Security Doors for A and E Departments

An A and E department runs round the clock beside a resuscitation room and a drug store, so each leaf takes the LPS 1175 grade its room needs.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

The entrance leaf of an accident and emergency department carries B3 to LPS 1175 Issue 8.2, and the waiting area, the triage room, the treatment cubicles and the staff office carry the same grade, while the resuscitation room, the drug store and the plant room carry C5.

Issue 8.2 of LPS 1175 arrived in September 2024, and it grades a leaf by how long it resists attack, so B3 means three minutes, C5 means five minutes and D10 means ten minutes, and the older names SR2, SR3 and SR4 match B3, C5 and D10 in the same order.

An accident and emergency department takes patients through the clock, day and night, with ambulances arriving at the bays beside the entrance, a waiting area that fills through the evening, a triage room where each arrival is seen in turn, treatment cubicles where care runs behind shut leaves, and a resuscitation room where the most urgent cases are treated, so the leaves round those rooms must hold against a stranger while letting staff move fast between them.

  • B3 / C5Grades to LPS 1175 Issue 8.2
  • Round the clockPatients arrive day and night
  • Staff officeWhere patient records and keys are kept
  • Resuscitation roomWhere critical kit is kept behind the leaf

Eight leaves round an accident and emergency department: the grade each one carries

Eight leaves guard an accident and emergency department, and each leaf takes the grade that fits the room behind it, with B3 on the entrance, the waiting area, the triage room, the treatment cubicles and the staff office, and C5 on the resuscitation room, the drug store and the plant room.

The five leaves that patients and staff pass through the day hold for three minutes at B3, and the three leaves that guard critical kit, controlled drugs or plant hold for five minutes at C5.

Room Grade Period
Entrance B3 FD30
Waiting area B3 FD30
Triage B3 FD30
Treatment cubicles B3 FD30
Staff office B3 FD30
Resuscitation room C5 FD60
Drug store C5 FD60
Plant room C5 FD60

One leaf can carry proof of a fire period and a forced entry grade together, with both results in a single report for the same doorset, and the dual certification guide covers how a leaf is tested for fire and for forced entry in one report.

Entrance leaf where ambulances bring patients in

Ambulances pull up to the bays beside the entrance through the day and the night, and patients come in on trolleys through the entrance leaf, so that leaf holds B3 for three minutes while the desk keeps watch over the way in.

The bays stay open to the road, because they are arrival bays and not rooms, so no leaf grade is put on a bay, and the leaf that guards the department sits at the entrance behind them.

The front of the department needs the same care as the leaf itself, because a vehicle that reaches the entrance reaches the patients who wait there on trolleys, and ProtectUK sets the clear gap between bollards at no more than 1,200 mm, with a height of no less than 500 mm. The bollard guide covers the posts that stand at the front of the department.

Patients arrive on trolleys with both hands of the crew busy, so the entrance leaf must open without a push when a trolley is wheeled through, and it must shut again behind each arrival even when the waiting area is full. The automatic leaf guide covers leaves that open without a push when both hands are busy with a trolley.

Martyn’s Law received Royal Assent in April 2025, with tiers at 200 to 799 and 800 and above, a go live expected in spring 2027, the SIA as regulator and an advisory first approach. The Martyn’s Law guide covers the duties a busy entrance must meet.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

The entrance takes every arrival: trolleys pass and the reader answers each card

The entrance door of an accident and emergency department takes every arrival through the clock, and it carries B3 to LPS 1175 Issue 8, three minutes against attack. Ambulances bring patients in on trolleys, and the door is thrown open for each one, then it must shut behind them so the department stays shut to the street. The reader beside the door must answer a card in a rush, because a member of staff with a trolley has no hand to spare and no time to try twice.

Gloved hands in a hurry must turn this lock, and it must still hold for three minutes when the entrance stands empty. A three star set under TS 007 pairs a one star cylinder and a two star handle, and the pair is proved together, so the report names the lock that is fitted. The lock guide sets out the pair: cylinder and handle proved together, with one proof for both.

A door thrown open in a rush asks a lot of its hinges. Under BS EN 1935 a grade 13 hinge is proved to 200,000 cycles under 120 kg, and a grade 14 hinge takes that count under 160 kg, so the hinge must match the weight of the door it carries, and a door that sags never pulls its lock out of line. The frame guide names the frame that takes a door thrown open in a rush.

Part Grade or period Rush check
Door B3, three minutes Shuts behind each arrival
Lock 3 star set, TS 007 Turns fast for gloved hands
Hinge Grade 13, 200,000 cycles Door swings free without dragging
Frame Steel, proved with door No gap at the lock side

The door that shuts behind each arrival keeps the street outside

One report can carry both proofs for a single door. This door carries FD60 to EN 1634-1 beside a B3 grade to LPS 1175 Issue 8. The hour against fire and the three minutes against attack stand together in one report. The dual certification guide sets out one doorset proved for fire minutes and for a forced entry grade together.

A grade stands only while door, frame and hardware stay as they were proved. The entrance gets a try on the routine round, and a fault found there is written beside its own door the day it is found, because a reader that answers slowly and a door that shuts slowly fail the same arrival together. The reader is tried with a card on the same round, so a slow answer is found before the next ambulance arrives. The rating guide sets out which changes strip an LPS 1175 result from a fitted door, and the maintenance checklist sets out the checks for a door, its lock and its closer.

The department list goes to the quote page with the entrance first, grade and lock beside each room, so the door that takes every arrival is ordered to take the next one too.

Waiting area and triage leaves where arrivals are seen in turn

The waiting area holds the chairs where patients sit after they have been booked in, and its leaf takes B3, because the room fills through the evening and the leaf guards it again once the room empties and the patients have moved through to triage.

Patients wait in the waiting area, and the leaf on the way in must move fast for people who arrive in a group at the start of the evening. Under BS EN 1125, the push bar on a leaf that serves more than 60 people must span at least 60 percent of the leaf width.

Triage sees each arrival in turn, and the leaf on that room holds B3 for three minutes, because the notes made in triage decide where the patient goes next, and the leaf stays shut between patients. The panic hardware guide covers the bar that must open the leaf fast when the waiting area empties in a hurry.

An accident and emergency department is not a ward, because the patients who sit in its waiting area leave the same day after treatment, and a hospital asks more of its leaves across a whole building. The hospital door guide covers a building where wards stay full round the clock, while the GP surgery door guide covers a building where patients arrive without an ambulance at the door.

Treatment cubicle leaves where care runs behind a shut leaf

Treatment cubicles hold the beds and the trolleys where care runs, and the leaves round those cubicles take B3 and hold for three minutes, because the beds and the kit stay in place through the day and the leaf guards them between patients.

Staff push trolleys and wheeled beds through the cubicle leaves through the day, so a leaf must move under a light hand even when it carries B3. BS 8300 with Approved Document M keeps the push to open it under 30 N through the first 30 degrees of swing and under 22.5 N past that point.

Between patients the cubicles stand empty with the beds made ready, and the leaves round them stay shut until staff open them for the next arrival. A leaf left open between patients would let a stranger reach the kit unnoticed, so the leaf is drawn shut each time the cubicle empties and the key stays with the nurse on duty.

A cubicle leaf opens many times in a day, as staff come and go beside the beds, so the lock has to work fast for gloved hands and still hold for three minutes when the cubicle stands empty. A 1 star cylinder paired with a 2 star handle gives a 3 star set under TS 007, and the lock guide shows the cylinder and the handle working as one set.

Staff office leaf where records and keys are kept

Patient records and the keys for every other leaf live in the staff office, which is why that leaf holds B3 for three minutes and stays shut through the day and through the night.

The senior nurse and the charge nurse carry the key that opens every leaf in the department, while treatment cubicle keys open cubicles only, and no other key in the building opens the staff office, the drug store or the resuscitation room. The master key guide shows how the keys for the whole department sit together on one suite.

The LPS 1175 grades and the ASTM ratings have no published table that joins them, so the order names the LPS 1175 grade on its own and leaves the two sets apart, and the ASTM comparison guide covers how the two rating sets differ.

Resuscitation room leaf where critical kit stands ready

The resuscitation room holds the beds and the kit for the most urgent cases, and its leaf holds C5 for five minutes, because the controlled drugs and the critical kit behind it must stay guarded from the first arrival until the last.

Only a small group of key holders ever opens the resuscitation room, and the leaf stays shut between cases, so a fault comes to light on a routine visit by a key holder rather than through a stranger who wanders in. The steel frame guide covers the frame that carries the leaf and its lock together, while the hospital fire door guide covers the leaves on the wards beside the department.

Clean air matters beside the beds in the resuscitation room, and the room sits apart from the waiting area for that reason. The cleanroom door guide covers the leaves that keep dust and damp out of the room they guard.

The leaf that guards the room where the team works through the night

The most urgent cases are treated behind one leaf, where the beds and the kit stand ready, and the leaf holds C5 for five minutes to LPS 1175 Issue 8. The team is called in a rush and the leaf flies open, then it shuts behind them while they work, so the grade must hold in use and between cases alike. Few hands hold the key, and the room stands shut between cases, so a stranger who wanders in meets a locked leaf.

The lock has to answer to gloved hands in a hurry and still hold for five minutes when the room is empty. A cylinder with one star and a handle with two stars make a three star set under TS 007, and the two are proved as a pair, so the lock fitted is the lock the report names. The lock guide runs through the cylinder and the handle as a pair, and the proof they carry together.

Fire proof and forced entry proof can sit in one report for a single leaf. This leaf carries FD60 to EN 1634-1 with its C5 grade to LPS 1175 Issue 8, so the hour against fire and the five minutes against attack sit side by side in one report. The dual certification guide explains how fire minutes and a forced entry grade are proved on one doorset.

Part Grade or period Check
Leaf C5, five minutes Shut between cases
Lock 3 star set, TS 007 Turns fast for gloved hands
Frame Steel, proved with leaf No gap at the lock side
Period FD60, EN 1634-1 Report names leaf and frame

Opening in a rush and shutting behind the team

A leaf that is thrown open in a rush needs hinges that take its weight again and again. BS EN 1935 proves grade 13 hinges to 200,000 cycles under 120 kg and grade 14 to the same count under 160 kg, so the hinge is matched to the leaf it carries and a sagging leaf never drags its lock out of line. The steel frame guide sets out what the frame must do when the leaf is thrown open in a rush.

One key opens every leaf in the department, and it sits with the senior nurse and the charge nurse. The cubicle keys open cubicles and nothing more. No key taken from a cubicle opens the resuscitation room, the drug store or the staff office, so a lost cubicle key opens little. The master key guide explains which keys open the whole department and which open a single room.

A grade stands only while leaf, frame and hardware stay as they were tested. The room is tried on the routine round, and any fault is written beside its own leaf the day it is found. The rating guide names the changes that can take an LPS 1175 result off a fitted leaf, and the healthcare doors quote page prices the department room by room, grade and lock beside each leaf.

Drug store leaf where controlled drugs are kept under lock

Controlled drugs for the department are kept in the drug store, and its leaf holds C5 for five minutes, because the stock inside is counted and checked and the leaf guards it through the day and through the night.

Staff fetch drugs from the drug store at set points in the day, and the leaf shuts behind them each time, so the room is open for minutes at a time and shut for the rest of the day. Day case treatment runs beside a drug store in an oncology unit too, and the oncology unit door guide covers a building where that pattern holds.

The senior nurse holds the drug store key with the staff office key, and no treatment cubicle key opens the drug store, so a key taken from a cubicle opens nothing beyond the cubicles. The dental practice door guide covers a smaller building where medicines are kept behind a shut leaf.

Plant room leaf and the order: one line per leaf

Pumps, heaters and boards that warm the department and light the cubicles sit in the plant room, and its leaf holds C5 for five minutes, because the kit inside keeps the whole department running and the leaf is the only guard on it.

The department is busy all week, so the keys and the cards have to fit the people who hold them. One key in the senior nurse hand opens every leaf in the building, while treatment cubicle keys open cubicles only, and the plant room guide covers what the leaf on that room must do.

Every leaf in the department goes on one list for the order, with a line per leaf naming its room, grade, lock and closer, and each line is read back against its own room before the order is signed. The ten steps guide shows how to build that list, the LPS 1175 guide sets out the grades that sit behind it, and the specifying guide treats the leaf, the frame and the hardware as one doorset.

A grade holds only while the leaf, the frame and the hardware stay in the state they were tested in. The rating guide covers what keeps an LPS 1175 result in force, and the maintenance checklist covers the routine checks on each leaf, its lock and its closer.

Write one line per leaf with its room, grade, lock and closer, then check each line against its own room before the order leaves the department.

What grade should an A and E entrance door carry?

B3 to LPS 1175 Issue 8.2, a three minute hold, because patients arrive by ambulance through the day and the night and the desk watches the leaf from the first arrival to the last.

What grade should an A and E treatment cubicle door carry?

B3 to LPS 1175 Issue 8.2, because the cubicle leaf guards the beds and the kit where care runs behind a shut leaf.

What grade should an A and E drug store door carry?

C5 to LPS 1175 Issue 8.2, a five minute hold, because the controlled drugs for the department are counted and checked behind that leaf.

Can an A and E leaf hold a fire period and a security grade?

Yes, an A and E leaf can be proved for fire and for forced entry together, and the two results stand side by side in one report.

Who holds the keys in an A and E department?

The senior nurse and the charge nurse hold the key that opens every leaf, while treatment cubicle keys open cubicles only.

Specifying security doors for an A and E department?Send the list of rooms with the grade each leaf must carry, and ask for a quotation on tested doors.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →

Products

One supplier for the whole building envelope

Ready to specify your project?

Free assessment, written specification and test evidence. Reply within one working day.