Fire Door Rules for Squash Clubs
Squash clubs run enclosed indoor courts, changing rooms and a bar from morning into the evening, so each door takes the period its room asks for.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
A squash club entrance leaf takes FD30 to EN 1634-1, and the courts, the changing rooms and the bar take the same period, while the kitchen, the back office and the plant room take FD60.
EN 1634-1 tests a leaf against fire and gives it minutes, from FD30 up to FD120, and the letters beside the minutes name what the leaf stops: E for flame, EW for flame and part of the heat, and EI for flame and heat together.
A squash club plays inside four walls, where players book a court for an hour, change beside the courts and sit in the bar after the match, so each leaf round the courts takes the period that fits the room behind it.
The courts in a squash club are shut rooms with four walls and a glass back, which sets them apart from the open hall of a badminton club and from the outdoor courts of a tennis club, and the leaf on each court sits on the route that players use to leave.
- FD30 / FD60Periods to EN 1634-1
- Enclosed courtsFour walls and a glass back
- Back officeWhere FD60 holds the heat
- One routeFrom the courts to the car park
The squash club fire order: a period beside each of the seven leaves
The fire order names seven leaves, and the period beside each one follows the room that sits behind it, so the entrance, the courts, the changing rooms and the bar sit at FD30, and the kitchen, the back office and the plant room sit at FD60.
Four of the seven leaves sit at FD30, a thirty minute hold, because the rooms behind them stay full of players from the first booking to the last, and the other three sit at FD60, a sixty minute hold, because the rooms behind them hold food, takings, records or plant.
Every leaf on the order gets a line of its own that names the room, the period, the grade and the closer, so the fitter, the club secretary and the person who signs all work from the same list.
| Room | Period | Grade | What to check |
|---|---|---|---|
| Entrance | FD30 | B3 | Leaf, closer, seals |
| Courts | FD30 | B3 | Leaf, closer, seals |
| Changing rooms | FD30 | B3 | Leaf, closer, seals |
| Bar | FD30 | B3 | Leaf, closer, seals |
| Kitchen | FD60 | C5 | Leaf, closer, seals |
| Back office | FD60 | C5 | Leaf, closer, seals |
| Plant room | FD60 | C5 | Leaf, closer, seals |
A single leaf can hold fire minutes from EN 1634-1 next to a forced entry grade from LPS 1175 Issue 8.2, so FD30 or FD60 can sit beside B3 or C5 on the same leaf, and the dual doorset guide covers the fire test and the forced entry test on one leaf.
An hour behind the kitchen, office and plant room leaves
The hour belongs to the doorset as a whole, not to the leaf by itself, so the frame, the seals and the closer all carry their share of it, and a leaf hung in a different frame keeps none of the minutes the report names.
FD60 sits on the kitchen leaf, which stays shut between services, because the cookers behind it run through the evening and the leaf has to hold the heat back while the kitchen is empty.
FD60 sits on the back office leaf too, because the till, the membership records and the keys to every other room sit behind it, and the plant room leaf takes FD60 because the pumps and boards that keep the courts lit and warm sit behind that one. The plant room fire door guide covers the leaf that guards the plant.
The pumps and boards behind the plant room leaf run unwatched between visits, so the leaf stays shut, and a leaf left open lets heat and smoke reach the plant before anyone knows a fire has started. Only the holder of the plant room key opens that leaf, and it is shut again before the key goes back.
Entrance and enclosed courts: FD30 on the way in and the way out
FD30 sits on the entrance leaf, the court leaves, the changing room leaves and the bar leaf, because those four leaves sit on the way out, and thirty minutes is the time the route needs while players leave the courts together.
Players leave together once the last match ends, so the leaf on the way out has to open under a crowd without a key or a code, and a push bar proved to BS EN 1125 runs across no less than 60 percent of the leaf width on any leaf that serves more than 60 people. The panic hardware guide covers the bars, and the emergency exit guide covers the leaves that carry them.
A glazed panel in the court leaf lets staff watch the match without opening the leaf, so the court keeps its view of the play while the leaf stays shut on the route out. The vision panel guide covers the glass in a fire leaf and the beads that hold it.
Smoke inside an enclosed court: Sa and S200 beside the period
Smoke reaches the courts before flame does, so the leaves along the route from the courts past the changing rooms hold a smoke rating to BS EN 1634-3, Sa where the smoke is at room temperature and S200 where it is at 200 degrees.
Leaves that stand open through the evening hang on hold-open devices that let go when the alarm sounds, so each leaf shuts on its own and the smoke stays on one side of it. The closer guide covers the closers that shut the leaf, while the smoke control guide covers the leaves that hold smoke back.
Smoke moves down a corridor while players are still gathering rackets and kit bags, so the leaves on the route shut before the smoke reaches the courts, and the rooms on either side of the route stay apart. The compartmentation guide shows how those leaves split the building into parts that hold fire and smoke apart.
Closers, seals and gaps: what the squash club periods rest on
An FD60 leaf keeps its hour only when the closer shuts it, the seals meet the frame and the gaps round the leaf stay at 4 mm, because a leaf left ajar hands its minutes away before the fire reaches it. The gap guide shows how the 4 mm gap is measured.
Once the heat passes 200 degrees the seal in the groove swells shut, and it keeps swelling up to 250 degrees, so the gap round the leaf closes as the fire grows. The seal guide covers the seals that swell in the heat and the smoke seals beside them.
BS EN 1935 tests hinges through 200,000 cycles, with grade 13 rated for 120 kg and grade 14 rated for 160 kg, and a closer proved to BS EN 1154 runs from EN 1, the smallest power size, up to EN 3, the smallest size that may sit on a fire door. The hardware guide covers the hinges, the closers and the locks that hold a fire leaf together.
A fire leaf must open under a light hand as well as shut on its own, because a player with a racket in one hand and a kit bag in the other still has to get through it. BS 8300 and Approved Document M set the opening force below 30 N through the first 30 degrees and below 22.5 N past that point, so the closer that shuts the leaf must not make the leaf too heavy to push.
Night matches and the way to the car park: getting players out after dark
The route to the car park is signed at every turn, because the alarm may sound while the courts are full and players have to find the way out without asking. The signage guide covers the signs that sit on the leaf and along the route.
Martyn’s Law received Royal Assent in April 2025 and is expected to go live in spring 2027, with tiers for premises that hold 200 to 799 people and for premises that hold 800 or more, so a club that fills its courts through the evening needs to know which tier it sits in. The Martyn’s Law guide covers the tiers and what each one asks of a venue.
The car park outside needs the same thought as the route, because players gather there once the alarm sounds. ProtectUK puts the clear gap between bollards at no more than 1,200 mm and their height at no less than 500 mm, and the bollard guide covers the posts that guard the front of the building.
When the alarm sounds in a night match, the duty steward walks the courts and the changing rooms to check no one is left behind, while the bar staff clear the bar and the tables. That walk works only when the leaves on the route shut behind the steward, so the route stays clear and the smoke stays on one side of each leaf while the club empties.
Bar and changing rooms: FD30 beside the courts while players rest
The bar leaf takes FD30, because players eat and drink in the bar after a match and the leaf has to hold the heat back while they leave through the courts corridor and out to the car park.
The changing room leaves take FD30 as well, because players change there through the evening and the rooms hold rackets, kit bags and phones, so the leaves round those rooms hold for thirty minutes while the rooms empty.
A restaurant bar asks for the same period on its leaves, and a bowling alley keeps the same hours as a squash club, with play and drink running side by side into the evening. The restaurant fire door guide and the bowling alley fire door guide show how those rooms take FD30, while the leisure centre guide and the gym fire door guide cover buildings where the courts are only one part of the play.
The squash club fire order on one list: period, grade and proof
Each leaf on the order has its own line naming the room, the period, the grade and the closer, and that line is checked against the room before anyone signs, so no leaf is ordered with minutes that belong to another room.
Each leaf on the order is tried before the order is signed, because a closer that will not shut the leaf and a seal that will not meet the frame both take the minutes off the leaf. The certification guide covers the proof behind each leaf, and the specifying guide covers the leaf, the frame and the hardware as one doorset.
Once the club opens, the secretary walks round with the door list and tries each leaf in turn, and a leaf that will not shut goes on the list the same day. The inspection checklist covers what to try on each leaf, and the maintenance guide covers the work that keeps the leaves shutting as they should.
Put the period, the grade and the closer on one line for each leaf, then check that line against the room itself before the order goes in.
What period should a squash club plant room door carry?
FD60 to EN 1634-1, because the pumps and boards in the plant room keep the courts lit and warm.
What period should a squash club entrance door carry?
FD30 to EN 1634-1, because the entrance leaf stands on the way out to the car park.
Can a squash club leaf hold a fire period and a security grade?
Yes, one leaf can carry its fire minutes beside its forced entry grade, with both proofs written into the same report.
Do squash club fire doors need a smoke rating?
Yes, the leaves along the route from the courts to the car park carry Sa or S200 to BS EN 1634-3, so the smoke stays on one side of the leaf while players leave.
What happens when a fire door will not shut?
A leaf that will not shut is written on the door list the same day, and it stays on the list until the closer or the seals let it shut again.