Fire Door Regulations for Offices Explained
Office fire doors under the Fire Safety Order 2005: leased floors, landlord and tenant duties, open-plan escape routes, stair cores and fit-outs.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
An office is a building where the same people come back every day. A fire door in an office has to hold a fire back long enough for a whole floor of people to leave at once, and it has to do it on a day when the doors have already opened and closed hundreds of times. That is why the rules for office fire doors are not the same as the rules for a school, a hospital or a shop, even though the door itself looks much the same.
The law is the Regulatory Reform (Fire Safety) Order 2005, which names a responsible person for the premises and puts the duty to assess the fire risk and keep the doors working on that person. For a single-tenant office the responsible person is usually the employer who occupies the building. For a multi-let office the landlord is the responsible person for the common parts, the stair cores and the lift lobbies, and each tenant has its own responsible person for the doors inside its own demise. Our fire door regulations for commercial buildings guide covers the Order and Approved Document B in full, our fire door regulations for schools guide covers the same Order from the school side, our fire door regulations for hospitals guide covers it from the hospital side, where the users are patients who cannot move on their own, and our fire door regulations for retail guide covers it from the shop side, where strangers walk in all day.
The two periods an office meets most often are FD30 and FD60. They are fire resistance periods tested to EN 1634-1, and the number is the minutes the doorset held its rating in the furnace test. FD30 holds for 30 minutes and FD60 for 60 minutes. The letters in front of the number say what the door holds back: E for integrity, EW for integrity with a limit on radiated heat, and EI for integrity with insulation. A door marked FD30S also carries a smoke rating. Our fire ratings page sets out the three letters and the periods behind them.
- Fire Safety Order 2005The law that names a responsible person for the premises
- FD30 and FD60Fire resistance periods tested to EN 1634-1
- FD30S30 minutes integrity plus smoke control
- BS EN 1154 closersSized to the leaf, minimum EN 3 on a fire door
The Order names a responsible person for every office floor
The Regulatory Reform (Fire Safety) Order 2005 applies to non-domestic premises, and an office is one of them. Article 3 defines the responsible person: in a workplace, the employer, to the extent the workplace is under their control; elsewhere, the person in control of the premises in connection with a trade, business or undertaking, or the owner. In multi-let buildings the duties can be shared, and the law requires co-operation between the parties who hold them.
Three duties matter for fire doors. Article 9 requires a suitable and sufficient fire risk assessment, reviewed regularly and after significant change, with the findings recorded. The assessment decides where fire doors go: escape routes, compartment lines and higher risk rooms. Article 14 requires emergency routes and exits to be kept usable. Article 17 requires a suitable maintenance system so doors stay in working order and good repair. The duty is not a one-off task.
In a single-tenant office the position is simple: the employer who occupies the building is the responsible person for the whole building, entrance doors, office floors, stair cores and plant rooms included. In a multi-let office the position is shared. The landlord or managing agent is the responsible person for the common parts, and each tenant is the responsible person for the doors inside its own demise. The boundary between the two must be written down, because a door that both sides think the other side looks after is a door nobody looks after.
A lease can set out who pays for the work, but it cannot remove the duty from the person the Order names. A tenant who signs a lease that says the landlord maintains the doors should still check that the doors are maintained, and a landlord who lets a floor should still check that the tenant’s doors close and latch. The fire risk assessment is the document that names the doors, the ratings and the checks, and it should be read whenever the office changes hands or the layout changes.
Landlord and tenant: who owns which office door
The common parts of an office building are the parts more than one tenant uses: the entrance doors, the stair cores, the lift lobbies, the corridors that serve more than one floor, the risers and the plant rooms.
Inside its own demise, the tenant owns the doors: the office floor doors, the meeting room doors, the doors between departments, the doors to its own store rooms and the doors to its own server rooms. A tenant who fits out a floor with new partitions and new doors has created new fire doors, and the tenant’s assessment must be reviewed to cover them.
Lift lobby doors sit on the boundary and matter more than most doors in the building. The lift lobby is the route from the office floor to the stair, and its doors must hold smoke back so the stair stays clear while a whole floor leaves.
Open-plan floors: where the fire lines run
An open-plan floor is one large space, and its fire lines run through it rather than around it. The fire strategy draws the lines: cross-corridor doors divide the floor into compartments, doors to the stair cores protect the way down, and doors to plant rooms and server rooms close off the higher risk rooms. The fire risk assessment names those lines, and every door on them carries the rating the strategy gives it.
FD30 is the workhorse of an office floor. Office floor doors, meeting room doors, store doors and doors between departments commonly carry FD30, which means the doorset held its rating for 30 minutes in the test to EN 1634-1. FD60 belongs where the fire strategy asks for a longer hold. Compartment walls, doors to stair cores and doors that protect a long escape route commonly carry FD60, because the people behind them need more time, and plant rooms and server rooms commonly carry FD60 too, because the fire risk inside them is higher than on the open floor.
The letter matters as much as the number. An EI door adds insulation, so the temperature rise on the safe side is limited and the door can be touched. Escape routes and corridors where staff pass close to the door usually need EI, because people escape past the door and may need to put a hand on it.
The wall around the door matters as much as the door itself. A rated doorset set into an unrated partition leaves the compartment line only as strong as the partition, and no fire door regulation will catch that on its own.
Escape from an open-plan floor: corridors, stair cores and the lift lobby
In an office the whole floor leaves at once. At the alarm, staff stand up from their desks and walk the same corridors to the same stairs, and the route must stay clear from the back of the floor to the stair door. Desks pushed into the corridor, boxes left by the lifts and deliveries stacked in the gangway all narrow the route at the very point it matters most.
Stair core doors commonly carry FD60, because the stair must hold while floors above move down through it. Panic hardware to BS EN 1125 belongs on escape doors where people leave under pressure: a bar across the leaf that opens the door when it is pushed, covering at least 60 percent of the leaf width, for escape doors where more than 60 people may need to leave at once. The door must open in the direction of escape, and it must open in one action without a key, a code or a card.
Lifts are not escape routes, and the lift lobby doors are the reason the stair stays usable. When the alarm sounds, the lobby doors must hold smoke back so the people waiting at the stair are not standing in smoke. A door marked FD30S carries 30 minutes of integrity plus smoke control, tested to BS EN 1634-3, and the S must be named in the specification where the fire strategy needs it. Our smoke control doors guide sets out the smoke classes, Sa and S200, and where each one belongs.
Locked doors must release on alarm. An office floor that is locked for security, a server room that is locked for safety and a records room that is locked for privacy all need the same answer: the lock must release when the fire alarm sounds, so nobody is trapped behind a door they cannot open. Our dual certification guide works through how fire and security sit on one doorset.
Meeting rooms and glazed partitions: glass that must hold fire
Meeting rooms need glass for light and sight, and the glass must be part of the tested doorset. A pane of glass fitted into a fire door after the test is a change to the tested assembly, and the rating does not cover it.
Glazed partitions carry the same rule as the doors in them. A fire rated partition needs fire rated glass as part of the tested assembly, with the frame, the beads and the seals named in the same evidence. Our fire rated windows guide sets out how glass, frame and beads are tested together, and the same discipline applies to a glazed office partition.
Meeting room doors often stand open. Staff leave them open for air, for movement and for the next meeting, and a door that stands open all day is a door that will stand open in a fire unless it has a hold-open device to BS EN 1155 that releases the door when the alarm sounds. A wedge, a chair or a hook on the wall has no such release, and a door held open by one of those will stand open in a fire.
Refurbishment and fit-out: the doors a new layout creates
Offices change more often than any other commercial building. A new tenant takes a floor, a growing team takes another floor, a fit-out moves the meeting rooms and the partitions, and every change creates new doors and moves the compartment lines. Article 9 of the Order requires the fire risk assessment to be reviewed after significant change, and a fit-out is a significant change.
Where the Order governs buildings in use, the Building Regulations 2010 govern building work. Approved Document B is the official guidance supporting the fire safety requirements of the Building Regulations, and Volume 2 covers buildings other than dwellings, the one that matters for commercial projects in England. Approved Document B is guidance, not law. The 2005 Order is what an occupied building must comply with.
At handover, note regulation 38 of the Building Regulations 2010. Where Part B applies, the person carrying out the work must give fire safety information to the responsible person by completion or first occupation, whichever is earlier. Ask for them and file them where the next responsible person will find them.
The Fire Safety (England) Regulations 2022 do not apply to offices. They apply in England only, and their fire door duties in regulation 10 cover a defined group of buildings, not commercial premises in general: buildings with two or more sets of domestic premises, with fixed schedules of best-endeavours checks of flat entrance doors at least every 12 months and checks of communal area doors at least every 3 months, for buildings above 11 metres. The frequency comes from the fire risk assessment and the article 17 maintenance system.
Closers, seals and the parts that fail first in an office
The closer is the part that fails most often, and in an office it fails under the hardest use in any building. A closer sized to BS EN 1154 for the leaf weight will close the leaf and hold the latch every time, but a closer that has been adjusted by hand, a closer with a leaking body, or a closer taken off because it was too stiff, will leave the leaf standing open. Our fire door closers guide sets out the power sizes in BS EN 1154 and how to read them.
Opening force is an office problem as much as a fire problem. A door must open with less than 30 N in the first 30 degrees and less than 22.5 N beyond that, under BS 8300 and Approved Document M, because staff push trolleys, wheelchairs and delivery cages through these doors all day. Hinges to BS EN 1935 carry the leaf, grade 13 or grade 14, and a hinge that has dropped lets the leaf sag, so the closer cannot close it squarely.
Seals and gaps are the small parts that decide the rating. A 4 mm gap around the leaf is the usual limit, and a doorset fitted with wider gaps has lost the performance the certificate describes. Intumescent seals close the gap in a fire, expanding at roughly 200 to 250 degrees, and smoke seals close it against cold smoke. Our fire door hardware guide sets out the hardware set, hinges, seals and latches included, and how each part is graded.
Card readers and maglocks: the access control that must still release
An office door often carries a card reader on the outside and a release button on the inside, and the two must work together. The reader keeps strangers out during the day, and the release must let everyone out in one action when the alarm sounds. A door that needs a card to open from the inside has no place on an escape route, and a door that needs a code has the same fault.
A maglock holds the leaf shut with a magnet, and it must release when the power fails or the alarm sounds. Test the release with the power off, not with the power on, because a lock that only releases on power has failed the test that matters. The release button should sit where a person in a crowd can reach it without looking, and it should work for a person carrying a box, a person in a wheelchair and a person who has never used the door before.
Keep the access control and the fire hardware on one schedule. The reader, the maglock, the closer, the hinges and the seals belong on the same line as the leaf and the frame, so a change to one part is checked against the rest. A closer changed for a stronger model can push the opening force past 30 N in the first 30 degrees, and a maglock fitted to a door that was never tested with one breaks the tested construction. The power sizes in BS EN 1154 are set out in our fire door closers guide.
When the floor plan moves: keeping the door schedule honest
An office floor is rarely the same floor a year later. Desks move, partitions move, a meeting room becomes two rooms, and each move changes the escape route the doors serve. A door that opened onto a corridor can open onto a dead end after a refit, and a door that served 40 people can serve 90 after a layout change. The schedule should be checked whenever the plan changes, not only when the doors are replaced.
The check is a walk, not a paper exercise. Walk the escape route from the deepest part of the floor to the final exit, and note every door on that route, the direction it opens and the hardware it carries. Check that the closer still brings the leaf back and holds the latch, that the seals are whole and the gaps are inside 4 mm, and that no door is wedged open for convenience. A wedged door will stand open in a fire, and a door that stands open cannot hold fire or smoke.
A door that serves more than 60 people needs panic hardware to BS EN 1125, with a bar across the leaf covering at least 60 percent of the leaf width. A bar that covers less than 60 percent of the leaf can be missed by a person in a crowd. Under BS 8300 and Approved Document M, a door must open with less than 30 N in the first 30 degrees and less than 22.5 N beyond that. The checks that catch a failing leaf before it matters are in our fire door inspection checklist, and our security turnstiles guide works through readers, fobs and biometrics and how the lane is wired into the access system.
| Part | What to look for | When |
|---|---|---|
| Closer | Leaf closes squarely and holds the latch | Every month |
| Seals and gaps | 4 mm gap, seals whole and fixed | Every month |
| Maglock and release | Releases with the power off | Every month |
| Escape route | No wedge, direction of escape clear | After every refit |
Ask for the test report and the classification with the doorset, and keep both with the door schedule, so the next responsible person can find the evidence without asking.
Ordering office fire doors: one specification, one set of evidence
Ordering fire doors for an office is a specification exercise, not a shopping exercise. The order should name the rating in full, FD30 or FD60 with the letter and the smoke rating where the strategy asks for it, and it should name the leaf, the frame, the glass, the beads, the seals and the hardware as one doorset. Our how to specify security doors guide covers the same discipline for rated security doors, and our types of security doors guide sets out the range of doors an office may need.
The security side needs its own evidence where the door must also resist attack. A server room door must hold fire and resist forced entry, and the two jobs need two sets of evidence on one assembly: a fire classification to EN 1634-1 and a forced entry rating to LPS 1175 or PAS 24. A steel leaf is strong, but strength is not a security rating, and a door rated FD60 can still fail a forced entry test. Our fire rated steel doors page covers the steel leaf that carries both jobs most often, and our server room doors guide covers the room that needs both jobs at once.
Finally, order the evidence with the doors. The test report, the classification and the hardware schedule should arrive with the doorset, and the handover pack should name the inspection routine the office will follow. Our fire door inspection checklist gives the checks that catch a failing leaf before it matters.
| Door position | Period | What it must do | What to check |
|---|---|---|---|
| Office floor door | FD30 | Let staff in and out, close and latch after every use | Closer, latch, hold-open release |
| Cross-corridor door | FD30 or FD60 | Hold the corridor as a compartment line | Gaps, seals, hold-open release |
| Stair core door | FD60 | Protect the stair while floors above move down | Smoke seals, closer, latch |
| Lift lobby door | FD30S | Hold smoke out of the stair and the lobby | Smoke seals, closer, 4 mm gaps |
| Plant and server room door | FD60 | Hold a higher-risk fire inside its own compartment | Seals, gaps, self-closing |
In an office, a fire door wedged open for a delivery is a door that cannot protect the people on the floor behind it.
Who is responsible for fire doors in a rented office?
The Regulatory Reform (Fire Safety) Order 2005 names a responsible person for the premises. In a workplace it is the employer, to the extent the workplace is under their control. In multi-let buildings the landlord or managing agent may hold duties for the common parts, and the law requires co-operation between the parties. A lease cannot remove the statutory duty from the person the Order names.
How often must fire doors be checked in an office?
The Order sets no fixed interval. Article 17 requires a suitable maintenance system, and the fire risk assessment sets the frequency. Record every check. The 3-month and 12-month schedules in the 2022 Regulations apply to residential blocks in England above 11 metres, and they do not extend to offices.
Do the Fire Safety (England) Regulations 2022 apply to my office?
No. They apply in England only, and regulation 10 covers buildings with two or more sets of domestic premises. Commercial premises follow the 2005 Order, and the check frequency comes from the fire risk assessment, not from a fixed statutory interval.
What is the difference between FD30 and FD60 in an office?
FD30 and FD60 are fire resistance periods tested to EN 1634-1, and the number is the minutes the doorset holds its rating in the furnace test. FD30 holds for 30 minutes and FD60 for 60 minutes. Office floor and meeting room doors commonly carry FD30, while stair core doors, plant rooms and server rooms commonly carry FD60, because the people and the contents behind them need more time. The fire strategy names the period for each opening.
Can an office fire door be held open?
Only with a hold-open device to BS EN 1155 that releases the door when the alarm sounds. A wedge, a chair or a hook on the wall has no such release, and a door held open by one of those will stand open in a fire. If a meeting room door needs to stand open, fit the right hold-open device and the right closer, so the door can stay open when the office needs it open and still close when it matters.