Fire Door Regulations Care Homes
Fire door regulations for care homes: FD30 and FD60 periods, bedroom doors, smoke control and the inspection round, with one schedule for the whole home.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
A care home is a building where the people inside cannot move quickly. Residents may need a wheelchair, a frame or a member of staff to reach the stairs, so the fire doors in a care home must hold fire back longer than the people inside need to get out.
The rules start with the people, not with the door. A bedroom corridor where residents sleep asks for a different door from a stair core that serves the whole home, and a kitchen that holds the highest fire load asks for a longer period than a lounge.
Every fire door in the home sits on one schedule, and an order that names each one plainly gets the right door on the right opening. The healthcare sector page sets out the buildings these doors guard, and the fire door regulations for hospitals guide covers the doors on the buildings where the same slow evacuation applies.
- FD30 / FD60Fire resistance periods tested to EN 1634-1
- BS EN 1634-3 Sa / S200Smoke control ratings for doors
- 4 mmMaximum gap round a fire door leaf
- TS 007 3-starCylinder and handle sets
Where the fire doors sit: bedrooms, corridors and stair cores
Bedroom doors guard the rooms where residents sleep, so they must hold fire back while staff move residents to safety. A bedroom door takes FD30 as a minimum, with a closer that pulls the leaf shut every time, because a bedroom door left open is a corridor full of smoke.
Corridor doors and cross-corridor doors split the home into compartments, so fire is held in one part of the building while residents move to another. The period follows the compartment, and a door on a compartment wall takes FD60 where the fire load behind it is heavier.
Stair cores are the escape routes for the whole home, so the doors on them must hold fire and smoke back while residents move down the stairs. The commercial buildings fire door regulations guide sets out the periods for the shared parts of a building.
Lounges and dining rooms hold residents through the day, so the doors on them must open easily for wheelchairs and frames and still shut on their own. A door that is too heavy for a resident to push open is a door that stands open, and a door that stands open is a gap in the compartment, so the closer power and the opening force belong on the schedule beside the period.
Matching the period to the room: FD30, FD60 and the fire load
Fire resistance is proved to EN 1634-1, with FD30 or FD60 and the letters E, EW or EI naming what the furnace measured. The period on the order should match the fire load behind the door, not the door the catalogue shows first.
Kitchens hold the highest fire load in a care home, so the doors around them take FD60, while bedrooms and lounges take FD30. A door on a smoke path takes FD30S, with the seal proved to BS EN 1634-3, to Sa for smoke at room temperature and S200 for smoke at 200 degrees Celsius.
Glazed screens and vision panels let staff see along a corridor without opening a door, and the glass in them must be proved for the job, because a pane that was never tested is a hole in the door. The fire rated windows guide covers the windows that share the same wall, and the fire rated glazed doors guide covers the glazed leaves that carry the higher periods. Sliding doors on a corridor take the same proof, and the fire rated sliding doors guide covers the leaves that slide rather than swing.
The bedroom door: thumb turn, lock and the resident inside
A bedroom door must open from the inside without a key, because a resident who cannot find a key in smoke has no time to hunt for one. A thumb turn on the inside lets the resident leave at once, and the lock should shut the door without a struggle, because a door that will not latch is a door that stands open.
Hardware carries the rating with the leaf. A TS 007 3-star set, made of a 1-star cylinder with a 2-star handle or escutcheon, keeps the lock proved, and hinges to BS EN 1935, grade 13 for leaves up to 120 kg and grade 14 for leaves up to 160 kg, each proved through 200,000 cycles, keep the leaf hanging true.
Flat entrance doors in a care home face the same two jobs, fire and security, and the flat entrance doors guide covers the doors that must hold both. Where a resident needs a door that leaves nothing to hold, the anti-ligature doors guide covers the leaves, the hardware and the gaps.
Keeping smoke back: FD30S, seals and the corridor
Smoke kills before fire reaches a corridor, so the doors on the escape route must hold smoke back as well as fire. FD30S names a door whose seal is proved to BS EN 1634-3, to Sa for smoke at room temperature and S200 for smoke at 200 degrees Celsius, so the corridor stays clear while residents move.
The seal is the part that does the work, and it must be checked on every round. Intumescent seals expand at around 200 to 250 degrees, and the gap round a fire door leaf must stay at 4 mm, because a wider gap lets fire and smoke past whatever the rating on the leaf says.
The smoke control doors guide covers the doors that must hold smoke back while people move past them, and the fire door hardware guide covers the grades and the parts behind a working fire door.
Closers and hold-open devices: the door that must shut itself
A fire door that stands open is no fire door, so every fire door in a care home needs a closer that pulls the leaf shut every time. No fire door takes less than EN 3 to BS EN 1154, with the power size chosen for the leaf that is fitted, and the fire door closers guide covers the sizes and the fitting.
Some doors are held open through the day so residents can move freely, and a hold-open device to BS EN 1155 lets the door shut the moment the alarm sounds. A wedge under a fire door is not a hold-open device, and it leaves the door open when the alarm sounds, so the device should be ordered with the door, not improvised after it.
Closers on heavy leaves need the right power size, and the opening force must stay below 30 N for the first 30 degrees of travel and below 22.5 N beyond, under BS 8300 and Approved Document M, so a resident of any strength can push the door open.
Escape routes for residents who cannot move quickly
Escape in a care home is slow, because residents move with staff, wheelchairs and frames, so the routes must stay clear and the doors on them must open with a light push. Panic hardware to BS EN 1125 takes a bar across at least 60 percent of the leaf width, and it is the hardware for a room that holds more than 60 people.
When the alarm sounds, every door on the escape route must open at once. Staff should not have to hunt for a key while residents wait, and a visitor who has never been in the home before must be able to push the door open and leave.
The plant rooms and stores behind the home need doors of their own, and the plant room door requirements guide covers the doors on the rooms that feed the building, while the hospital security doors guide covers the doors on the buildings where the same slow evacuation applies.
Staff should know which doors they must shut on the way out, because a fire door only works when it is shut. The evacuation plan should name the doors on each route, and a drill that runs the plan shows whether the doors shut as they should, so the drill and the inspection round belong together on the record.
The monthly round: closers, seals and gaps
Fire doors in a care home are checked on a routine, and each round looks at the closers, the seals, the gaps and the glazing. A closer that no longer pulls the leaf shut, a seal that has come away or been painted over, or a gap wider than 4 mm each leaves the door unproved, so the fault goes on the record the day it is found.
A rating stays valid only while the door stays as it was tested. The leaf, the frame and the hardware named in the test report must all still be there, so a closer changed for a lighter one or a seal painted over leaves the door without its proof.
The fire door inspection checklist names what each round should look for, and the security door maintenance checklist covers the doors that must hold both fire and forced entry.
One schedule for the whole home: every door on one line
Write the enquiry as one schedule with a line for every door in the home, and put the position, the fire period, the hardware and the closer on each line, so the door that arrives is the door that was proved.
Match every quote to the schedule line by line before the order is placed. A closer or a seal left off a quote will still need buying, and fitting it round a door that is already in use costs more than ordering it with the door. The security door cost factors guide sets out what each step up the scale adds to the build, and the how to specify security doors guide sets out the columns the schedule needs.
File the test reports and the inspection routine with the doors when they arrive, so the record covers the whole life of every door in the home.
| Position | Door | Rating | What to check |
|---|---|---|---|
| Bedroom | Fire door | FD30 | Closer, seals, thumb turn |
| Corridor | Fire door | FD30S | Seals, closer, gaps |
| Stair core | Fire door | FD60 | Seals, closer, release |
| Kitchen | Fire door | FD60 | Seals, closer, latch |
| Plant room | Fire door | FD60 | Seals, closer, latch |
A care home door must hold fire back while residents move slowly, so the period, the closer and the seal must all sit on the same schedule.
What fire rating do care home doors need?
The room decides. Bedrooms and lounges take FD30, doors on compartment walls and around kitchens take FD60, and doors on a smoke path take FD30S.
Do bedroom doors need a thumb turn?
Yes, so the resident can leave without a key. The thumb turn sits on the inside, and the lock should shut the door without a struggle.
Can a fire door be held open in a care home?
Only by a hold-open device to BS EN 1155, which lets the door shut when the alarm sounds. A wedge is not a hold-open device.
Who checks care home fire doors?
The person who runs the home, on the routine the fire risk assessment sets. Every round covers the closers, the seals, the gaps and the glazing, and every fault found is written on the record the same day.
Steel or timber for a care home fire door?
Either, where the door is proved for the job. Steel suits doors that take hard use, timber suits doors where the home wants a warmer look, and the steel versus timber fire doors guide sets out the choice.