A GP surgery fills with patients who do not know the building, so each fire door takes its period from the room behind the leaf, consulting room to drugs store.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
A GP surgery is a waiting room, a row of consulting rooms and the small rooms behind them where the records and the drugs sit, and the fire doors between those parts decide how long a fire stays where it started while the patients find the way out. Each leaf takes its period from the room behind it.
Surgeries share their fire rules with other commercial buildings, and those shared rules are set out in the fire door regulations commercial buildings guide. The care with patients who move slowly is taken in the fire door regulations care homes guide, and the hospital pattern of moving patients sideways is covered in the fire door regulations hospitals guide, which a surgery does not follow because its patients leave by the front door. The surgery order names every opening with its period and its hardware beside it.
The fire plan comes first, before any leaf is ordered, and it gives every opening its period and every patient the route they must follow, so the order follows the plan leaf by leaf.
- FD30 / FD60Fire periods to EN 1634-1
- E / EW / EI 30-120What the letters beside the period mean
- Sa / S200Smoke proof to BS EN 1634-3
- One listEvery surgery door named
Consulting rooms, records and the drugs store: one surgery, two periods
A surgery works as three parts: the waiting room where the patients sit, the consulting rooms where they are seen, and the small rooms behind them where the records and the drugs are kept. The rules follow those parts, because a leaf between a consulting room and the corridor must hold the fire where it started.
The consulting rooms take the doors that let patients pass in and out through the day, and each leaf must open for a patient who has never seen the building before. The records room guards the notes, and its leaf must hold the fire back where the paper sits in rows.
The plan gives every opening a door of its own, so a leaf ordered for the drugs store never ends up guarding the waiting room, and a leaf ordered for the records room never ends up on the route.
FD30 and FD60 in a GP surgery: which room takes which period
Each part of a surgery asks a different period of its doors, because the load behind each leaf differs. The consulting rooms hold patients and notes, the records room holds paper in rows, and the drugs store holds the controlled drugs, so the period follows the room and never the leaf alone.
The period on a surgery leaf is proved to EN 1634-1, which tests the leaf, the frame and the seals together against flame and heat and counts the minutes they hold. The letters name what it held back: E for flames alone, EW where some heat was held back as well, and EI where the heat was held back too, from 30 minutes to 120.
A leaf that must hold for sixty minutes is built heavier than one that must hold for thirty, with a deeper frame and hinges that carry the weight. The order never puts a thirty-minute leaf where the plan asks for sixty.
The consulting room: the leaf that shuts on a patient mid-consultation
A consulting room is a small room where one patient sits with one clinician, and the leaf on it must shut on its own after every patient who passes through. A glazed panel in the leaf lets the reception team see whether the room is in use without opening it, and the pane takes the same proof as the leaf.
The notes in the consulting room and the drugs in the cabinet beside it carry a fire load of their own, and the doors between the consulting room and the corridor must hold the fire where it starts. A leaf between the two takes the period the consulting room demands, because a fire that starts among the notes must stay there while the patient moves out.
The glass in a consulting room leaf is covered in the fire rated windows guide, and the figure the pane adds to the order is worked through in the fire rated glass cost guide.
Reception and the waiting room: the doors every patient passes
The waiting room is the one room every patient passes, and the leaves on it must open for patients who arrive with prams, sticks and wheelchairs. A leaf that needs a hard pull fails the patient who reaches it with both hands full, so the opening force is checked against BS 8300 and Approved Document M: below 30 N through the first 30 degrees, and below 22.5 N beyond them.
Reception sits beside the waiting room, and the counter leaf behind it takes the period the records beside it take. The leaf between reception and the records room takes FD60, because the fire that starts among the notes must not reach the front desk.
The back office and the plant room sit at the back of the surgery, and their leaves take FD60, because the bookings and the machinery behind them serve the whole building. What the plant room leaf must do is set out in the plant room door requirements guide.
The drugs store and the records room: the rooms that take FD60
The drugs store holds the controlled drugs, and its leaf takes FD60, because the period follows the value in the room, not the size of the building. The records room holds the paper notes in rows, and its leaf takes FD60.
A leaf that must hold fire and keep an intruder out takes both proofs on the one doorset: EN 1634-1 gives the fire minutes and letters, E, EW and EI from 30 to 120, while LPS 1175 Issue 8.2 gives the forced entry grade, B3 at three minutes, C5 at five and D10 at ten. How one doorset carries both proofs is shown in the fire and security doors dual certification guide.
The drugs store takes D10, the highest grade on the surgery, because the controlled drugs behind its leaf justify the ten minutes it takes to break through. LPS 1175 Issue 8.2 of September 2024 names B3, C5 and D10 at three, five and ten minutes, and the leaf, the frame and the lock are proved together as one doorset. What can break a rating after fitting is set out in the keeping an LPS 1175 rating valid guide.
Getting slow-moving patients out: the route from the consulting room
When the alarm sounds in a surgery, the patients in the consulting rooms take the route the signs point to, and the way must be kept free of chairs, prams and anything stored against the doors. Every leaf on that route opens under one push, whether the power is on or off.
Smoke must be held back as well as flame, so every door on the route carries a smoke rating beside its fire period. BS EN 1634-3 gives the marks: Sa where the smoke is at room temperature, and S200 where it is at 200 degrees. A seal stops smoke only where it meets the frame all the way round, and smoke reaches the route ahead of the flames. The smoke control doors guide sets out how the doors hold smoke back while patients move past them.
A surgery is a small building, so the patients on the route are few and the staff know them by name. The fire door regulations dental practices guide takes the same care with the patients in a dental practice.
| Position | Door | Period | What to check |
|---|---|---|---|
| Consulting room | Steel leaf | FD60 | Leaf, lock, seals |
| Records room | Steel leaf | FD60 | Leaf, lock, seals |
| Drugs store | Steel leaf | FD60 | Leaf, lock, reader |
| Back office | Steel leaf | FD60 | Leaf, lock, seals |
| Plant room | Fire leaf | FD60 | Leaf, seals, gap |
| Waiting room | Fire leaf | FD30 | Leaf, bar, closer |
What keeps the period: closers, seals and gaps on surgery doors
A surgery leaf opens and shuts between every appointment, so its closer works from morning to evening without rest. The smallest closer power on a fire door is EN 3 to BS EN 1154.
The gap between the leaf and the frame is 4 mm, measured with a gauge, not judged by eye. When the heat nears 200 to 250 degrees the intumescent seal in the groove swells and closes that gap, but paint over the seal stops it swelling. The gap and the seal are tried on the round, and any fault is written against its door on the day it is found.
The hinges carry the leaf through every swing, and a loose one lets the leaf drop until it catches on the floor. The fire door hardware guide sets out what the lock the key turns must do, and the fire door closers guide covers closer sizes and fitting.
Ordering for a GP surgery: one list for every door
The whole surgery order sits on one list, a line for every door with the leaf, the period, the lock and the closer beside it, so the door that arrives is the door its room asked for. A list that names a single leaf for the whole surgery leaves the fitter to guess which room takes which period.
Before anything is signed the surgery reads the quotation against the schedule, door by door. What the schedule must hold is named in the how to specify security doors guide, and what each step up the grade adds to the figure is worked through in the security door cost factors guide.
The doors are tried through the week, a few leaves each day, so none goes untried for long: the waiting room at opening, the consulting rooms before the first patient, and the drugs store at closing. Any fault found is written against its own door on the day it is found. The record stays with the surgery file, and what the visit should cover is set out in the fire door inspection checklist.
A surgery door holds only as long as the consulting rooms behind it and the waiting room beside it, so the period, the release and the closer must all sit on the same list.
What period should a GP surgery door carry?
The minutes on a surgery leaf come from EN 1634-1, and they change with the room. A consulting room leaf holds fire for sixty minutes while the waiting room leaf holds it for thirty, so the order names the period room by room.
Can one leaf hold fire and forced entry?
Yes. A single doorset can carry both proofs where it faced the fire test and the forced entry test together, on the same leaf, frame and seals.
Do GP surgery doors need panic hardware?
Where the route serves a crowd, the leaves on the way out take a bar proved to BS EN 1125, across at least 60 percent of the leaf, so the latch throws under one push from a patient who has never used the door before.
What period should a consulting room door carry?
A consulting room leaf takes FD60, because the patient inside it and the notes beside it need the fire held back while the room empties. The waiting room leaf takes FD30, because the patients there are already on the way out.
Who checks the GP surgery doors?
The practice manager tries the doors a few at a time through the week, and each fault is written against its own door on the day it is found. The record of each visit stays with the surgery file.