Fire Door Rules for GP Surgeries

A GP surgery fills with patients who do not know the building, so each fire door takes its period from the room behind the leaf, consulting room to drugs store.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

A GP surgery is a waiting room, a row of consulting rooms and the small rooms behind them where the records and the drugs sit, and the fire doors between those parts decide how long a fire stays where it started while the patients find the way out. Each leaf takes its period from the room behind it.

Surgeries share their fire rules with other commercial buildings, and those shared rules are set out in the fire door regulations commercial buildings guide. The care with patients who move slowly is taken in the fire door regulations care homes guide, and the hospital pattern of moving patients sideways is covered in the fire door regulations hospitals guide, which a surgery does not follow because its patients leave by the front door. The surgery order names every opening with its period and its hardware beside it.

The fire plan comes first, before any leaf is ordered, and it gives every opening its period and every patient the route they must follow, so the order follows the plan leaf by leaf.

  • FD30 / FD60Fire periods to EN 1634-1
  • E / EW / EI 30-120What the letters beside the period mean
  • Sa / S200Smoke proof to BS EN 1634-3
  • One listEvery surgery door named

Consulting rooms, records and the drugs store: one surgery, two periods

A surgery works as three parts: the waiting room where the patients sit, the consulting rooms where they are seen, and the small rooms behind them where the records and the drugs are kept. The rules follow those parts, because a leaf between a consulting room and the corridor must hold the fire where it started.

The consulting rooms take the doors that let patients pass in and out through the day, and each leaf must open for a patient who has never seen the building before. The records room guards the notes, and its leaf must hold the fire back where the paper sits in rows.

The plan gives every opening a door of its own, so a leaf ordered for the drugs store never ends up guarding the waiting room, and a leaf ordered for the records room never ends up on the route.

FD30 and FD60 in a GP surgery: which room takes which period

Each part of a surgery asks a different period of its doors, because the load behind each leaf differs. The consulting rooms hold patients and notes, the records room holds paper in rows, and the drugs store holds the controlled drugs, so the period follows the room and never the leaf alone.

The period on a surgery leaf is proved to EN 1634-1, which tests the leaf, the frame and the seals together against flame and heat and counts the minutes they hold. The letters name what it held back: E for flames alone, EW where some heat was held back as well, and EI where the heat was held back too, from 30 minutes to 120.

A leaf that must hold for sixty minutes is built heavier than one that must hold for thirty, with a deeper frame and hinges that carry the weight. The order never puts a thirty-minute leaf where the plan asks for sixty.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

The consulting room: the leaf that shuts on a patient mid-consultation

A consulting room is a small room where one patient sits with one clinician, and the leaf on it must shut on its own after every patient who passes through. A glazed panel in the leaf lets the reception team see whether the room is in use without opening it, and the pane takes the same proof as the leaf.

The notes in the consulting room and the drugs in the cabinet beside it carry a fire load of their own, and the doors between the consulting room and the corridor must hold the fire where it starts. A leaf between the two takes the period the consulting room demands, because a fire that starts among the notes must stay there while the patient moves out.

The glass in a consulting room leaf is covered in the fire rated windows guide, and the figure the pane adds to the order is worked through in the fire rated glass cost guide.

Reception and the waiting room: the doors every patient passes

The waiting room is the one room every patient passes, and the leaves on it must open for patients who arrive with prams, sticks and wheelchairs. A leaf that needs a hard pull fails the patient who reaches it with both hands full, so the opening force is checked against BS 8300 and Approved Document M: below 30 N through the first 30 degrees, and below 22.5 N beyond them.

Reception sits beside the waiting room, and the counter leaf behind it takes the period the records beside it take. The leaf between reception and the records room takes FD60, because the fire that starts among the notes must not reach the front desk.

The back office and the plant room sit at the back of the surgery, and their leaves take FD60, because the bookings and the machinery behind them serve the whole building. What the plant room leaf must do is set out in the plant room door requirements guide.

The drugs store and the records room: the rooms that take FD60

The drugs store holds the controlled drugs, and its leaf takes FD60, because the period follows the value in the room, not the size of the building. The records room holds the paper notes in rows, and its leaf takes FD60.

A leaf that must hold fire and keep an intruder out takes both proofs on the one doorset: EN 1634-1 gives the fire minutes and letters, E, EW and EI from 30 to 120, while LPS 1175 Issue 8.2 gives the forced entry grade, B3 at three minutes, C5 at five and D10 at ten. How one doorset carries both proofs is shown in the fire and security doors dual certification guide.

The drugs store takes D10, the highest grade on the surgery, because the controlled drugs behind its leaf justify the ten minutes it takes to break through. LPS 1175 Issue 8.2 of September 2024 names B3, C5 and D10 at three, five and ten minutes, and the leaf, the frame and the lock are proved together as one doorset. What can break a rating after fitting is set out in the keeping an LPS 1175 rating valid guide.

Getting slow-moving patients out: the route from the consulting room

When the alarm sounds in a surgery, the patients in the consulting rooms take the route the signs point to, and the way must be kept free of chairs, prams and anything stored against the doors. Every leaf on that route opens under one push, whether the power is on or off.

Smoke must be held back as well as flame, so every door on the route carries a smoke rating beside its fire period. BS EN 1634-3 gives the marks: Sa where the smoke is at room temperature, and S200 where it is at 200 degrees. A seal stops smoke only where it meets the frame all the way round, and smoke reaches the route ahead of the flames. The smoke control doors guide sets out how the doors hold smoke back while patients move past them.

A surgery is a small building, so the patients on the route are few and the staff know them by name. The fire door regulations dental practices guide takes the same care with the patients in a dental practice.

Position Door Period What to check
Consulting room Steel leaf FD60 Leaf, lock, seals
Records room Steel leaf FD60 Leaf, lock, seals
Drugs store Steel leaf FD60 Leaf, lock, reader
Back office Steel leaf FD60 Leaf, lock, seals
Plant room Fire leaf FD60 Leaf, seals, gap
Waiting room Fire leaf FD30 Leaf, bar, closer

What keeps the period: closers, seals and gaps on surgery doors

A surgery leaf opens and shuts between every appointment, so its closer works from morning to evening without rest. The smallest closer power on a fire door is EN 3 to BS EN 1154.

The gap between the leaf and the frame is 4 mm, measured with a gauge, not judged by eye. When the heat nears 200 to 250 degrees the intumescent seal in the groove swells and closes that gap, but paint over the seal stops it swelling. The gap and the seal are tried on the round, and any fault is written against its door on the day it is found.

The hinges carry the leaf through every swing, and a loose one lets the leaf drop until it catches on the floor. The fire door hardware guide sets out what the lock the key turns must do, and the fire door closers guide covers closer sizes and fitting.

Ordering for a GP surgery: one list for every door

The whole surgery order sits on one list, a line for every door with the leaf, the period, the lock and the closer beside it, so the door that arrives is the door its room asked for. A list that names a single leaf for the whole surgery leaves the fitter to guess which room takes which period.

Before anything is signed the surgery reads the quotation against the schedule, door by door. What the schedule must hold is named in the how to specify security doors guide, and what each step up the grade adds to the figure is worked through in the security door cost factors guide.

The doors are tried through the week, a few leaves each day, so none goes untried for long: the waiting room at opening, the consulting rooms before the first patient, and the drugs store at closing. Any fault found is written against its own door on the day it is found. The record stays with the surgery file, and what the visit should cover is set out in the fire door inspection checklist.

A surgery door holds only as long as the consulting rooms behind it and the waiting room beside it, so the period, the release and the closer must all sit on the same list.

What period should a GP surgery door carry?

The minutes on a surgery leaf come from EN 1634-1, and they change with the room. A consulting room leaf holds fire for sixty minutes while the waiting room leaf holds it for thirty, so the order names the period room by room.

Can one leaf hold fire and forced entry?

Yes. A single doorset can carry both proofs where it faced the fire test and the forced entry test together, on the same leaf, frame and seals.

Do GP surgery doors need panic hardware?

Where the route serves a crowd, the leaves on the way out take a bar proved to BS EN 1125, across at least 60 percent of the leaf, so the latch throws under one push from a patient who has never used the door before.

What period should a consulting room door carry?

A consulting room leaf takes FD60, because the patient inside it and the notes beside it need the fire held back while the room empties. The waiting room leaf takes FD30, because the patients there are already on the way out.

Who checks the GP surgery doors?

The practice manager tries the doors a few at a time through the week, and each fault is written against its own door on the day it is found. The record of each visit stays with the surgery file.

Specifying doors for a GP surgery?Send the door list and the period each door must hold for a tested door quotation.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →

Products

One supplier for the whole building envelope

Ready to specify your project?

Free assessment, written specification and test evidence. Reply within one working day.