Fire Door Closers Explained
A fire door only works if it closes and latches. How to choose a closer to BS EN 1154, read the power sizes, and keep the door shutting every time.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
A fire door closer is the controlled device that shuts the leaf and drives the latch home after every opening. A fire door that stands open when fire breaks out has no fire performance at all, whatever its rating, so the closer is not an accessory. It is the part that makes the rating work in practice. Every fire door on an escape route or a compartment line needs one, matched to the leaf it has to close and tested with the doorset it sits on.
The standard behind the closer is BS EN 1154. It sets seven power sizes, EN 1 to EN 7, and a six digit code that states what the closer can do. On a fire door the power size must be at least EN 3, and the closer must carry evidence that it was fire tested as part of a doorset. A closer chosen on looks, or on a price, or because it was in stock, is a closer that may never latch the door it is fitted to.
- EN 3 minimumThe lowest power size permitted on a fire door
- EN 1 to EN 7Power sizes under BS EN 1154, by leaf width and mass
- 500,000 cyclesDurability grade 8 under BS EN 1154
- BS EN 1155Hold-open devices that release on alarm
What a closer must do on a fire door
A closer has one job, and it must do it from any position. Open the leaf a little or open it wide, release it, and it must travel back to the frame, press through the resistance of the seals and the latch, and finish fully latched. A door that swings shut and stops short of the latch is still open to fire and smoke. The closing force has to beat the latch, the seals and any air pressure across the opening, and it has to do so every time, for the life of the door.
The fire rating belongs to the door closed, not the door nearly closed. A fire test to EN 1634-1 tests the doorset shut, with the leaf latched and the seals in place. Nothing in that test covers a leaf standing open, or a leaf resting against its latch without engaging it. The closer is what turns the tested condition into the everyday condition, and a door that is wedged open, or whose closer has failed, has lost the rating it was bought for.
The closer also has to work against the building around it. Stack pressure in a tall building, wind through a corridor, and a draught from an open window all push against the leaf. A closer sized only for the leaf, with nothing left over for the air moving past it, will fail on the days the building is under pressure. Where a door is subject to draughts or wind it is usual to increase the power size by one, and the door should still be tested in the conditions it will meet in use. For the duties the law places on the person responsible for the door, see our fire door regulations for commercial buildings guide.
Reading the EN 1154 code on the closer body
Every closer to BS EN 1154 carries a six digit classification code, and the code is the fastest way to check whether the closer suits the door. The first digit is the category of use: grade 3 closes a door from at least 105 degrees open, and grade 4 closes from 180 degrees open. The second digit is durability: grade 8 means the closer completed 500,000 test cycles. The third digit is the power size, from 1 to 7, which the next section sets out in full.
The fourth digit is the one that matters most on a fire door. Grade 1 means the closer is suitable for use on fire and smoke door assemblies, having been included in a successful fire test to EN 1634-1. A closer without that grade has no place on a fire door, whatever its power size. The fifth digit is safety in use, grade 1 for every closer that meets the standard. The sixth digit is corrosion resistance, from grade 0 with no defined resistance to grade 3 with high resistance, which matters on external doors and in damp or coastal sites.
Read the code before the order is placed, not after the closer arrives. A variable power closer states its range, for example 2 to 4, and both the minimum and the maximum size must be shown. Where the closer is supplied separately from the doorset, ask for the fire test evidence that names it, and check that the doorset it was tested with matches the doorset on site. For how to read test evidence and what to ask for before acceptance, see our how to specify security doors guide.
Power sizes EN 1 to EN 7: matching the closer to the door
The power size follows the leaf, and two measurements decide it: the width of the leaf and its mass. EN 1 suits a leaf up to 750 mm wide and 20 kg in mass. EN 2 suits a leaf up to 850 mm wide and 40 kg. EN 3, the minimum for a fire door, suits a leaf up to 950 mm wide and 60 kg. EN 4 suits a leaf up to 1,100 mm wide and 80 kg. EN 5 suits a leaf up to 1,250 mm wide and 100 kg. EN 6 suits a leaf up to 1,400 mm wide and 120 kg. EN 7, the largest size, suits a leaf up to 1,600 mm wide and 160 kg. The table at the end of this guide sets the seven sizes out together.
Both measurements matter, and the larger one governs. A wide light leaf still needs the size for its width, because the closer has to move the leaf through its full swing and the leverage changes with width. A narrow heavy leaf, such as a steel fire door with a thick leaf and a security rating, needs the size for its mass.
Closers come in three forms. A fixed power closer has one size, set at manufacture. A variable power closer can be adjusted on site across a range, for example EN 2 to EN 4, which suits a building where leaf sizes vary and one closer model must cover them. A selectable power closer is set by template at fitting. Variable power is the most flexible choice, because it can be adjusted to the conditions on site and set to the lowest opening force that still closes the door. A closer set too strong makes the door hard to open; a closer set too weak never latches it. For the ratings the leaf itself must carry, see our fire ratings page, and for steel doors that carry fire and security ratings together, see our dual certification guide.
Overhead, concealed and floor spring: where each type fits
The overhead surface mounted closer is the type most specifiers will know. The body sits on the leaf or the frame, above the opening, with an arm that links the two. It is easy to reach, easy to adjust and easy to replace, which is why it is the default on corridor and office doors. The arm takes two forms: a scissor arm, which folds as the door opens, and a slide channel arm, which runs in a guide rail and sits tidier against the frame. BS EN 1154 covers surface mounted, concealed and transom mounted closers, so the standard follows the type rather than the other way round.
A concealed closer hides the body inside the leaf or the frame, leaving only the arm or the channel visible. It suits doors where the hardware must not spoil the look of the opening, such as a reception door or a door in a listed interior, and it suits doors where a surface mounted body would be damaged. The trade is access: adjustment is harder, and a closer that cannot be reached is a closer that is never adjusted. Name the access in the specification, and check that the closer can be serviced without taking the door off its hinges.
A floor spring sits in the floor beneath the leaf, with a spindle that carries the door. It suits heavy leaves, frameless glass doors and double action doors that swing both ways, and it suits openings where nothing may sit above the door. It needs a pocket cut into the floor, drainage where water can reach it, and a level base, so it is a decision for the design stage, not a change made on site. A transom mounted closer sits in the transom above the door and suits a similar brief where the frame can carry it. Whichever type is chosen, the power size and the fire evidence must be the same: the type changes where the closer sits, not what it must do. For the doorset the closer sits on, see our fire rated steel doors page.
Cam action against rack and pinion
Two mechanisms sit inside the closer body, and they feel different in the hand. A rack and pinion closer is the traditional design: a toothed rack drives a pinion as the door opens, and a spring drives it back. The opening resistance stays high through the swing, and the closing force is spread across the whole travel.
A cam action closer uses a shaped cam and a slide arm instead of a scissor arm. The opening force falls away fast after the first few degrees, so the door feels light once it is moving, and the closing force peaks in the final 0 to 15 degrees, where the latch and the seals need it most. That shape is what makes it the easier choice where people push the door all day, and it is the design that most readily meets the accessibility limits in BS 8300 and Approved Document M: an opening force below 30 N through the first 30 degrees of opening, and below 22.5 N beyond that. On a fire door those limits must be met at a minimum spring strength of EN 3.
The choice follows the use of the door. Choose cam action where people pass through all day, where wheelchair users, older people and staff carrying loads use the opening, and where the opening force must stay low without giving up the latch. Choose rack and pinion where the door takes heavy use and a backcheck must protect the wall and the hinges. Either mechanism must carry the EN 1154 code and the fire evidence for the doorset. For how the leaf and the frame it sits in are chosen, see our steel versus timber fire doors guide.
Hold-open devices to BS EN 1155: when a fire door may stay open
Some fire doors must stay open in normal use: a corridor door that carries trolleys all day, a ward door that staff pass through with beds, a door on a route used by people who cannot manage a self-closing leaf. The answer is a hold-open device to BS EN 1155, and only that answer. An electromagnetic hold-open device holds the leaf open and releases it when the fire alarm operates or when power to the device is lost, so the closer shuts the door. An electromagnetic hold-open closer does the same job in one unit, combining the closer and the release.
Two other release types exist. An acoustically activated device listens for the sound of the fire alarm and releases the door when it hears it, which suits a door where no wiring can be run, but it is not suitable where a voice alarm is used, where the first alarm alerts staff only, or on a fire door to a protected stair. A swing-free arm lets the leaf move freely and independently of the closer in normal use, and the closer takes over when the alarm operates or the power fails, which suits bedroom doors and doors used by people who need no resistance at all.
Three limits apply to every hold-open device. First, it must release on alarm and on power loss, and a device that needs power to close is not a hold-open device for a fire door. Second, hold-open devices should not be used for a door to a room where the only automatic detector is a heat detector, because the alarm may sound too late. Third, nothing else may hold a fire door open: a wedge, a hook, a piece of furniture or a mechanical hold-open that cannot release is a maintenance failure, not a solution. Record every hold-open device on the door schedule, with the release type and the alarm circuit it sits on. For the inspection checks that catch a failed release, see our fire door inspection checklist.
Setting the closing speed and the latch
A closer is adjusted with valves, and two of them decide whether the door closes well. The closing speed valve sets the pace of the main sweep, from open to the last few degrees. The latching speed valve sets the pace of the final degrees, where the leaf must press through the seals and drive the latch home. Set the main sweep slow enough that the door does not slam, and set the latch fast enough that it engages every time. A door that closes gently and never latches is no better than a door that slams and bounces off its latch.
Two further functions appear on many closers. A backcheck cushions the leaf as it approaches full opening, protecting the wall, the hinges and the closer itself on doors that are thrown open. A delayed action holds the door open for a short time before the closer takes over, which helps people passing through with loads, but it must still close the door every time, and it must never be set so long that the door is effectively held open. Both functions are set at commissioning and checked after, not left at the factory setting.
Test the setting at several angles. Open the leaf to 90 degrees and release it, then to 30 degrees, then to a few degrees short of closed, and watch it latch every time. Test it again after any change to the door: new seals, a heavier latch, a different hinge, or a change in the air pressure across the opening. A closer that passed its test on installation day and fails after the seals were changed has not been maintained, it has been forgotten. For the sliding fire door, where the closing device works along a track rather than a hinge, see our fire rated sliding doors guide.
Testing, adjusting and replacing a closer
A closer is tested the same way it is set: by opening the door and watching it close. Open it to several positions, release it, and confirm it closes fully and latches every time, without help and without slamming. Check that the arm is fixed firmly, that the valves have not been turned by hand, and that the leaf has not dropped on its hinges, because a leaf that drags on the floor will defeat any closer. Record the date, what was checked, what was found and who did it, and keep the record with the fire safety records for the building.
The closer is part of the tested doorset, so replacing it is not a like-for-like swap of a worn part. A replacement closer must carry the same power size, the same EN 1154 code and the same fire evidence, and it must be tested with the doorset it sits on. A closer with no fire test evidence, or a closer of a lower power size than the door needs, takes the doorset outside its evidence. Where a closer has been changed, note the change on the door schedule and keep the new evidence with the old, so the next person to work on the door knows what must not change.
When a closer cannot be adjusted to latch the door, the fault is often not in the closer. A leaf that has swollen, a seal that has been painted over, a latch that sticks, or a hinge that has worn will all stop a good closer from finishing its job. Fix the door first, then set the closer, and test the whole doorset together. A closer that is blamed for a door that drags will be replaced, and the new closer will fail in the same way. For the servicing that keeps a doorset working, see our maintenance page, and for the changes that can cost a door its rating, see our guide to keeping an LPS 1175 rating valid.
| Power size | Maximum leaf width | Maximum leaf mass | Where it is used |
|---|---|---|---|
| EN 1 | 750 mm | 20 kg | Small, light interior doors |
| EN 2 | 850 mm | 40 kg | Light interior doors |
| EN 3 | 950 mm | 60 kg | Standard fire doors, the minimum size on a fire door |
| EN 4 | 1,100 mm | 80 kg | Wide commercial doors |
| EN 5 | 1,250 mm | 100 kg | Large commercial doors |
| EN 6 | 1,400 mm | 120 kg | Heavy entrance doors |
| EN 7 | 1,600 mm | 160 kg | Very large or heavy doors |
A fire door that does not close and latch is a hole in the compartment line. Test the close, not the label.
What power size closer does a fire door need?
At least EN 3, which suits a leaf up to 950 mm wide and 60 kg in mass. The size must match the leaf: measure its width and its mass as supplied, with glazing, seals and ironmongery fitted, and use the larger of the two. Where the door is subject to draughts or wind, go up one size.
Can a fire door closer be adjusted?
Yes. A variable power closer can be adjusted on site across its range, and every closer has valves for closing speed and latching speed. Set the main sweep so the door does not slam, set the latch so it engages every time, and test the door from several angles after any adjustment.
Can a fire door be held open?
Only by a hold-open device to BS EN 1155 that releases the door when the fire alarm operates or when power is lost. A wedge, a hook or a mechanical hold-open that cannot release must never be used. Acoustic devices and swing-free arms are other release types, with their own limits on where they may be used.
What is the difference between cam action and rack and pinion closers?
A rack and pinion closer drives a toothed rack and keeps its opening resistance high through the swing. A cam action closer uses a shaped cam and a slide arm, so the opening force falls away fast after the first few degrees and the closing force peaks in the final 0 to 15 degrees, where the latch needs it. Cam action is the easier choice where people push the door all day.
How do I know a closer is suitable for a fire door?
Check the six digit BS EN 1154 code on the closer body: the fourth digit must be grade 1, which means the closer is suitable for fire and smoke door assemblies. Ask for the fire test evidence to EN 1634-1 that names the closer and the doorset, and check the power size is at least EN 3 and matched to the leaf.
What a closer cannot fix
A closer has one job: to close the leaf and hold the latch. It cannot fix a leaf that is warped, a frame that is out of square, or gaps wider than 4 mm around the leaf. The closer pulls against the leaf, so if the leaf binds on the frame the closer works harder and wears faster, and the door still does not latch. A door that does not latch has no fire performance at all, whatever the closer cost.
It cannot fix a hinge problem. Hinges to BS EN 1935 carry the leaf, and a hinge that has dropped or a screw that has worked loose lets the leaf sag. A closer fitted to a sagging leaf will not close it squarely, and adjusting the closing speed only hides the fault for a few weeks. Check the hinges first, and replace a hinge that no longer holds the leaf before touching the closer.
It cannot fix the wrong power size. Closers are sized EN 1 to EN 7 under BS EN 1154, and the size follows the leaf width and weight. A closer sized below the leaf will not close it against air pressure or a draught from a corridor. A closer sized above the leaf makes the door hard to open, and a door that needs more than 30 N to open in the first 30 degrees, or more than 22.5 N beyond that, fails the access rules. Our fire door hardware guide sets out the hardware the closer works with.
It cannot fix the wall beside the door. The closer, the leaf and the frame were tested together, and the rating stops at the frame. A closer fitted to a frame fixed into a weak partition will pull the frame out of square over time, and the leaf will start to bind. Check the wall and the fixings before blaming the closer.
It cannot fix seals that have been painted over. Intumescent seals expand at roughly 200 to 250 degrees, and a coat of paint stops them expanding when heat reaches them. The closer can close the leaf, but the gap stays open in a fire and the rating counts for nothing. Keep paint off the seals, and check them at every inspection. For the checks themselves, see our fire door inspection checklist.
Mistakes that leave a fire door standing open
Most fire doors that stand open do so because of a small mistake, not a failed closer. Each mistake below has the same result: a leaf that stands open when fire breaks out, and a rating that counts for nothing.
| Mistake | Why it fails | What to do instead |
|---|---|---|
| Closing speed set too slow | The leaf takes so long to close that people prop it open. | Set the speed so the leaf closes and latches on its own. |
| Latch speed left at zero | The leaf reaches the frame but never pulls into the latch. | Set a short latch action that pulls the leaf home. |
| Closer disconnected after a delivery | A closer taken off to move furniture is rarely refitted. | Refit the closer the same day, sized to BS EN 1154 for the leaf. |
| Hold-open device with no alarm link | A hold-open device that never releases leaves the door open in a fire. | Link the device to the alarm to BS EN 1155. |
| Wrong closer for the leaf weight | A closer below the leaf weight cannot close it against a draught. | Match the power size to the leaf width and weight. |
Keep the evidence with the door. The closer model, the power size and the test report should travel with the doorset, so the next inspection can check what was fitted against what was tested.