A car showroom holds visitors, fuel and high-value stock behind its doors, so each fire door takes its period from the room behind it and the way out.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

A car showroom is a public building where visitors walk among cars they have never sat in before, and the fire doors must hold the line and let people out. The leaf holds fire back for its period, and it opens for people who have never walked the route, so each door takes the period the room behind it demands.

The period on a showroom door follows the room behind the leaf, because the showroom floor, the workshop and the parts store ask different things of the doors that guard them. The order carries the period beside each opening, so the leaf that arrives is the leaf the room needs.

The rules for the shared parts of a public building are set out in the fire door regulations commercial buildings guide, and the rules for the shops beside the showroom are set out in the fire door regulations retail guide. The showroom order names every door in the building, with the period and the hardware beside each one.

  • FD30 / FD60Fire periods to EN 1634-1
  • E / EW / EI 30-120What the letters beside the period mean
  • 4 mmThe gap round the leaf
  • One listEvery showroom door named

Showroom floor, workshop and offices: one building, three parts

A car showroom is three buildings in one: the floor where the cars stand and the visitors walk, the workshop where the cars are serviced, and the offices and stores that serve them both. The rules follow those parts, because a door between one part and the next must hold the fire where it started while the visitors reach the way out.

The showroom floor takes the doors that let a visitor in and out, and each leaf must open for people who have never seen the building before. The workshop takes the doors that guard the service bays, and each leaf must hold fire back where the fuel and the paint sit. The route that joins them takes the doors the visitors pass through, and each leaf takes the period the escape needs.

The showroom writes its fire strategy first, naming every opening with the door beside it, and the order follows the strategy, so no leaf is ordered without the room it guards behind it.

FD30 and FD60 in a showroom: the periods each part takes

Each part of a showroom asks a different period of its doors, because the load behind each leaf is different. The floor holds the cars and the visitors, the workshop holds the fuel and the paint, and the parts store holds the stock in boxes and crates, so the period on each door follows the room, not the leaf.

EN 1634-1 is the test that proves a fire door, and the proof is written as minutes beside letters. Thirty minutes is the shortest period on the scale and 120 is the longest, and the letters say what stayed back: flames on their own, flames with some heat, or flames with the heat as well. Minutes and letters are ordered together, because the minutes alone say only half of what the door proved.

A door that must hold longer is a heavier door, with a deeper frame to carry it, and the figure on the quotation climbs with the weight. No opening that needs 60 minutes should take a leaf proved for 30, because the shorter leaf is the one that gives way first.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

The showroom floor: glass, cars and the doors between them

The showroom floor is mostly glass, and the doors on it must hold their proof while letting the light through. A glazed leaf lets a visitor see the cars beyond it without opening the leaf, and the pane takes the same proof as the leaf, because the leaf and the glass are proved as one doorset. The bead and the fixings the test report names are written on the order beside the glass.

The cars on the floor carry fuel in their tanks, and the doors between the floor and the workshop must hold the fire where it starts. A leaf between the floor and the workshop takes the period the workshop demands, because the fire that starts among the cars must stay among the cars while the visitors move out.

Windows that share the same wall are covered in the fire rated windows guide, and the fire rated glass cost guide works through what the glass itself costs.

Workshops and paint shops: the doors behind the service bays

The workshop takes the heaviest fire load in the showroom, because the fuel, the oil and the paint sit behind its doors all day. A workshop leaf takes FD60 where the load is heaviest, and the period follows the fire load, not the size of the showroom.

The paint shop takes the same care, because the solvents behind its doors burn fast once the fire reaches them. A paint shop leaf takes the period the load behind it demands, and the seals round it must hold as long as the leaf, because a seal that has come away lets the smoke reach the corridor first. The gap round the leaf is kept to 4 mm, and the seal is checked with the leaf shut.

The service bays take doors that stand open through the day, so the cars can move in and out without stopping at every leaf. A leaf that must stand open takes a hold-open device proved to BS EN 1155, so the leaf shuts on its own the moment the alarm sounds. A leaf wedged open with a trolley holds nothing back when the fire comes, and the wedge belongs in the store, not under the leaf.

Parts stores and back offices: the doors that guard the stock

The parts store holds the stock the workshop runs on, and the leaf that guards it takes the period the load behind it demands. A store leaf takes FD60 where the stock is boxed and crated, because the boxes burn fast once the fire reaches them, and the leaf must shut after every load that passes.

The back offices take the doors that guard the staff and the records, and each leaf takes the period the office beside it takes.

A showroom leaf earns its forced entry category from what sits behind it. Issue 8.2, dated September 2024, sets B3 at three minutes, C5 at five and D10 at ten, so the category on the order follows the value of the stock in the room. The LPS 1175 vs PAS 24 guide puts the two ratings beside each other, and the keeping an LPS 1175 rating valid guide lists what can break a rating after a door is fitted.

Escape routes through a showroom: the way out for visitors

The visitors in a showroom follow the route the building gives them, and the way out must be clear when the alarm sounds. Each door on the route opens with one push from anyone who reaches it, because the leaf must open whether the power is there or not.

The seals on the route doors carry a smoke proof to BS EN 1634-3, Sa where the smoke is at room temperature and S200 where it is at 200 degrees. A seal only works when it meets the frame all the way round, and smoke gets to the route ahead of the flames. The smoke control doors guide covers how the doors hold smoke back while people move past them.

One route takes one period on every leaf, because the weakest door on the route sets how long the route holds. A leaf with a shorter proof than the leaves beside it is the leaf that fails first, so the route takes no leaf shorter than the period the route needs. The doors that guard a warehouse are covered in the warehouse security doors guide, and a showroom takes the same care with its stores as a warehouse takes with its own.

Position Door Period What to check
Showroom floor Glazed leaf FD30 Leaf, glass, closer
Workshop Steel leaf FD60 Leaf, lock, seals
Parts store Steel leaf FD60 Leaf, lock, seals
Public route Fire leaf FD30 Leaf, bar, closer
Plant room Fire leaf FD60 Leaf, seals, gap

What keeps the period: the closer, the seal and the gap

Every visitor who walks through a showroom door puts the closer to work, and the leaf must come home behind each one without a slam. BS EN 1154 sets EN 3 as the smallest power a fire door closer may take, and the test is simple: open the leaf and watch it shut on its own. A closer that has lost its pull leaves the leaf standing open after the visitor has passed.

The gap beside the leaf stays at 4 mm, so the leaf swings without catching and the seal can close the opening when the leaf shuts. Heat near 200 to 250 degrees makes the intumescent seal swell, and paint laid over the seal stops it swelling when the fire comes. A seal that has slipped out of its groove is written against its door on the day someone finds it.

Each hinge takes its share of the leaf through every opening of the day. A hinge that works loose lets the leaf sink a little month by month, until it drags and the gap at the top lets smoke through. The fire door hardware guide names what the lock the key turns must do, and the fire door closers guide works through sizes and fitting.

The showroom order: every door on one list

The showroom order is one list, with a line for every door in the building and the leaf, the period, the lock and the closer beside each one, so the door that arrives is the door that was ordered. Where the list names one leaf for the whole showroom, the fitter must guess which room takes which period, and a leaf fitted to the wrong room guards the wrong thing.

The quotation is checked against the list, figure by figure, with each one sitting beside the door it belongs to. A figure missed off the quotation still has to be paid, and a part added later costs more than the same part ordered with the building. The how to specify security doors guide sets out the columns the list needs, and the security door cost factors guide works through what each step up the scale adds to the price.

Once a month the showroom tries every leaf before the doors open, working from the floor through the workshop to the stores. A leaf that drags, a seal that has slipped from its groove, or a closer that has lost its pull is written against its door on the day it is found, and the repair is booked while the fault is still small. The record stays with the building file, and the fire door inspection checklist sets out what the visit should cover.

In a car showroom the period, the release and the closer decide together whether the way out works, so all three sit on the same list before the order goes out.

What period should a showroom door carry?

FD30 or FD60 to EN 1634-1, with letters beside the minutes that say what the doorset held back. Which period the door takes depends on the room behind the leaf.

Can one leaf hold fire and forced entry?

Yes, when the same leaf, frame and seals went through the fire test and the forced entry test together, so one doorset carries the proof for both jobs.

Do showroom doors need panic hardware?

Yes, the leaf on the way out takes a bar proved to BS EN 1125, running across at least 60 percent of the leaf, so one push opens it for the visitors behind it.

What grade should a parts store door carry?

The grade follows the room: B3, C5 or D10 to LPS 1175, with the parts store taking a higher category than the showroom floor.

Who checks the showroom doors?

The showroom manager walks the round that covers every door, and each visit is written into the record the building keeps.

Specifying doors for a car showroom?Send the door list and the period each door must hold for a tested door quotation.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →

Products

One supplier for the whole building envelope

Ready to specify your project?

Free assessment, written specification and test evidence. Reply within one working day.