Fire Rated Sliding Doors Explained
Yes, a sliding door can be fire rated. How a sliding fire doorset is tested, where it fits, and why it never stands on an escape route in a fire.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
Yes. A sliding door can be fire rated, when the complete doorset was tested together and classified for fire. The leaf, the track, the guides, the seals and the closing device were tested as one assembly to BS EN 1634-1, classified to BS EN 13501-2, and supplied under the product standard BS EN 16034. A swing door certificate does not cover a sliding leaf, and a security rating does not prove a fire rating. Where a swing leaf would hit racking, equipment or people, or where the opening is too wide for a hinged leaf, the sliding fire door is the product that fills the opening, and it closes the compartment line on its own when the alarm sounds.
- E30 to EI120Integrity and insulation classifications on tested sliding doorsets
- BS EN 1634-1The furnace test behind the classification
- BS EN 15269-7Extended application for steel sliding doorsets
- Not an escape doorA sliding door does not stand on an escape route
Can a sliding door be fire rated?
A sliding door can be fire rated when the doorset was tested as a sliding doorset. The fire test is BS EN 1634-1, and the test specimen is the whole assembly: leaf, frame, track, suspension, guides, seals and closing device, built into the tested wall type. The result is classified to BS EN 13501-2, and the doorset is supplied under the product standard BS EN 16034 with a Declaration of Performance. Ask for all three by name: test, classification and product standard. One without the others leaves a gap in the evidence.
The extended application standard for steel sliding doorsets is BS EN 15269-7. It covers horizontally sliding doorsets in single and double leaf form, telescopic doorsets in single and double form, and single vertically sliding doorsets, and it sets out how test results from BS EN 1634-1 can be extended to other sizes and constructions. A doorset outside the tested range needs its own evidence, and the extended application report is the document that reaches it.
The rating belongs to the exact configuration that was tested. A certificate for a single leaf does not cover a bi-parting pair, and a certificate for a manual leaf does not cover a powered leaf. The leaf count, the track type, the guide arrangement and the closing device must all match the certificate, because each of them carries the rating. Our sliding security doors page shows the same rule on the security side, and our fire ratings page gives the classifications in full.
The leaf, the track and the seals as one tested assembly
On a swing door the hinges take the load. On a sliding door it is the track and the guide, and in a fire the leaf must stay on its track and keep the gap closed while the furnace heat works on it. A leaf that lifts off its track, or a bottom guide that lets the leaf swing out of its line, leaves a gap the fire passes through. The tested assembly therefore includes continuous top and bottom guides, anti-lift devices that stop the leaf being raised clear of the track, and fixings that anchor the track into the structure around the opening.
The seals close the gaps the leaf cannot close on its own. Intumescent seals expand in heat and seal the gap around the leaf, and the meeting stiles on a bi-parting pair need their own seals so the centre cannot leak. A seal fitted after the test, or a seal of a different profile from the one in the test evidence, is a change to the tested assembly, and the rating does not follow the change.
The wall the track is fixed to is part of the evidence. A doorset tested on a rigid wall, such as masonry, has not shown what it does on a flexible wall, such as timber stud, and the classification can differ between them. The specification must name the wall type the track will be fixed to, and the evidence must cover that wall type. The threshold needs the same care: a bottom guide recessed flush with the floor keeps the leaf in line without a trip hazard, and debris in the track is a failure in waiting, because a leaf that cannot close fully cannot seal. For how the two ratings sit together on one doorset, see our dual certification guide.
E, EW and EI on a leaf that slides
Sliding doorsets are classified with the same letters as swing doorsets, and the letters mean the same things. E is integrity: the doorset stops flames and hot gases passing through for the stated time. EW adds a limit on radiated heat from the unexposed face. EI adds a limit on temperature rise on the unexposed face. The letter is always paired with minutes: E 60 is a complete statement, and E on its own is not.
Most sliding fire doorsets carry an E or EI classification, in periods from 30 to 120 minutes depending on the tested construction. EI matters where people must pass close to the door, or where the fire strategy needs insulation as well as integrity, because a steel leaf carries heat to the unexposed face. Where the strategy needs insulation and the leaf cannot carry it, the fire engineer may call for a different product, such as a fire rated doorset with an EI classification. Our fire rated steel doors cover the swing doorset side.
The period comes from the fire strategy, not from the door. The fire engineer marks the compartment walls on the plan and assigns a period to each opening, and the door schedule follows that plan opening by opening. A door ordered before the compartment plan is settled can arrive with the wrong rating for the wall it guards. Get the plan first, then order. Where the opening also needs glazing, our fire rated glazed doors must meet the fire test and the acoustic test on the same construction, and our acoustic doors guide sets out how the two ratings sit together.
Where a sliding fire door belongs
A sliding fire door belongs where a swing leaf cannot do the job. Warehouses and logistics buildings use them on wide openings between storage and dispatch, where a swing leaf would hit racking or forklifts. Plant rooms use them where the leaf would swing into equipment. Corridors in hospitals use them where a swing leaf would swing into beds and trolleys, and where the leaf must stay clear of the route when it is open. For the warehouse side, see our warehouses and logistics page, and for plant rooms, see our plant room door requirements guide.
The sliding leaf also suits openings that must stay clear for trolleys and beds while the door is open, and then close the compartment line when the alarm sounds. A swing leaf held open all day is a door that may never be closed, while a sliding leaf held open by an electromagnetic hold-open device closes on its own when the alarm releases it. Hospitals face the same sequence on ward and kitchen openings, as our hospital security doors guide shows for the security side.
The sliding leaf is the wrong product where the opening is also an escape route, and that limit is set out in the next sections. It is also the wrong product where the opening is narrow enough for a swing leaf: a swing fire door is simpler, cheaper to maintain, and carries an EI classification the sliding leaf may not. Where the opening is wide and high, and a single leaf cannot cover it, a fire rated roller shutter may be the answer instead, and our fire rated roller shutters page sets out that product.
Self-closing on a sliding leaf: how the door shuts itself
A fire door must close on its own, and a sliding leaf is no exception. A sliding fire door spends its working life open and must close without anyone touching it when the alarm sounds. Three closing methods are used, and the specification must name which one the doorset carries.
A spring closer or a counterweight drive pulls the leaf shut along its track when the hold-open device releases. It needs no power and no signal, and it acts on the leaf itself. A powered leaf closes on a signal from the fire alarm, driven along its track by its motor, and it needs a fail-safe that closes the leaf if the power fails. An electromagnetic hold-open device holds the leaf open in normal use and releases it when the alarm sounds. Whichever method is used, it must be tested as part of the doorset: a closer or a motor added afterwards is not part of the evidence.
The close must be controlled and complete. The leaf must travel the full length of its track and meet its seals, because a leaf that stops short leaves a gap the fire passes through, and the rating applies to the door closed, not the door nearly closed. The closing speed must be slow enough not to injure anyone in the opening. Powered sliders need a manual override, so the leaf can still be opened from the escape side if the power fails or the controls are damaged, and the override must work without tools or specialist knowledge. Test the override during commissioning, not during an emergency.
Escape routes: the limit every specifier must respect
A sliding fire door is a compartment door, not an escape door. Approved Document B guidance is that doors on escape routes should open in the direction of escape and be readily openable, and that sliding doors are not permitted as emergency exits. A sliding leaf does not swing open in the direction of escape, and a person pushing against it in a crowd cannot open it the way a swing leaf opens. The fire strategy must therefore show escape independent of every sliding leaf, so the sliding door and the escape route are planned as separate things.
Where an opening is also an escape route, use a swing fire door. The swing leaf opens in the direction of escape, it can be fitted with panic hardware that releases from the escape side, and it can be held open by a device linked to the alarm. Our fire rated steel doors cover the swing doorset, and our flat entrance doors guide shows a swing doorset that carries fire and security ratings together.
Where the sliding leaf divides a corridor, the fire strategy must still give people a way out that does not depend on the sliding leaf. That way out is usually a swing door in the same wall, or a different route altogether. If the opening has no other escape route, the sliding leaf is the wrong product for that opening, however well it fits the space. For the rules the strategy follows, see our fire door regulations for commercial buildings guide.
Evidence for a sliding doorset: what to ask for before you order
Ask for the evidence before the order is placed, not after the door arrives. The table below lists what to ask for and what each item proves.
| Evidence | What it must state | Why it matters |
|---|---|---|
| Test report | BS EN 1634-1, classification, exact doorset, leaf count, sizes and supporting construction | Proves the doorset was furnace tested as it will be supplied |
| Classification report | BS EN 13501-2, letter and minutes, rigid or flexible construction | Turns the test result into the rating the strategy uses |
| Declaration of Performance | BS EN 16034, CE or UKCA marking, doorset type and sizes | Proves the product standard and marking behind the doorset |
| Extended application | BS EN 15269-7 where size or construction differs from the test | Reaches doorsets outside the tested range |
| Closing evidence | Self-closing device, hold-open release, manual override, closing to the seals | Proves the leaf closes on its own when it matters |
Compare the submittal with the evidence line by line before the order is signed. Where the evidence is missing, or the leaf count, sizes or wall type do not match, the order should wait: a door ordered on a promise and evidenced later is a door that may have to come out again. For how to read the ratings on a certificate, see our how to specify security doors guide, and for the changes that cause problems after installation, see our keeping an LPS 1175 rating valid guide.
Keeping a sliding fire door working: inspection and testing
A sliding fire door is only as good as its last test. The closing must be tested at planned intervals by triggering the release and watching the leaf travel the full length of its track and meet its seals, and each test must be recorded with the date, what was checked, what was found and who did it. Keep those records with the fire safety records for the building, and make sure the fire risk assessment names who checks the door and how often.
The parts that wear are the parts that move the leaf: the rollers, the track, the guides and the closing device. Tracks collect dirt, rollers wear flat, and a leaf that has not moved for months can stick in its guides. A planned service visit keeps the leaf free to move, and a door that is never tested is a door whose failure is found in a fire, not in a service visit. Our fire door inspection checklist applies the same discipline to doorsets, and our maintenance page gives planned servicing and records.
Any change to the doorset needs fresh evidence. A new motor, a different closer, a re-sized leaf or a change to the wall around the opening takes the doorset outside its tested assembly, and the rating does not follow the change. Record the tested configuration at handover, with the certificate and the inspection intervals, so the next person to work on the opening knows what must not change.
A sliding fire door that cannot close on its own is a partition with a gap in it. Test the close, not the label.
Can a sliding door be fire rated?
Yes, when the complete doorset was tested as a sliding doorset to BS EN 1634-1 and classified to BS EN 13501-2. The leaf, track, guides, seals and closing device must all match the test evidence, and the extended application standard for steel sliding doorsets is BS EN 15269-7.
Can a sliding fire door be used on an escape route?
No. Approved Document B guidance is that sliding doors are not permitted as emergency exits, because a sliding leaf does not open in the direction of escape. A sliding fire door is a compartment door, and escape must be provided by another route or a swing door.
What fire rating do I need for my sliding door?
The period comes from the building’s fire strategy, not from the door. Ask the fire engineer for the schedule and specify a doorset tested to match it. Do not guess the period, and do not buy a longer rating than the strategy asks for.
Does a sliding fire door stop smoke?
Not on its fire classification alone. Smoke control needs its own test to BS EN 1634-3 and its own evidence, and an E60 doorset has not shown anything about cold smoke passing around its edges. Name both performances in the specification where the strategy needs both.
Can a sliding fire door also be a security door?
Yes, where the same construction has been tested for both. A fire rating says nothing about forced entry, and a security rating says nothing about fire. For how the two ratings sit together, see our dual certification guide, and for the security side of sliding doors, see our sliding security doors page.
What a sliding fire door does not cover
A fire rating belongs to one tested assembly. The leaf, the track, the seals and the frame were tested together to EN 1634-1, and the rating covers that exact combination for the stated minutes, E, EW or EI from 30 to 120. Change one part and the rating no longer describes what stands in the opening. Check the evidence against the doorset on site before the order is placed.
The rating does not prove the door suits an escape route. A sliding leaf is not normally on an escape route, because a person escaping a fire needs a door that opens with a push. A sliding leaf needs a pull or a powered drive to open. Panic hardware to BS EN 1125 is made for hinged leaves that swing open under pressure. Where the fire strategy names an escape route, the door on that route is a hinged leaf.
The rating does not cover the wall and the pocket the leaf slides into. The leaf disappears into a pocket in the wall, and the wall around that pocket must hold back fire for the same minutes as the leaf. A leaf rated EI60 in a 30 minute wall gives a 30 minute opening. Check the wall and the pocket lining against the fire strategy.
The rating does not prove smoke control unless the doorset was tested for it. A fire rating to EN 1634-1 tests flame and heat, and smoke passes through a cold gap long before heat reaches the seals. Smoke control needs a Sa or S200 test to BS EN 1634-3. Intumescent seals expand at roughly 200 to 250 degrees, so they do nothing against cold smoke. Ask for the Sa or S200 evidence by name where the strategy asks for smoke control.
Mistakes that stop a sliding leaf closing
A sliding fire door fails most often in small ways. The leaf is heavy, the track is long, and the closing device has to pull that weight home and hold the latch every time. Each mistake below has the same result: a leaf that stands open when fire breaks out, and a rating that counts for nothing.
| Mistake | Why it fails | What to do instead |
|---|---|---|
| Track left obstructed | Dust or stored goods stop the rollers, so the leaf never latches. | Keep the full track clear. |
| Seals painted over | Paint stops intumescent seals expanding in heat, so the gap to the frame stays open. | Tell decorators the seals are never to be coated. |
| Closer disconnected | A closer taken off leaves the leaf where it was last pushed, often standing open. | Refit the closer, sized to BS EN 1154 for the leaf weight. |
| Wrong leaf weight on the track | Rollers rated below the leaf weight wear fast and drag the leaf to a stop. | Match the track and hangers to the leaf weight. |
| No evidence held on site | Without the test report, nobody can check the doorset against what was tested. | File the evidence with the building records. |
A closer sized for a hinged leaf will not close a sliding leaf, because the force needed changes along the track. Our fire door closers guide sets out the power sizes in BS EN 1154 and how to read them, and our fire door inspection checklist gives the checks that catch a failing leaf before it matters.