A security door must do two jobs at once: keep the wrong people out and let everyone in. A leaf that meets its rating but will not open for a wheelchair user or a person with limited strength fails the building it serves. This guide explains what Approved Document M asks.
- 30 NForce limit, shut to 30 degrees
- 800 mmClear width, straight-on approach
- 15 mmHighest raised threshold
- 750-1000 mmHeight of powered door controls
Two rules every rated door must meet
Approved Document M Volume 2 gives the Building Regulations guidance for buildings other than dwellings. Its aim is plain: the principal entrance, main staff entrances and lobbies should be accessible to all.
The security rating answers a different question: how long the doorset holds against the tools named in its test. LPS 1175 Issue 8.2 (September 2024) rates the whole assembly, leaf, frame, hardware and glazing, from A1 to H20. A rating says nothing about who can open the leaf. Secured by Design lists LPS 1175 Issue 8.2 among doorset standards.
Ask for rating and access in one specification. Where the principal entrance will not be accessible, for example in an existing building, an alternative accessible entrance should be provided, with a route inside that reaches the same spaces. The communal entrance guide gives the same balance for a block entrance.
Clear width: the first check
Once open, every door to an accessible entrance must be wide enough for wheelchair users, luggage, assistance dogs, and pushchairs. Double buggies are wider than wheelchairs, so the width should allow for them.
Minimum clear widths run through a single leaf, or one leaf of a double leaf door. Straight on, without a turn: 800 mm new, 750 mm existing. At right angles to a route at least 1500 mm wide, the same figures; to a 1200 mm route, 825 mm new and 775 mm existing. External doors to buildings used by the general public: 1000 mm new, 775 mm existing.
Clear width is measured at right angles to the wall, from the door stop on the closing side to any obstruction on the hinge side. A leaf that meets its rating but loses width to its own furniture still fails. The automatic doors guide takes powered leaves apart, operator and sensors included.
Opening force: the heavy leaf test
A manually operated entrance door that is not powered must open with a force at the leading edge of no more than 30 newtons from shut to 30 degrees open, and no more than 22.5 newtons from 30 to 60 degrees. The same limits apply to doors inside the building opened by hand.
A heavy rated leaf with a self-closing device is where the test bites. A non-powered door fitted with a closer strong enough to work against wind and draught seals is unlikely to be openable by many people, particularly wheelchair users. Self-closing devices disadvantage people with limited strength, people pushing prams, and people carrying heavy objects.
Where a self-closing leaf is required and a person will not manage the force, a power-operated opening and closing system must be used. A lobby can allow a closer of lower power, but the force limits may still not be met. The fire door closers guide gives the power sizes and the test for a closer.
Thresholds, furniture, pull side
The route across the threshold should give weather protection without presenting a barrier to a wheelchair user or a trip hazard. A level threshold is preferred, especially for doors in frequent use. Where a raised threshold is unavoidable, its total height must be no more than 15 mm, and any upstand over 5 mm chamfered or rounded.
Space beside the leaf matters as much as the leaf. There must be an unobstructed space of at least 300 mm on the pull side, between the leading edge and any return wall, unless the door is powered. The space lets a wheelchair user reach and grip the handle, then open the door without releasing hold.
Door furniture must be easy to work with limited manual dexterity, and easy to see against the door. A latch must work with one hand using a closed fist, a lever handle, and contrast with the door surface without feeling cold to the touch. Door entry systems must be usable by deaf and hard of hearing people and by people who cannot speak. The security door locks guide gives the locking choices.
Powered doors and fail-safe
A powered opening and closing system is the most satisfactory answer for most people. An automatic sliding arrangement is particularly useful, as it avoids the risks of swing doors and can shorten the entrance lobby. Powered entrance doors may slide, swing or fold, worked by hand or by sensor.
Sensors must be set so the doors open early enough and stay open long enough for safe entry and exit. Swing doors that open towards people approaching need visual and audible warnings. The doors must carry a safety stop that works if they close on a person, and must revert to manual control or fail safe in the open position if the power fails. When open, they must not project into any adjacent access route.
Manual controls for a powered door must sit between 750 mm and 1000 mm above floor level, work with a closed fist, and, when on the opening side, sit back 1400 mm from the leading edge when fully open. The lockdown hardware guide gives the fail-safe and fail-secure rules, and the access control guide gives the entry system behind the leaf.
Glass, vision panels, being seen
People should see others approaching from the opposite direction. Exceptions may be acceptable for privacy or security, but the starting point is that the door is seen and seen through. A person with visual impairment should be in no doubt where a glass door sits, and a different style of manifestation for door and screen helps tell them apart.
The door should be apparent not only when it is shut but also when it is open. Where a leaf can be held open, steps should be taken to avoid people walking into it. Glass doors and glazed screens must comply with Approved Document K, Section 7.
Doors inside the building carry the same rule. In leaves or side panels wider than 450 mm, vision panels must include at least the zone from 500 mm to 1500 mm above the floor, broken from 800 mm to 1150 mm for an intermediate rail. Door frames must contrast with the surrounding wall, and the leading edge of a leaf that is not self-closing, or is likely to be held open, must contrast with the other surfaces. The panic hardware guide covers bars and pads for a leaf on an escape route.
Lobbies, corridors, the route inside
A lobby limits air infiltration, controls draughts, increases security, and gives transitional lighting. It must be large enough for a wheelchair user, with or without a companion, or a person pushing a pram, to move clear of one door before opening the second.
With double swing doors the lobby length must be at least the two door projections plus 1570 mm. Its width must be at least 1200 mm, or the leaf width plus 300 mm, whichever is greater, for single leaf doors, and at least 1800 mm for double leaf doors. Floor surfaces inside the lobby must not impede wheelchairs, mat wells must sit level with the adjacent floor, and columns or ducts that project more than 100 mm must carry a guard rail.
A door opening towards a corridor that is a major access route or an escape route must be recessed so that, when fully open, it does not project into the corridor, except for minor utility facilities. Fire doors in corridors are held open with an electro-magnetic device, but self-close on smoke detectors, a hand switch, or a power failure. The emergency exit guide gives the escape rules for a crowded building, and the commissioning guide gives the tests that prove each unit on site. The revolving doors guide covers the one leaf type the document does not count as accessible, and the installation handover guide holds the checks for each opening.
| Item | What the document asks | What it means for a rated door |
|---|---|---|
| Clear width | 800 mm straight on; 1000 mm public | Leaf and furniture must leave it |
| Opening force | 30 N to 30 degrees, 22.5 N to 60 degrees | A heavy leaf needs power, not strength |
| Threshold | Level preferred, raised no more than 15 mm | Weather seal must not become a step |
| Pull side | 300 mm clear beside the leading edge | Room to grip, pull and pass through |
| Vision panel | Zone 500 to 1500 mm above the floor | See who approaches from the other side |
A rating proves the leaf holds against attack. Access proves everyone can use it. Ask for both, or the door fails one of its two jobs.
What opening force must a security door meet?
Thirty newtons to 30 degrees open, then 22.5 newtons to 60 degrees.
What clear width does a rated entrance door need?
800 mm straight on, 825 mm at right angles to a 1200 mm route, 1000 mm at a public entrance.
Can a heavy rated leaf stay manually operated?
Only where the force limits are met. If a person will not manage the force, power must do it.
What happens to a powered door when the power fails?
It must fall back to hand control or stay open.
Is a revolving door an accessible entrance?
No. A revolving door needs an accessible leaf beside it, signed so people can find it.