Hospital Security Gates

Hospital gate rules: pedestrian and vehicle gates, ambulance routes, access control and the vehicle ratings that order a whole hospital estate.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

A hospital never closes, and the gates on its boundary decide who reaches the buildings and when. Ambulances arrive at all hours, staff change shifts through the night, visitors come and go all day, and the gate line has to sort them without stopping the care inside.

The order comes from the estate, not from one gate. A main entrance takes visitors on foot, an ambulance bay takes emergency vehicles, a service yard takes deliveries, and a staff car park takes cars, and each gate needs a rating, a control and hardware to fit the opening it guards.

The rating, the access control, the automation and the records all sit inside one schedule, and an order that names them plainly gets the right gates on the right openings. Our hospital security doors guide covers the doors behind the gate line, and the healthcare sector page covers the buildings the gates protect.

  • ISO 22343-1Vehicle security barrier ratings
  • LPS 1175 B3 / C5 / D10Forced entry ratings, three, five and ten minutes
  • 1,200 mm / 500 mmProtectUK clear gap and minimum height
  • PAS 68:2013Superseded by ISO 22343-1:2023

Main entrances, ambulance bays and service yards: where a hospital puts its gates

A hospital divides into parts that meet the public in different ways, and each part puts its gates in a different place. The main entrance meets visitors on foot, the ambulance bay meets emergency vehicles, the service yard meets deliveries, and the staff car park meets cars at the start and the end of a shift.

Every one of those parts has gates that must hold against attack and gates that must open for an emergency vehicle, and the two duties sit on the same line. A gate that holds against a vehicle but traps an ambulance outside has failed its other duty, and a gate that opens freely but lets any stranger onto the wards has failed its first.

Walk the boundary and note every gate a person or a vehicle can reach, then set each one by the attack it could face. A staffed main entrance faces less risk than a rear gate onto a road nobody watches after dark, so the rating follows the gate, not the hospital.

Pedestrian gates: the way staff, patients and visitors arrive on foot

Pedestrian gates sort people, not vehicles, and they work all day. Staff pass through on their way to a shift, patients arrive with relatives, and visitors come and go between visiting hours, so the gate has to let the right people through and keep strangers out of the wards behind it.

A pedestrian gate must close behind the person who passes through, and a gate left standing open is no gate at all. A closer or a motor that pulls the leaf shut belongs on the schedule beside the gate, and the inspection round should look for the gate that no longer shuts on its own.

A pedestrian gate on an escape route must release without a key, in one action, in the direction of escape. Turnstiles and speed gates sit on the way in, not on the way out, and they must release when the alarm sounds. The security turnstiles guide covers readers, fobs and biometrics in the lane.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

Vehicle gates and the ambulance route: keeping the emergency route clear

A sliding gate suits the ambulance entrance because it opens across a wide gap without swinging into the road, and the track, the wheels and the motor belong on the inspection round. A gate that sags on its track leaves a gap a vehicle can push through, and a gate whose motor fails shut blocks the one route an ambulance must use. Our sliding vehicle gates page covers the gates in full, and our gate automation guide covers how a gate is driven and released.

The ambulance route must stay clear at all hours, and nothing on the estate may queue across it. Deliveries and service vehicles use a separate gate, so a lorry waiting at the service yard never blocks the bay. A gate that opens for an ambulance must open fast enough that the crew is not waiting at the line, and the opening time belongs on the schedule beside the gate.

Where a vehicle must be stopped, not just slowed, the gate line needs a barrier behind it. Anti-ram gates and road blockers hold the line where a vehicle must be stopped, and the rating for that line comes from the vehicle test, not from the gate leaf alone. Our anti-ram gates and barriers guide works through the options, and our road blockers guide covers the blockers that rise from the road.

Reading the vehicle rating: ISO 22343-1, mass, speed and penetration

Under ISO 22343-1 a barrier is proved against a vehicle driven at it, and the rating records the vehicle, the speed, the angle and how far the vehicle gets past the line. The test runs vehicles from a 1,500 kg car to a 30,000 kg truck, at 48, 64 or 80 km/h, and the rating names the vehicle, the speed and the penetration in one string. A rating string such as V/7500[N3]/80/90:0/0 names the vehicle class, the speed and the penetration, so the schedule can name the exact rating the gate line must carry.

PAS 68:2013 no longer carries the vehicle rating; ISO 22343-1:2023 took its place, so a schedule that asks for the old standard by quoting the new one asks for something that does not exist. Put the current standard beside the product it belongs to, and the rating beside the standard. The ratings in full are in our ISO 22343 vehicle security barriers guide, and the change from PAS 68 and IWA 14-1 to the current standard is worked through in our PAS 68 bollards guide.

ProtectUK guidance caps the clear gap beside a barrier at 1,200 mm and sets the minimum height at 500 mm. A gap wider than the cap lets a vehicle through beside the barrier, and a barrier lower than the minimum lets a vehicle climb it, so the gap and the height belong on the schedule beside the rating. The hostile vehicle mitigation page covers the line in full.

The ambulance route first: the gate that must never block the way

A hospital gate guards the ambulance route, and the route must stay clear at all hours. A vehicle gate that will not open for an ambulance is a gate that has failed its first job, so the release on alarm and the fail safe state belong on the order beside the gate.

Vehicle ratings are proved to ISO 22343-1, which supersedes PAS 68:2013, with test vehicles from a 1,500 kg car to a 30,000 kg truck at 48, 64 or 80 km/h. The rating on the order should match the vehicle the approach could bring, and the ratings in full are set out in our ISO 22343 vehicle security barriers guide.

ProtectUK sets the spacing on the line, with no more than 1,200 mm clear between bollards and a minimum height of 500 mm. The hostile vehicle mitigation page covers the line in full, and the rated options for the gate line are covered in our anti-ram gates and barriers guide.

Pedestrian gates take a different proof from vehicle gates, because a person on foot faces a different threat from a vehicle. The pedestrian gate, the vehicle gate and the fence between them belong on the same schedule line, so the line that arrives is the line that was tested.

Bollards and barriers close the gaps a gate leaves open, and the spacing between them matters as much as the rating. A gap wider than the spacing the line was proved to leaves the hospital open to the vehicle the gate was meant to stop.

The reader, the intercom and the card: who opens the gate

Access control at a hospital gate must open for staff and ambulances and stay shut for the rest. A reader opens the gate for a card the system knows, and an intercom at the gate lets a visitor ask to be let in, so the record shows who opened the gate and when.

One system across the hospital keeps the gates together, so one card opens the gate, the staff areas and the yard, and one stopped card stops working everywhere at once. A card that belongs to staff who have left must be stopped the same day.

The gate must fail safe on power loss, so a gate that loses power opens for the ambulance route and does not trap anyone inside. The fail position belongs on the order beside the motor, because a gate ordered without it leaves the hospital guessing in a power cut.

Gate automation must release on alarm, with no key, no card and no code standing between the hospital and the street. The safety devices that stop the gate when a person or a vehicle is in its way are covered in our gate automation guide, and the lanes and readers at the staff entrance are covered in our security turnstiles guide.

Gate Rating Access What to check
Main entrance ISO 22343-1 Reader, intercom Release, fail safe
Ambulance route ISO 22343-1 Reader, intercom Release, fail safe
Service yard ISO 22343-1 Reader Motor, safety devices
Pedestrian gate LPS 1175 B3 Reader Lock, hinges, closer

Put the rating, the access control and the fail position on one schedule line for every gate, so the next reader can see what was tested and what holds it. The choice between a turnstile, a speed gate and a portal is worked through in our turnstile versus speed gate versus portal guide.

Access control at the gate line: readers, intercoms and the fail safe state

Access control at a hospital gate decides who can open which gate, and when. Cards and fobs suit staff who come and go every day, an intercom suits a visitor who has no card, and a code suits a gate that many hands use.

When the power goes, the gate line must fail safe, so staff and patients can still leave. The release on power failure belongs in the specification beside the reader, and a gate that locks shut in a power cut traps people inside. A card that is lost should stop working everywhere at once, so one lost card never opens every gate on the estate.

The system must work as one system across the whole estate. A card that opens the main entrance should open the staff car park and the service yard, and the office that issues the cards should be able to stop one card without stopping the rest. Our how to specify security doors guide runs through the same discipline column by column.

Gate automation and the release on alarm: the gate that must open in an emergency

Power operated gates follow BS EN 12453 for safety in use, and the motor, the controls and the safety edges belong on the schedule beside the gate. A gate that closes on a person or a vehicle has failed the safety test, so the safety devices are tested on the same round as the gate itself.

On alarm the gates must release, and the release on alarm belongs in the fire strategy. A gate that keeps people inside during an evacuation has failed the duty it was fitted for, so the release is tested on the inspection round, not left to the day it is needed. A gate wedged open has no release at all, and a wedged gate is written on the record the same day it is found.

The release must work when the power is gone as well as when the alarm sounds. A battery backup or a manual release belongs on the schedule beside the motor, and the staff who use the gate must know where the release is and how it works.

Bollards, barriers and the gap between them: closing the line a gate leaves open

A gate line is only as strong as the gap beside it, and the gaps beside a hospital gate are where a vehicle finds its way in. Bollards fill the gap between the gate post and the wall, between the gate and the fence, and along the pavement where a vehicle could mount the kerb. Our choosing HVM bollards guide works through the options, and the security bollards page covers the bollards themselves.

Crash rated fences carry the same discipline to the boundary. A fence that holds against a vehicle needs its own rating, and the rating for the fence must match the rating for the gate beside it, or the line fails at the fence. Our crash rated fences guide covers the fencing, and the security gates page covers the gate lines themselves.

Where the gap runs along a footpath, street furniture can carry the line. Planters and seats that hold against a vehicle close a gap without closing the path, and the rating for the furniture must sit beside the rating for the gate on the same schedule. The HVM street furniture page covers the options.

The hospital estate order: one schedule for every gate

Build the enquiry as a specification, with one line for every gate on the estate. Each line names the position, the gate type, the vehicle rating, the access control and the automation, and the leaf, the frame, the fixings and the motor as one assembly. Where a gate must resist a vehicle as well, ask for the rating on the whole line, not on the leaf alone.

Have the test report, the classification and the hardware schedule travel with the gates, and file them the day the gates arrive. The handover pack should name the inspection routine the estate will follow, so the record covers the whole life of the line.

Position Gate Rating What to check
Main entrance Pedestrian gate LPS 1175 B3 Closer, reader, self-closing
Ambulance entrance Sliding vehicle gate ISO 22343-1 Track, motor, release on alarm
Service yard Vehicle gate ISO 22343-1 Motor, fixings, release
Staff car park Barrier and gate ISO 22343-1 Barrier, reader, fail safe
Boundary beside gate Bollards ISO 22343-1 Fixings, spacing, height

A hospital gate line guards the buildings behind it, so the rating, the release on alarm and the fail safe state must all sit on the same schedule.

What vehicle rating do hospital gates need?

The estate decides, by the vehicle the line must stop. ISO 22343-1 tests barriers against vehicles from a 1,500 kg car to a 30,000 kg truck, at 48, 64 or 80 km/h.

Do hospital gates need to fail safe?

Yes. When the power goes, or the alarm sounds, the gates must release so staff and patients can leave, and the release belongs in the specification beside the reader.

Can one hospital gate line hold a vehicle rating and a forced entry rating?

Yes, where the line is tested for both. ISO 22343-1 proves the vehicle side and LPS 1175 proves the forced entry side, and both proofs must name the line that will be fitted.

What breaks a hospital gate rating?

A gate that sags on its track, a motor that fails shut, a bollard with loose fixings, or a gap beside the gate wider than 1,200 mm. Repair or replace it, and record the work.

Who checks hospital gates?

The estates team, on the routine the fire strategy and the security plan set. Each record names the gate, the fault, the repair and the date.

Specifying security gates for a hospital?Send the gate schedule and the estate plan for a tested gate line quotation.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →