Fire Rated Sliding Doors Explained

Yes, a sliding door can be fire rated. How a sliding fire doorset is tested, where it fits, and why it never stands on an escape route in a fire.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

Yes. A sliding door can be fire rated, when the complete doorset was tested together and classified for fire. The leaf, the track, the guides, the seals and the closing device were tested as one assembly to BS EN 1634-1, classified to BS EN 13501-2, and supplied under the product standard BS EN 16034. A swing door certificate does not cover a sliding leaf, and a security rating does not prove a fire rating. Where a swing leaf would hit racking, equipment or people, or where the opening is too wide for a hinged leaf, the sliding fire door is the product that fills the opening, and it closes the compartment line on its own when the alarm sounds.

  • E30 to EI120Integrity and insulation classifications on tested sliding doorsets
  • BS EN 1634-1The furnace test behind the classification
  • BS EN 15269-7Extended application for steel sliding doorsets
  • Not an escape doorA sliding door does not stand on an escape route

Can a sliding door be fire rated?

A sliding door can be fire rated when the doorset was tested as a sliding doorset. The fire test is BS EN 1634-1, and the test specimen is the whole assembly: leaf, frame, track, suspension, guides, seals and closing device, built into the tested wall type. The result is classified to BS EN 13501-2, and the doorset is supplied under the product standard BS EN 16034 with a Declaration of Performance. Ask for all three by name: test, classification and product standard. One without the others leaves a gap in the evidence.

The extended application standard for steel sliding doorsets is BS EN 15269-7. It covers horizontally sliding doorsets in single and double leaf form, telescopic doorsets in single and double form, and single vertically sliding doorsets, and it sets out how test results from BS EN 1634-1 can be extended to other sizes and constructions. A doorset outside the tested range needs its own evidence, and the extended application report is the document that reaches it.

The rating belongs to the exact configuration that was tested. A certificate for a single leaf does not cover a bi-parting pair, and a certificate for a manual leaf does not cover a powered leaf. The leaf count, the track type, the guide arrangement and the closing device must all match the certificate, because each of them carries the rating. Our sliding security doors page shows the same rule on the security side, and our fire ratings page gives the classifications in full.

The leaf, the track and the seals as one tested assembly

On a swing door the hinges take the load. On a sliding door it is the track and the guide, and in a fire the leaf must stay on its track and keep the gap closed while the furnace heat works on it. A leaf that lifts off its track, or a bottom guide that lets the leaf swing out of its line, leaves a gap the fire passes through. The tested assembly therefore includes continuous top and bottom guides, anti-lift devices that stop the leaf being raised clear of the track, and fixings that anchor the track into the structure around the opening.

The seals close the gaps the leaf cannot close on its own. Intumescent seals expand in heat and seal the gap around the leaf, and the meeting stiles on a bi-parting pair need their own seals so the centre cannot leak. A seal fitted after the test, or a seal of a different profile from the one in the test evidence, is a change to the tested assembly, and the rating does not follow the change.

The wall the track is fixed to is part of the evidence. A doorset tested on a rigid wall, such as masonry, has not shown what it does on a flexible wall, such as timber stud, and the classification can differ between them. The specification must name the wall type the track will be fixed to, and the evidence must cover that wall type. The threshold needs the same care: a bottom guide recessed flush with the floor keeps the leaf in line without a trip hazard, and debris in the track is a failure in waiting, because a leaf that cannot close fully cannot seal. For how the two ratings sit together on one doorset, see our dual certification guide.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

E, EW and EI on a leaf that slides

Sliding doorsets are classified with the same letters as swing doorsets, and the letters mean the same things. E is integrity: the doorset stops flames and hot gases passing through for the stated time. EW adds a limit on radiated heat from the unexposed face. EI adds a limit on temperature rise on the unexposed face. The letter is always paired with minutes: E 60 is a complete statement, and E on its own is not.

Most sliding fire doorsets carry an E or EI classification, in periods from 30 to 120 minutes depending on the tested construction. EI matters where people must pass close to the door, or where the fire strategy needs insulation as well as integrity, because a steel leaf carries heat to the unexposed face. Where the strategy needs insulation and the leaf cannot carry it, the fire engineer may call for a different product, such as a fire rated doorset with an EI classification. Our fire rated steel doors cover the swing doorset side.

The period comes from the fire strategy, not from the door. The fire engineer marks the compartment walls on the plan and assigns a period to each opening, and the door schedule follows that plan opening by opening. A door ordered before the compartment plan is settled can arrive with the wrong rating for the wall it guards. Get the plan first, then order. Where the opening also needs glazing, our fire rated glazed doors must meet the fire test and the acoustic test on the same construction, and our acoustic doors guide sets out how the two ratings sit together.

Where a sliding fire door belongs

A sliding fire door belongs where a swing leaf cannot do the job. Warehouses and logistics buildings use them on wide openings between storage and dispatch, where a swing leaf would hit racking or forklifts. Plant rooms use them where the leaf would swing into equipment. Corridors in hospitals use them where a swing leaf would swing into beds and trolleys, and where the leaf must stay clear of the route when it is open. For the warehouse side, see our warehouses and logistics page, and for plant rooms, see our plant room door requirements guide.

The sliding leaf also suits openings that must stay clear for trolleys and beds while the door is open, and then close the compartment line when the alarm sounds. A swing leaf held open all day is a door that may never be closed, while a sliding leaf held open by an electromagnetic hold-open device closes on its own when the alarm releases it. Hospitals face the same sequence on ward and kitchen openings, as our hospital security doors guide shows for the security side.

The sliding leaf is the wrong product where the opening is also an escape route, and that limit is set out in the next sections. It is also the wrong product where the opening is narrow enough for a swing leaf: a swing fire door is simpler, cheaper to maintain, and carries an EI classification the sliding leaf may not. Where the opening is wide and high, and a single leaf cannot cover it, a fire rated roller shutter may be the answer instead, and our fire rated roller shutters page sets out that product.

Self-closing on a sliding leaf: how the door shuts itself

A fire door must close on its own, and a sliding leaf is no exception. A sliding fire door spends its working life open and must close without anyone touching it when the alarm sounds. Three closing methods are used, and the specification must name which one the doorset carries.

A spring closer or a counterweight drive pulls the leaf shut along its track when the hold-open device releases. It needs no power and no signal, and it acts on the leaf itself. A powered leaf closes on a signal from the fire alarm, driven along its track by its motor, and it needs a fail-safe that closes the leaf if the power fails. An electromagnetic hold-open device holds the leaf open in normal use and releases it when the alarm sounds. Whichever method is used, it must be tested as part of the doorset: a closer or a motor added afterwards is not part of the evidence.

The close must be controlled and complete. The leaf must travel the full length of its track and meet its seals, because a leaf that stops short leaves a gap the fire passes through, and the rating applies to the door closed, not the door nearly closed. The closing speed must be slow enough not to injure anyone in the opening. Powered sliders need a manual override, so the leaf can still be opened from the escape side if the power fails or the controls are damaged, and the override must work without tools or specialist knowledge. Test the override during commissioning, not during an emergency.

Escape routes: the limit every specifier must respect

A sliding fire door is a compartment door, not an escape door. Approved Document B guidance is that doors on escape routes should open in the direction of escape and be readily openable, and that sliding doors are not permitted as emergency exits. A sliding leaf does not swing open in the direction of escape, and a person pushing against it in a crowd cannot open it the way a swing leaf opens. The fire strategy must therefore show escape independent of every sliding leaf, so the sliding door and the escape route are planned as separate things.

Where an opening is also an escape route, use a swing fire door. The swing leaf opens in the direction of escape, it can be fitted with panic hardware that releases from the escape side, and it can be held open by a device linked to the alarm. Our fire rated steel doors cover the swing doorset, and our flat entrance doors guide shows a swing doorset that carries fire and security ratings together.

Where the sliding leaf divides a corridor, the fire strategy must still give people a way out that does not depend on the sliding leaf. That way out is usually a swing door in the same wall, or a different route altogether. If the opening has no other escape route, the sliding leaf is the wrong product for that opening, however well it fits the space. For the rules the strategy follows, see our fire door regulations for commercial buildings guide.

Evidence for a sliding doorset: what to ask for before you order

Ask for the evidence before the order is placed, not after the door arrives. The table below lists what to ask for and what each item proves.

Evidence What it must state Why it matters
Test report BS EN 1634-1, classification, exact doorset, leaf count, sizes and supporting construction Proves the doorset was furnace tested as it will be supplied
Classification report BS EN 13501-2, letter and minutes, rigid or flexible construction Turns the test result into the rating the strategy uses
Declaration of Performance BS EN 16034, CE or UKCA marking, doorset type and sizes Proves the product standard and marking behind the doorset
Extended application BS EN 15269-7 where size or construction differs from the test Reaches doorsets outside the tested range
Closing evidence Self-closing device, hold-open release, manual override, closing to the seals Proves the leaf closes on its own when it matters

Compare the submittal with the evidence line by line before the order is signed. Where the evidence is missing, or the leaf count, sizes or wall type do not match, the order should wait: a door ordered on a promise and evidenced later is a door that may have to come out again. For how to read the ratings on a certificate, see our how to specify security doors guide, and for the changes that cause problems after installation, see our keeping an LPS 1175 rating valid guide.

Keeping a sliding fire door working: inspection and testing

A sliding fire door is only as good as its last test. The closing must be tested at planned intervals by triggering the release and watching the leaf travel the full length of its track and meet its seals, and each test must be recorded with the date, what was checked, what was found and who did it. Keep those records with the fire safety records for the building, and make sure the fire risk assessment names who checks the door and how often.

The parts that wear are the parts that move the leaf: the rollers, the track, the guides and the closing device. Tracks collect dirt, rollers wear flat, and a leaf that has not moved for months can stick in its guides. A planned service visit keeps the leaf free to move, and a door that is never tested is a door whose failure is found in a fire, not in a service visit. Our fire door inspection checklist applies the same discipline to doorsets, and our maintenance page gives planned servicing and records.

Any change to the doorset needs fresh evidence. A new motor, a different closer, a re-sized leaf or a change to the wall around the opening takes the doorset outside its tested assembly, and the rating does not follow the change. Record the tested configuration at handover, with the certificate and the inspection intervals, so the next person to work on the opening knows what must not change.

A sliding fire door that cannot close on its own is a partition with a gap in it. Test the close, not the label.

Can a sliding door be fire rated?

Yes, when the complete doorset was tested as a sliding doorset to BS EN 1634-1 and classified to BS EN 13501-2. The leaf, track, guides, seals and closing device must all match the test evidence, and the extended application standard for steel sliding doorsets is BS EN 15269-7.

Can a sliding fire door be used on an escape route?

No. Approved Document B guidance is that sliding doors are not permitted as emergency exits, because a sliding leaf does not open in the direction of escape. A sliding fire door is a compartment door, and escape must be provided by another route or a swing door.

What fire rating do I need for my sliding door?

The period comes from the building’s fire strategy, not from the door. Ask the fire engineer for the schedule and specify a doorset tested to match it. Do not guess the period, and do not buy a longer rating than the strategy asks for.

Does a sliding fire door stop smoke?

Not on its fire classification alone. Smoke control needs its own test to BS EN 1634-3 and its own evidence, and an E60 doorset has not shown anything about cold smoke passing around its edges. Name both performances in the specification where the strategy needs both.

Can a sliding fire door also be a security door?

Yes, where the same construction has been tested for both. A fire rating says nothing about forced entry, and a security rating says nothing about fire. For how the two ratings sit together, see our dual certification guide, and for the security side of sliding doors, see our sliding security doors page.

What a sliding fire door does not cover

A fire rating belongs to one tested assembly. The leaf, the track, the seals and the frame were tested together to EN 1634-1, and the rating covers that exact combination for the stated minutes, E, EW or EI from 30 to 120. Change one part and the rating no longer describes what stands in the opening. Check the evidence against the doorset on site before the order is placed.

The rating does not prove the door suits an escape route. A sliding leaf is not normally on an escape route, because a person escaping a fire needs a door that opens with a push. A sliding leaf needs a pull or a powered drive to open. Panic hardware to BS EN 1125 is made for hinged leaves that swing open under pressure. Where the fire strategy names an escape route, the door on that route is a hinged leaf.

The rating does not cover the wall and the pocket the leaf slides into. The leaf disappears into a pocket in the wall, and the wall around that pocket must hold back fire for the same minutes as the leaf. A leaf rated EI60 in a 30 minute wall gives a 30 minute opening. Check the wall and the pocket lining against the fire strategy.

The rating does not prove smoke control unless the doorset was tested for it. A fire rating to EN 1634-1 tests flame and heat, and smoke passes through a cold gap long before heat reaches the seals. Smoke control needs a Sa or S200 test to BS EN 1634-3. Intumescent seals expand at roughly 200 to 250 degrees, so they do nothing against cold smoke. Ask for the Sa or S200 evidence by name where the strategy asks for smoke control.

Mistakes that stop a sliding leaf closing

A sliding fire door fails most often in small ways. The leaf is heavy, the track is long, and the closing device has to pull that weight home and hold the latch every time. Each mistake below has the same result: a leaf that stands open when fire breaks out, and a rating that counts for nothing.

Mistake Why it fails What to do instead
Track left obstructed Dust or stored goods stop the rollers, so the leaf never latches. Keep the full track clear.
Seals painted over Paint stops intumescent seals expanding in heat, so the gap to the frame stays open. Tell decorators the seals are never to be coated.
Closer disconnected A closer taken off leaves the leaf where it was last pushed, often standing open. Refit the closer, sized to BS EN 1154 for the leaf weight.
Wrong leaf weight on the track Rollers rated below the leaf weight wear fast and drag the leaf to a stop. Match the track and hangers to the leaf weight.
No evidence held on site Without the test report, nobody can check the doorset against what was tested. File the evidence with the building records.

A closer sized for a hinged leaf will not close a sliding leaf, because the force needed changes along the track. Our fire door closers guide sets out the power sizes in BS EN 1154 and how to read them, and our fire door inspection checklist gives the checks that catch a failing leaf before it matters.

Need a fire rated sliding door for an opening a swing leaf cannot serve?Send the opening sizes, the wall type and the rating from your fire strategy for a tested sliding doorset quotation.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →

Products

One supplier for the whole building envelope

Ready to specify your project?

Free assessment, written specification and test evidence. Reply within one working day.