Fire Door Rules for Colleges
A college fills with students between lessons, so each fire door takes its period from the room behind the leaf, from classroom to plant room.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
A college is a building where students move in crowds between lessons, carrying books and tools through corridors they know only by the timetable, and the fire doors stand between the teaching rooms and the corridors they use. Each leaf holds a fire where it starts while the students find the way out, and the period on the leaf follows the room behind it, because a classroom, a workshop and a plant room ask different things of the doors that guard them.
The fire rules for school buildings are set out in the fire door regulations schools guide, and the doors of a university are covered in the university security doors guide. A college sits between the two, with the crowds of a school and the workshops of a university, and its order names every door in the building, with the period and the hardware beside each one.
Before a single leaf is ordered the college sets down its fire plan, naming the period each opening must hold and the route each student must follow, and the order follows that plan door by door.
- FD30 / FD60Fire periods to EN 1634-1
- Sa / S200Smoke proof to BS EN 1634-3
- EN 3Smallest closer power to BS EN 1154
- One listEvery college door named
Classrooms, workshops and offices: one college, three periods
Three kinds of room share one college roof: classrooms full of students and desks, workshops full of tools and materials, and offices full of records and fees. The rules follow the rooms, because a leaf between a classroom and a workshop must hold fire back while the students on the other side find the way out.
The classrooms take the doors the students pass through between lessons, and each leaf must open for a student with books in hand who has never read the fire plan. The workshops take the doors the tutors open and the students never open alone, and each leaf must hold fire back where the tools and the materials sit.
The plan names each opening with its door, so a leaf ordered for the workshops never ends up guarding a classroom corridor.
FD30 and FD60 across a college: the periods each part takes
Each part of a college asks a different period of its doors, because the load behind each leaf is different. The classroom corridor holds students and desks, the workshops hold tools and fuel, and the plant room holds the machinery that serves the whole building, so the period is set by the room, never by the leaf alone.
A fire door takes its period from a test to EN 1634-1, where the leaf faces flames and heat and the minutes are counted. The proof is written as minutes beside letters, and the letters say whether the leaf stopped flames alone, flames with some heat, or flames with the heat as well.
The heavier leaf costs more to make and more to hang, because the frame must be deeper and the hinges stronger, so the figure climbs as the period climbs. Where the opening asks for 60 minutes, a 30-minute leaf is the wrong leaf, because the shortest proof in the wall is the one that gives way first.
The classroom corridor: students, lessons and the doors between them
The classroom corridor runs past every teaching room in the college, and the doors on it must hold their proof while letting students pass with books and bags all day. A glazed leaf lets a tutor see the corridor beyond it without opening the leaf, and the pane takes the same proof as the leaf, because the leaf and the glass are proved as one doorset.
The desks and the fittings in a classroom carry a fire load of their own, and the doors between the corridor and the workshops must hold the fire where it starts. The workshop side of that wall takes the period the workshops demand, because the fire that starts among the tools must stay among the tools while the students move out.
The windows that share the same wall are covered in the fire rated windows guide, and what the glass itself costs is worked through in the fire rated glass cost guide.
Workshops and stores: the doors behind the teaching rooms
The workshops take the heaviest fire load in the college, because the tools, the materials and the fuel sit there all day. A workshop leaf takes FD60, and the period follows the fire load, not the size of the room.
The stores beside the workshops take the same care, because the spares and the materials sit behind their doors. A stores leaf takes FD60 where the stores sit beside the workshops, because the fire that starts among the materials must not reach the teaching rooms.
A leaf on a workshop or a stores room often carries two proofs at once, because the rooms behind it need fire held back and an intruder held out. The forced entry side follows LPS 1175 Issue 8.2 of September 2024, with B3 holding three minutes, C5 five and D10 ten. The LPS 1175 vs PAS 24 guide puts the two ratings side by side, the keeping an LPS 1175 rating valid guide lists the faults that undo a rating after the door is fitted, and the fire and security doors dual certification guide explains how a single doorset holds both proofs at once.
The office and the plant room: what the back of the college must hold
The office holds the records and the fees, and the leaf that guards it takes the period the room beside it takes. An office leaf takes FD60 where the office sits beside the workshops, because the fire that starts among the tools must not reach the records.
The plant room takes the same care, because the machinery and the boards sit behind its doors all day, so its leaf takes FD60.
Leaves that must stand open through the teaching day take a hold-open device proved to BS EN 1155, which lets the leaf go the moment the alarm sounds. A chair wedged under a leaf is not a hold-open device, because the leaf it holds open cannot shut when the fire reaches it.
When the alarm sounds: the routes a full college uses
Once the alarm sounds, everyone in the college takes the route the building gives them, so the way out must be clear of anything in the way. Every door on that route opens at one push, with the power on or off, so no student waits for a key.
The doors on the route need a smoke rating as well as a fire period, and BS EN 1634-3 gives it: Sa where the smoke is at room temperature, S200 where it is at 200 degrees. Smoke moves faster than flame, so it reaches the students on the route ahead of the fire, and a seal holds only where it meets the frame all round. The smoke control doors guide works through how the doors hold smoke back while people move past them.
A route is only as strong as the leaf on it with the shortest proof, so each leaf on the route takes the period the route needs. One leaf proved for less than its neighbours gives way first, and the route goes with it. The fire door regulations leisure centres guide takes the same care with the visitors in a leisure centre.
| Position | Door | Period | What to check |
|---|---|---|---|
| Classroom corridor | Glazed leaf | FD30 | Leaf, glass, bar |
| Workshops | Steel leaf | FD60 | Leaf, lock, seals |
| Stores | Steel leaf | FD60 | Leaf, lock, seals |
| Office | Steel leaf | FD60 | Leaf, lock, seals |
| Plant room | Fire leaf | FD60 | Leaf, seals, gap |
| Public route | Fire leaf | FD30 | Leaf, bar, closer |
Closers, seals and gaps on college doors: what the period rests on
The closer on a college leaf works harder than the closer on most other doors, because students pass through it all day between lessons. Under BS EN 1154 the smallest closer power on a fire door is EN 3, and the check takes a moment: open the leaf and let it go, then watch it come home on its own. A closer that has lost its pull leaves the leaf standing open after the students have passed.
A 4 mm gap is left round the leaf, so it swings without catching and the seal meets the frame when the leaf shuts. The intumescent seal swells as the heat passes 200 degrees and closes that gap, unless paint over the seal holds it back. A seal that has slipped from its groove is written into the record against its own door on the day it is found, with the part and the date beside it.
The hinges carry the leaf through every opening of the day, and one that works loose lets the leaf drop until it drags and smoke slips through the gap above it. What the lock the key turns must do is set out in the fire door hardware guide, and the fire door closers guide covers sizes and fitting for closers.
Ordering for a college: one list, every door on it
The whole college order sits on one list, a line for every door with the leaf, the period, the lock and the closer beside it, so the door that arrives is the door each room asked for. A list that names a single leaf for the whole college leaves the fitter to guess which room takes which period, and a leaf fitted to the wrong room guards the wrong thing.
The college reads the quotation beside the schedule before anything is signed, line against line, because a door with no figure beside it still arrives with a charge, and a lock ordered on its own after the doorset was sent costs more than the same lock ordered with it. The how to specify security doors guide names the columns the list must hold, and the security door cost factors guide works through what each step up the scale adds to the price.
Each term the caretaker walks the college with the door list in hand, trying the leaves in turn from the entrance to the plant room. A leaf that drags, a seal out of its groove, or a closer that has lost its pull is written against its own door on the day it is found, and the repair is booked while the fault is still small. The record stays with the college file, and what the visit should cover is set out in the fire door inspection checklist.
On a college the period, the release and the closer decide together whether the classrooms, the workshops and the office hold, so all three sit on the same list before the order goes out.
What period should a college door carry?
FD30 or FD60, proved to EN 1634-1. The classroom corridor takes FD30 and the workshops take FD60, so the period follows the room the leaf guards, and the letters beside the minutes name what the doorset held back.
Can one leaf hold fire and forced entry?
Yes, where the fire test and the forced entry test were run on the same leaf, frame and seals, so a single report covers the pair.
Do college doors need panic hardware?
Yes, the leaf on the way out takes a panic bar proved to BS EN 1125, across at least 60 percent of the leaf, so one push throws the latch and the students behind it can get out.
What period should a workshop door carry?
A workshop leaf takes FD60, because the tools and the materials behind it carry the heaviest fire load in the college, and the stores beside the workshops take FD60 for the same reason.
Who checks the college doors?
The caretaker walks the round that covers every door, and each visit is written into the record the college keeps.