits across at least 60 percent of the leaf width, so a visitor who reaches the leaf in a crowd opens it with one push. What the bar must do for a crowd pushing against the leaf is covered in the panic hardware guide, and the leaves on the way out are covered in the emergency exit doors guide.

A glazed panel in the reception leaf lets the staff see the families waiting without opening the leaf, and the pane is proved with the leaf round it. The steel vs timber fire doors guide sets the two leaf materials beside each other.

Getting residents out: the slow route from the bedroom to the street

When the alarm sounds, the people in the bedrooms cannot walk fast, so the route out is planned round beds and chairs rather than people on their feet. The corridor from each bedroom runs straight to the stair or the exit, with no turn a bed cannot take, and nothing stands in it.

Staff move the residents along the route, and the leaves on the way must open with one push from hands full with a bed or a chair. The force to open a leaf on the route stays below 30 N for the first 30 degrees and below 22.5 N beyond them, to BS 8300 and Approved Document M, so a nurse pushing a bed can open the leaf without stopping.

Under Martyns Law, premises fall into tiers by the number of people they hold, one tier for 200 to 799 people and a higher tier at 800 and above, and the Martyns Law guide for premises sets out what each tier asks for. Whether a hospice sits in a tier turns on the number of people in the building, so the count is checked before the tier is named. Royal Assent came in April 2025 and the go-live is expected in spring 2027, so the route is planned now.

Closers, seals and gaps on hospice doors: the parts that wear first

The gap round a hung leaf is measured with a gauge, and a hinge or a frame that has shifted shows up as a gap that has grown past 4 mm. When heat of 200 to 250 degrees reaches the seal in the groove, the seal swells until it closes the gap, and paint over the seal stops it swelling, so the seal is looked at with the gap.

A fire door closer takes at least EN 3, the smallest power size the rules allow, and the leaf it serves must shut on its own from whatever angle it is opened to. BS EN 1154 runs the power sizes from EN 1, for a leaf 750 mm wide and 20 kg in weight, up to EN 7, for a leaf 1,600 mm wide and 160 kg in weight.

The hinges that carry the leaf come from BS EN 1935, where grade 13 is proved for 200,000 cycles at 120 kg and grade 14 for 200,000 cycles at 160 kg. What the hardware on a fire leaf must do is covered in the fire door hardware guide, and the closers are covered in full in the fire door closers guide.

The hospice fire door order: every leaf, its period and its proof

Every opening in the hospice gets a line on the order, with the leaf, the period, the lock and the closer written beside it. A single leaf named for the whole hospice leaves the fitter to guess, and a leaf in the wrong room holds fire for the wrong time.

Before the order is signed, each leaf on it is checked, because a closer ordered after the doorset arrives holds the job up, and a leaf with no line beside it cannot be checked when it arrives. What the order must hold for every door is covered in the how to specify security doors guide.

The faults that show first are a leaf that will not shut, a closer that leaves the leaf standing open and a seal that has been painted over, and each one is written against its own door on the day it is found. What to look for on each leaf is covered in the fire door inspection checklist, and the work that keeps the leaves holding is covered in the fire door maintenance guide.

The period on a hospice leaf means nothing on its own, so the leaf, the closer and the seal are ordered together and checked together against the room behind the leaf.

What period should a hospice fire door carry?

FD60 for the drugs store, the staff office and the plant room, and FD30 for the entrance and the reception, each proved to EN 1634-1.

Can one leaf hold fire and forced entry?

Yes, where the same doorset passed the fire test and the forced entry test together, so the period and the grade are named in one report.

Do hospice fire doors need a smoke rating?

Yes, Sa or S200 to BS EN 1634-3 sits beside the period on the route leaves, because smoke reaches the people on the way out before flame does.

Who checks the hospice fire doors?

The hospice manager keeps the door list and looks over the leaves in turn, so a leaf that will not shut is found before the leaf is asked to hold.

What happens when a hospice fire door will not shut?

A leaf that will not shut is written up against its own door the day the fault is found, and the hospice does not wait for the next look round before the leaf is put right.

Specifying fire doors for a hospice?Send the door list and the period each room must hold for a tested door quotation.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →