Hotel Fire Doors

Fire door rules for hotels: FD30S bedroom doors, corridor and stair core doors, escape routes for guests, and the schedule that orders them all.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

A hotel fire door has to work for guests who have never seen the building before. A guest arrives late, sleeps behind a door they did not choose, and if the alarm sounds in the night they must find the corridor, the stair and the exit through doors they have never opened.

The fire strategy for the hotel and the law behind it set the rules. The Order of 2005 puts one person in charge of fire safety for the premises, and the risk assessment they own maps the escape routes and draws the compartment lines.

Everything the order must name sits inside that strategy: the periods, the hardware, the glazing and the records. An order that names them plainly is the order that gets the right doors on the right openings. Our fire door regulations for commercial buildings guide covers the same duties for offices and shops, and the same problem in wards that hold people overnight is covered in our fire door regulations for hospitals guide.

  • FD30S30 minutes with a smoke seal tested to BS EN 1634-3
  • FD30 / FD60Fire resistance periods tested to EN 1634-1
  • BS EN 1125Panic hardware for doors serving more than 60 people
  • Martyn’s LawDuties for premises that hold crowds

Bedroom corridors and stair cores: the doors that guard sleeping guests

A hotel divides into parts that hold guests in different ways, and each part puts its fire doors in a different place. The bedrooms hold guests behind closed doors, the corridors move guests between the rooms and the stairs, and the stair cores carry guests down to the exits.

Each of those parts has doors on escape routes and doors on compartment lines, and the two sets do different jobs. An escape door must open at once and let a guest through, while a compartment door must stay shut and hold fire on one side of a wall. One door can do both jobs, but only where the test evidence covers both, on the one assembly that will be fitted.

Guests do not know the building, so the doors must work without instruction. A bedroom door must shut by itself after the guest leaves, and a stair core door must stay shut against smoke while guests pass through it.

FD30S bedroom doors: the door between the room and the corridor

Each bedroom door in a hotel is a flat entrance door in all but name, and it does two jobs at once. It holds fire inside the room and keeps strangers out while the guest is away. The fire proof is a classification to EN 1634-1 and the security proof a rating to LPS 1175 or PAS 24, each proved on the same doorset. The flat entrance doors guide covers the same door in full, and the dual certification guide works through how the two proofs sit on one doorset.

Bedroom doors in hotels are most often FD30S doorsets, 30 minutes of integrity with a smoke seal proved to BS EN 1634-3, to Sa for ambient temperature smoke and S200 for smoke at 200 degrees Celsius. Smoke reaches a sleeping guest before fire does, so the seal matters as much as the period. The gap around the leaf must stay at 4 mm, because a wider gap lets smoke past the seal.

The lock must work from both sides without trapping the guest inside. A thumb turn on the inside lets the guest leave without a key, and a TS 007 cylinder, a 1-star cylinder with a 2-star handle or escutcheon giving a 3-star set, resists attack from the corridor side. Our fire door hardware guide covers the grades and the parts that make a fire door work.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

The bedroom door that holds smoke: FD30S between the room and the corridor

A bedroom door in a hotel guards a sleeping guest, so it must hold smoke as well as fire. A guest asleep behind the door cannot smell smoke in the corridor, and the door is the only thing between the room and the smoke outside it. The door takes FD30S, with the smoke seal proved to BS EN 1634-3, to Sa for smoke at room temperature and S200 for smoke at 200 degrees Celsius.

The gap round the leaf must stay at 4 mm, because a wider gap lets smoke past the leaf into the room while the guest sleeps. Intumescent seals expand at around 200 to 250 degrees, and the seal must be the one the test report names, because a seal from another doorset carries no proof on this leaf.

The closer on a bedroom door must pull the leaf shut every time, because a door left open by a guest holds nothing back. No fire door takes less than EN 3 to BS EN 1154, and the closer belongs on the order beside the leaf, with the power size chosen for the weight of the leaf it must shut.

Corridor doors and cross-corridor doors hold smoke off the escape route, so guests reach the stairs through clear air. A cross-corridor door that must stay open through the day takes a hold-open device proved to BS EN 1155, which lets the leaf shut the moment the alarm sounds, and the release belongs on the schedule beside the door.

Stair cores and the escape route: doors that keep the way out clear

Stair cores take the doors that keep the escape route clear, because every guest in the hotel must reach the stairs through doors that shut behind them. A stair door takes FD60 where the fire load behind it is heaviest, and the period follows the fire load, not the size of the hotel.

Escape routes in a hotel serve guests who do not know the building, so the doors on them must open with a light push. The force to open a door must stay below 30 N for the first 30 degrees of travel and below 22.5 N beyond, under BS 8300 and Approved Document M, so a guest carrying a child or a bag can push the door open with one hand.

Kitchens, plant rooms and back of house take the doors the public never sees, and they take the period the fire load behind them demands. A kitchen door takes FD60, because the kitchen holds the highest fire load in the hotel, while a store takes FD30, and each needs a closer that pulls the leaf shut.

The round that looks after a hotel walks every floor in turn and stops at each bedroom door, each corridor door and each stair door. The closer, the seal, the gap and the latch are checked on every door, and a fault is written against the door it belongs to on the same day, so the repair is ordered before the next guest arrives.

Position Door Period What to check
Bedroom Fire door FD30S Seal, closer, gap
Corridor Fire door FD30 Closer, seals, latch
Cross-corridor Fire door FD30S Release, seals, gap
Stair core Fire door FD60 Closer, seals, latch

Put the period, the seal and the closer on the same line as every hotel door on the order, so the leaf that arrives is the leaf that was tested. The doors that hold smoke back while people move past them are covered in our smoke control doors guide, and the sizes and the fitting of closers are set out in our fire door closers guide. What each visit should look for is set out in our fire door inspection checklist, and the periods for the shared parts of a public building are set out in our commercial buildings fire door regulations guide.

Corridor doors and cross-corridor doors: holding smoke off the escape route

Corridors are the escape routes of a hotel, and the doors on them hold fire and smoke back from those routes. A corridor door that lets smoke through fills the route out, and a cross-corridor door that fails lets smoke travel the length of the floor.

A corridor door must close on its own every time a guest passes through it. A closer too weak to pull the leaf home leaves the door ajar, and a door left ajar lets smoke reach the escape route. The closer power sizes in BS EN 1154 are covered in our fire door closers guide, and the smoke control duties of a corridor door are covered in our smoke control doors guide.

Glazing lets staff see along a corridor before they open a door, and a rated screen behind the glass holds if a room catches fire. Glass, frame, beads and fixings are tested as one assembly, so a rated pane in an untested frame is not a rated screen. Our fire rated windows guide covers how glass, frame and beads are tested together.

Stair cores and the doors that keep them clear

A stair core serves every floor, so the doors on it carry the highest duty in the building. A stair core door that lets smoke in fills the one route every guest above and below must use. The doors on a stair core usually take FD60, with a smoke seal to BS EN 1634-3.

Hold-open devices to BS EN 1155 belong on doors that must stay open during the day and shut when the alarm sounds, and a door wedged open has no release at all. A device that keeps a stair core door open for housekeeping trolleys must release on the alarm.

Read the period off the EN 1634-1 furnace test: the minutes a doorset holds in the furnace give the number after FD, 30 for FD30 and 60 for FD60. The letters say what the furnace measured, E for integrity, EW for integrity with limited radiation and EI for integrity with insulation, with periods from 30 minutes up to 120. Under EI the heat on the safe side stays below 140 degrees Celsius on average and 180 at the hottest point. Our fire ratings guide sets out each figure.

Escape routes for guests who do not know the building

A guest who does not know the building follows signs, lights and the crowd, and every door on that route must open in one action, in the direction of escape, without a key. Doors that serve more than 60 people take panic hardware to BS EN 1125, with the bar across at least 60 percent of the leaf width, working in one push.

BS 8300 and Approved Document M cap the opening force: below 30 N through the first 30 degrees and below 22.5 N beyond that. A closer set too strong for the leaf leaves the door outside those limits, and a guest with luggage, a child or a disability cannot open it. The closer power sizes come from BS EN 1154, and the minimum power size on a fire door is EN 3.

A hotel that holds crowds carries duties with it. Martyn’s Law works in tiers for premises that hold 200 or more people: the standard tier covers premises holding 200 to 799 people and the enhanced tier covers premises holding 800 or more, so a large hotel sits in the enhanced tier. Royal Assent came in April 2025, with go-live expected in spring 2027. Our Martyn’s Law guide covers the tiers and what they ask of a building, and our airports guide shows the same periods at work in a terminal.

The kitchen and the plant room: the doors the guests never see

The kitchen takes the heaviest fire load in the hotel, because the heat, the fat and the open flame sit behind its doors all day. A kitchen leaf takes FD60 where the load is heaviest, and the period follows the fire load, not the size of the hotel. The leaf must shut after every trolley that passes, because a kitchen door left open lets the fire reach the corridor while the guests sleep.

The plant room and the laundry take the same care, because the machinery and the linen stores behind them burn hotter than a bedroom. A plant room leaf takes the period the fire load demands, and the seals round it must hold as long as the leaf, because a seal that has come away lets the smoke reach the corridor first. The gap round the leaf is kept to 4 mm, and the seal is checked with the leaf shut.

The laundry and the stores take the same care, because the linen and the chemicals behind them burn fast once the fire reaches them. A store leaf takes the period the load behind it demands, and the leaf must shut after every load that passes, because a store door left open lets the fire reach the corridor while the guests sleep above it.

Back of house corridors take doors that stand open through the day, so the staff can move trolleys and linen without stopping at every leaf. A leaf that must stand open takes a hold-open device proved to BS EN 1155, so the leaf shuts on its own the moment the alarm sounds. A leaf wedged open with a bin holds nothing back when the fire comes, and the wedge belongs in the bin, not under the leaf.

The record the hotel keeps: what the file must hold after the visit

Every floor is walked in turn, from the bedrooms at the top to the kitchen at the bottom, and every leaf is tried as the visit reaches it. A closer that has lost its pull, a seal that has come away from its groove, or a gap that has opened since the last visit is written against the door, with the floor and the day beside it, so the repair is ordered while the fault is still small.

The record stays with the building file, naming the floor, the door, the fault and the day, so the next person who reads it can see which doors have been repaired and which still wait. A door that has been repaired without a note in the record is a door whose proof no one can show, and the file that holds the visits is the file the hotel shows when the doors are asked about.

Position Door Period What to check
Bedroom FD30S leaf FD30S Leaf, closer, smoke seal
Kitchen Steel leaf FD60 Leaf, closer, seals
Plant room Steel leaf FD60 Leaf, seals, gap
Corridor Fire leaf FD30 Leaf, hold-open, seals
Stair core Fire leaf FD60 Leaf, bar, closer

What each visit should cover is set out in the fire door inspection checklist, and the rules for the shared parts of a public building are set out in the fire door regulations commercial buildings guide. The doors that guard the hotel are covered in the hotel security doors guide, and the bars and pads that throw the latch are set out in the panic hardware guide.

Kitchens, plant rooms and back of house: the doors behind the public face

The kitchen behind the dining room carries the highest fire load in the building, so the doors between the kitchen and the dining room take FD60. A kitchen door opens and closes through the day and must still shut by itself after every use.

Behind the public rooms sit the plant rooms, the stores and the laundry, and their doors answer to different risks. A plant room door needs FD60 with a closer strong enough to pull a heavy leaf shut against the draught from the plant, and a door to a cash handling area needs a security rating next to the fire rating. Where a wide opening crosses a compartment wall, a sliding fire door on a track closes when the alarm sounds.

Trolleys, luggage and a thousand openings a week wear the small parts first, and the hinge grade decides how long a hotel door keeps working. BS EN 1935 grades a hinge by the cycles and the load it can carry: grade 13 is proved for 200,000 cycles at 120 kg, and grade 14 for 200,000 cycles at 160 kg. A heavy leaf hung on a hinge that cannot carry it sinks on its hinges, and a leaf that sinks drags on the floor and stops latching.

The inspection round: what the hotel checks and records

A hotel fire door is only as good as its last check. The responsible person sets the round, and the round covers every door on the escape routes and the compartment lines. The check takes in the leaf, the gaps, the seals, the closer and the latch, the hinges and the fixings, and the signs on the door. A door wedged open, a leaf that drags, a seal that has come away, each one is written on the record. The fire door inspection checklist covers what each check looks for.

Hotels change hands often, and a new operator inherits the doors left behind. Keep the fire strategy, the door schedule, the test reports and the inspection records together in one file, so the next operator can see which door carries which period and which check each door has passed.

The hotel order: one schedule for every floor

Put the enquiry together as a specification. It should name the building and the position, the fire period, the smoke seal and the security rating where one is needed, and the leaf, frame, glass, beads, seals and hardware as one doorset. Where a bedroom door must also resist attack, ask for the rating on the whole doorset, a rating to LPS 1175 or PAS 24, and not on the leaf alone. The how to specify security doors guide sets the columns for the same discipline.

File the evidence with the doors on the day they arrive. The test report, the classification and the hardware schedule should travel with each doorset, and the handover pack should name the inspection routine the hotel will follow.

Door position Period Hardware What to check
Bedroom door FD30S Thumb turn, TS 007 cylinder Seals, gaps, latch, self-closing
Corridor door FD30 or FD60 Closer, panic hardware Closer, seals, opening force
Stair core door FD60 Closer, hold-open to BS EN 1155 Closer, seals, smoke control
Kitchen to dining room FD60 Closer, hinges grade 13 or 14 Seals, gaps, self-closing
Plant room door FD60 Closer, latch, seals Seals, gaps, self-closing

A hotel bedroom door guards a sleeping guest, so the seal and the closer matter as much as the fire period on the schedule.

What fire rating should a hotel bedroom door carry?

Most often an FD30S doorset, 30 minutes of integrity with a smoke seal proved to BS EN 1634-3. The fire strategy for the hotel names the period for each door.

Can one hotel door hold a fire rating and a security rating?

Yes, where the same doorset has been tested for both. The fire proof is a classification to EN 1634-1 and the security proof a rating to LPS 1175 or PAS 24, and each proof must name the doorset that will be fitted.

Do hotel escape doors need panic hardware?

Yes, once more than 60 people use the door. Fit panic hardware to BS EN 1125, with the bar spanning at least 60 percent of the leaf.

How often should hotel fire doors be checked?

The responsible person sets the routine, and each check is written on the record with the door, the fault and the fix. The inspection checklist guide covers what each check looks for.

How do I order doors for a whole hotel?

Put one schedule together with one line for every opening, naming the position, the fire period, the smoke seal, the security rating and the whole doorset.

Specifying fire doors for a hotel?Send the door schedule and the fire strategy for a tested doorset quotation.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →