10 steps to specify an LPS 1175 door
Ten steps to specify an LPS 1175 door: threat, rating, doorset, fixings, access control, fire, survey, evidence and handover, with the gaps rival guides miss.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
Start with the threat, then write the rating, the doorset, the fixings and the evidence into the specification. A door ordered by rating alone, with the frame, the hardware and the wall left to chance, has no tested performance to rely on. These ten steps close each gap in turn.
- A1 to H20LPS 1175 ratings, tool letter plus minutes
- B3, C5, D10The three levels most doors use
- Doorset, not leafThe rating covers the tested assembly
- Check the evidenceCertificate and schedule before ordering
Step 1: Name the threat before you name the rating
A rating is an answer to a threat, not a badge. Write down who might attack the door, with what tools, for how long, and what they gain if they get through. A rear door on a quiet yard faces a different threat from a front door on a busy street.
Time matters as much as tools. The rating is a delay: minutes of attack time against a defined tool set. Ask how long it takes for someone to notice, respond and reach the door, and write the threat down in one paragraph attached to the specification. That paragraph stops the common error of ordering the highest rating for every opening, which costs more and still fails if the frame is wrong. The LPS 1175 standards page sets out the scale, and the LPS 1175 Issue 8 guide explains how the rating is built from a tool letter and a time.
Step 2: Check whether the project needs LPS 1175 at all
Not every door needs LPS 1175. For new dwellings in England, Approved Document Q asks for secure doorsets, and PAS 24 is the usual route, with LPS 1175 accepted as an equivalent or better standard. For commercial doors, the driver is usually the risk assessment, the insurer or the client brief, so check what the insurer accepts in writing: a door that passes one test but not the named standard is a wasted order.
Approved Document Q is under review, and a proposed change would ask for an enhanced standard on existing buildings as well as new ones. It is yet to be consulted on, so check the current edition at the time you specify. The British Woodworking Federation summary of the proposed changes sets out the position, and the LPS 1175 versus PAS 24 guide compares the two routes.
Step 3: Treat leaf, frame and hardware as one tested unit
The LPS 1175 rating belongs to the complete doorset as tested: leaf, frame, fixings, glazing and hardware together. A rated leaf in an unrated frame is not a rated door.
Most rival guides skip this gap: they list rating levels and tool sets, then stop. The test attacks the assembly as built, so the specification must name the doorset reference, frame section, hinge positions, lock and glazing, all as tested.
Ask the supplier for the certificate and the schedule that lists what it covers. If any part of your door falls outside the schedule, the rating does not cover it. The guide to specifying security doors works through the same discipline.
Step 4: Match the rating to the opening, not the building
LPS 1175 Issue 8 rates a doorset by tool category letter plus minutes of attack time, from A1 to H20. A1 resists 1 minute against opportunist attack with basic hand tools, B3 resists 3 minutes against screwdrivers, pliers and hand saws, C5 resists 5 minutes against crowbars, drills and chisels, and D10 resists 10 minutes against sledgehammers, disc cutters and jigsaws.
Use the threat from step 1 to pick the level per opening: a staffed front entrance usually takes B3, a rear door facing a quiet yard usually takes C5, and a door protecting high value stock, plant or cash handling usually takes D10. A higher rating means heavier construction, so it should be earned by the threat, not ordered by default.
| Rating | Old name | Attack time | Tool examples |
|---|---|---|---|
| A1 | SR1 | 1 minute | Basic hand tools |
| B3 | SR2 | 3 minutes | Screwdrivers, pliers, hand saws |
| C5 | SR3 | 5 minutes | Crowbars, drills, chisels |
| D10 | SR4 | 10 minutes | Sledgehammers, disc cutters, jigsaws |
Compare the three middle levels in the SR2 versus SR3 versus SR4 guide. LPS 2081 is a related standard for doorsets and windows, rating at SRA for 1 minute and SRB for 3 minutes, and it suits lighter applications where LPS 1175 would be more than the threat needs.
B3, C5 and D10 on one schedule: naming the rating beside each opening
The rating on the schedule names the opening, not the building. A store that holds valuable stock takes a higher grade than a corridor door that only staff use, because the threat follows the room and the goods behind it, not the address on the front of the building.
LPS 1175 grades forced entry in minutes, with B3 holding three minutes against category B tools, C5 holding five minutes against category C tools and D10 holding ten minutes against category D tools, all under Issue 8.2, dated September 2024. The minutes name the test, not the time a thief needs in real life, so the grade should match the opening it guards. The grades in full are set out on our LPS 1175 page.
Write each opening on its own line, with the position, the rating and the hardware beside it. A schedule that names one rating for the whole building leaves the fitter to guess which door goes where, and a guess is not a proof. How a schedule should name each proof is set out in our how to specify security doors guide.
Measure the opening before the order is placed, because a leaf ordered to the wrong size leaves a gap the seals cannot close. The width, the height and the wall the frame fixes to all belong on the schedule beside the rating, so the door that arrives fits the opening it was made for.
The frame, the hinges and the lock carry the rating as much as the leaf does. Ask for hinges to BS EN 1935, grade 13 carrying 120 kg and grade 14 carrying 160 kg, each through 200,000 cycles, and a TS 007 3-star set, so the hardware is chosen for the leaf it carries.
Fire, acoustic and thermal needs sit on the same line beside the forced entry grade. A door that must hold fire takes FD30 or FD60 proved to EN 1634-1, and the two proofs sit side by side because each is proved on its own test, and one test report cannot prove both.
The tool set behind the grade: what each category allows
The tool set grows from one category to the next, and the grade follows it. A door that must face powered tools takes a higher grade than a door that faces hand tools alone, so the threat the opening faces should decide the grade, not the grade the catalogue shows first.
No published table maps LPS 1175 grades to EN 1627 classes, so never write RC3 beside B3 as if the two matched. Each standard is proved on its own test, and the order should name the standard the door was tested to, not a class borrowed from another one.
Ask for the test report before the door is made, with the rating, the doorset and the fixings named. A report that names the leaf alone leaves the frame and the fixings unproved, and the door that arrives is not the door that was tested. Keeping a rating valid means keeping the door as it was proved, and the checks that keep it alive are set out in our keeping an LPS 1175 rating valid guide.
| Opening | Rating | Hardware | Evidence |
|---|---|---|---|
| Store | LPS 1175 B3 | TS 007 3-star, grade 13 hinges | Test report names the doorset |
| Plant room | LPS 1175 C5 | TS 007 3-star, grade 14 hinges | Test report names the doorset |
| Strongroom | LPS 1175 D10 | TS 007 3-star, grade 14 hinges | Test report names the doorset |
| Corridor | LPS 1175 B3 | TS 007 3-star, grade 13 hinges | Test report names the doorset |
Put the rating, the tool set and the evidence on one schedule line, so the next reader can see what was tested and what holds it. The mistakes to avoid are set out in our security door specification mistakes guide.
Step 5: Fix the frame to a wall that can hold it
A rated doorset fixed into a weak wall is a weak door. The frame must be anchored with the fixings named in the tested design, in every position provided, and the wall itself must resist the same attack. Brick, blockwork, concrete and steel each need their own fixing method.
Ask what the tested design assumed for the substrate and compare it with the wall on site. If the wall is weaker, it needs work before the door arrives. Write the fixing type, size and positions into the specification, and ask the installer to record each fixing as fitted.
Glazing follows the same rule: a vision panel must be part of the tested doorset, with the glazing and beading as tested. A panel cut in after the test, or a different glass type, breaks the evidence. The installation page covers how a doorset should be fixed, and the specification mistakes guide lists the errors that undo a good rating.
Step 6: Keep access control inside the tested design
Electric locks, magnetic locks, keypads, fob readers, intercoms and panic hardware all change the doorset. If they were not part of the tested design, they can void the rating: a cable routed through the leaf, a lock keep moved to fit a reader, or a magnetic lock replacing a tested mechanical lock.
State every access control item at enquiry stage, not after the door is made, and ask the supplier to confirm in writing that each item is inside the tested design for that doorset reference. On escape routes, the hardware must also release in one action from the inside, without a key or a code. The security consultancy page covers the advice stage, where access control and the rating are settled together.
Step 7: Add fire, acoustic and thermal needs before you order
Many openings need more than forced entry resistance. A door on an escape route needs a fire rating to EN 1634-1: E for integrity, EW for integrity and radiation, or EI for integrity and insulation, at 30, 60, 90 or 120 minutes. The LPCB LPS 1056 scheme covers fire doors.
Both ratings must name the same doorset reference. A fire door with a security lock fitted afterwards, or a security door with a closer changed after the test, may have lost its evidence, because each test attacked the assembly as built. Ask for both certificates against the same reference.
Acoustic and thermal needs work the same way: name them before ordering, and ask for the test evidence for the same doorset. A door that meets the security rating but fails the acoustic target is still the wrong door. The fire ratings page explains the classifications, and the dual certification guide works through the detail.
Step 8: Measure the opening and the survey behind the quote
A quote is only as good as the survey behind it. Before accepting one, ask whether the survey measured the opening, the squareness of the reveal, the floor levels, the wall thickness and the condition of the surrounding structure.
Ask whether the survey checked for cables, pipes and drains where the fixings will go, and recorded the swing direction and the clear width. A door made to the wrong handing or clear width cannot be fixed on site without cutting the leaf, which voids the rating.
Ask for the survey notes with the quote, and check the sizes on them against the order. A mismatch found now costs a phone call; a mismatch found on site costs a remake.
Ask for the certificate number, then check it. Certified LPS 1175 products are listed on the LPCB Red Book, so a certificate number you can check beats a claim you cannot.
Step 9: Ask for the evidence before the door is made
Before the order is placed, ask for the test evidence and the certification schedule for the doorset as specified: certificate number, rating, sizes and configurations covered, and hardware listed. Check the certificate is current and the listing is live.
Ask for the same in writing for any second rating on the same doorset, and for the ironmongery schedule with each item named. If the supplier cannot produce the evidence, the door has no rating you can rely on.
Put the evidence requirement into the order itself: no evidence, no acceptance. That one line protects the buyer more than any later inspection. The guide to keeping an LPS 1175 rating valid explains what the evidence must cover.
Step 10: Check the handover, then keep the rating alive
At handover, check the door against the order: the doorset reference, the rating label, the sizes, the hardware and the fixings as recorded. Open and close it through its full arc, check it latches from any position, and check the closer shuts it fully. Record any snag before acceptance.
The rating can be lost after handover: changing a lock, cylinder, closer or hinge to a part outside the tested design voids the evidence, as does cutting the leaf for a cable route or a new vision panel. Any change needs written confirmation first.
Keep the certificate, the schedule, the survey notes and the handover record together, and set a routine to check the door, its fixings and its seals. The maintenance page covers what regular checks should include.
What is the difference between SR2 and B3?
None in performance. B3 is the Issue 8 name for the old SR2: 3 minutes against category B tools. Check which notation your insurer or brief uses, and write the rating in both forms so nothing is misread.
Does LPS 1175 cover the frame and the lock?
Yes, the rating covers the complete doorset as tested: leaf, frame, fixings, glazing and hardware together. If any part of your door falls outside the certificate schedule, that part is not covered.
Can I fit an electric lock to an LPS 1175 door?
Only if the lock, its keep and its cabling are inside the tested design for that doorset reference. State the access control at enquiry stage and ask for written confirmation before you order.
What voids an LPS 1175 rating after installation?
Changing a lock, cylinder, closer or hinge to a part outside the tested design, cutting the leaf for a cable route or a new vision panel, or changing the fixings or the glazing. Any change needs written confirmation first.
Do I need LPS 1175 or PAS 24?
PAS 24 is enhanced security for doors and windows and is the usual route for new dwellings under Approved Document Q. LPS 1175 is the higher standard, for commercial doors and higher risk openings. The risk assessment or the insurer decides.