Fire Door Rules for Maternity Units

A maternity unit holds mothers and newborns overnight, so each door takes the fire period its room demands, FD30 on the way out, FD60 behind shut leaves.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

A maternity unit holds mothers and newborn babies through the night, and the fire rules for the building follow the rooms behind each leaf. Delivery rooms hold births, the postnatal ward holds mothers resting with their babies, and the drugs store, staff office and plant room sit behind leaves the mothers never pass. Mothers who have just given birth move slowly and some need help to leave, so the leaves on the way out matter as much as the leaves that hold flame back.

EN 1634-1 gives the minutes on a unit leaf, testing the leaf against fire and counting how long it holds. FD30 stands for thirty minutes and FD60 for sixty, and the letter beside the minutes says what stayed out: E for flames alone, EW for flames and part of the heat, and EI for flames and heat together.

A maternity unit is not a hospice, because babies are born here rather than people receiving end-of-life care, and it is not a care home, because mothers stay for days after a birth rather than living in the building for years. The ward is not a locked ward either, so mothers move freely and the fire rules follow the rooms. The fire door rules for care homes name the fire rules for a home where residents live for years, and the fire door rules for hospitals name the rooms a hospital keeps behind its public floor.

  • FD30 / FD60Fire periods to EN 1634-1
  • Postnatal wardWhere mothers leave from
  • Sa / S200Smoke ratings to BS EN 1634-3
  • One listEvery unit door named

Seven openings on a maternity unit: a period beside each room

Seven openings make up the unit order, and the period follows what each room holds. Mothers come in through the entrance, reception watches the ward entrance, and the delivery rooms hold births while the postnatal ward holds mothers resting with their babies. The drugs store keeps the drugs, the staff office keeps the keys and the records, and the plant room keeps the building running.

The drugs store, the delivery rooms, the staff office and the plant room take FD60, because the drugs, the births, the records and the boards behind those leaves ask for sixty minutes. The entrance, reception and the postnatal ward route take FD30, because the mothers on that route can reach the street in less than thirty minutes.

Every opening gets a line of its own, leaf and period written beside the room, and the table below sets the seven rooms beside their periods and grades.

Room Period Grade What to check
Entrance FD30 B3 Leaf, glass, closer
Reception FD30 B3 Leaf, glass, closer
Delivery rooms FD60 C5 Leaf, lock, seals
Postnatal ward FD30 B3 Leaf, glass, closer
Drugs store FD60 D10 Leaf, lock, seals
Staff office FD60 C5 Leaf, lock, seals
Plant room FD60 C5 Leaf, lock, seals

Sixty minutes where birth happens: FD60 in the delivery rooms

Minutes belong to the whole doorset, not to the leaf alone, so leaf, frame, fixings and lock are proved together and the report states the period they hold. That period is written beside the leaf on the order, so the leaf that arrives is the one the room asked for. What the report behind a period must hold is named in the fire door certification guide.

Fire minutes from EN 1634-1 and a forced entry grade from LPS 1175 Issue 8.2 of September 2024 can sit on the same doorset, so one report names both proofs for one leaf. How the pair is proved on a single leaf is shown in the dual certification guide for fire and security doors.

Minutes alone do not tell the whole story, because the letter beside them says what the leaf stopped. E stopped flame, EW stopped flame and part of the heat, and EI stopped flame and heat together, so the letter is written on the order with the minutes.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

FD60 on the drugs store, delivery rooms, staff office and plant room

The drugs store leaf takes FD60 and stays shut whenever no one is working behind it, because the drugs behind it are what the mothers are given through the day and the night. Sixty minutes is the hold that room asks for, because flame reaching it takes drugs mothers cannot do without.

Delivery room leaves take FD60 as well, because the equipment and notes behind them are what a birth depends on. A leaf left standing open through the day holds nothing back, so the last person out of the room shuts it behind them.

Keys, records and paperwork sit in the staff office, and boards and equipment that keep the lights and heating running sit in the plant room, so both leaves take FD60 because what sits behind them feeds the whole unit. The plant room leaves are covered in full by the plant room fire doors guide, and the doors that guard the plant are named in the plant room door requirements guide.

Thirty minutes on the way out: FD30 from ward to street

FD30 sits on the postnatal ward leaf and on the entrance leaf, because the mothers rest on the ward and reach the street through the entrance. Thirty minutes is more than the mothers need, and the route to the street is short.

Where the route serves mothers who move slowly, a push bar proved to BS EN 1125 sits on each leaf on the way out, and the bar runs across no less than 60 percent of the width of the leaf, so a mother who reaches it in a crowd opens it with one push. The panic hardware guide sets out what the bar must do when mothers push against the leaf, and the emergency exit doors guide covers the leaves on the way out.

A glazed panel in the reception leaf lets staff watch the mothers without opening the leaf, and the pane is proved with the leaf round it, glass, bead and fixings named together in the report. Which panels a fire leaf may carry is named in the fire door vision panels guide, and the two leaf materials are set beside each other in the steel vs timber fire doors guide.

Smoke before flame: Sa and S200 along the postnatal corridor

Mothers leaving the postnatal ward meet smoke before they meet flame, so the leaves on the way out carry a smoke rating beside their fire period. BS EN 1634-3 gives the two ratings, Sa for smoke at room temperature and S200 for smoke at 200 degrees, and the smoke control doors guide works through how the route leaves keep smoke back while mothers move past them.

Through the day a leaf that must stay open is held by a hold-open device proved to BS EN 1155, which lets the leaf go on its own the moment the alarm sounds. The fire compartmentation guide names how the leaves hold the line between one part of the unit and the next, and a chair wedged under a leaf gives it no period while it stands open.

Smoke spreads along a corridor faster than mothers walk, so the leaves between the ward and the entrance matter most. After each person through, a leaf that shuts on its own keeps the smoke on one side of it.

Closers, seals and gaps: the small parts that carry the period

An FD60 leaf holds its hour only when the closer shuts it, the seals meet the frame and the gaps stay narrow, because flame passes through a leaf left ajar in seconds and a wide gap soon after. From EN 1, for a leaf 750 mm wide and 20 kg, to EN 7, for a leaf 1,600 mm wide and 160 kg, BS EN 1154 sizes closer power, and a closer on a fire door takes at least EN 3.

Heat of 200 to 250 degrees at the frame makes the seal swell in its groove until the gap closes, so flame and hot gas cannot pass, while paint over the seal stops it swelling. A gauge checks the 4 mm gap round a hung leaf, and the monthly round shows whether any gap has grown past that figure. Fitting the seal is covered in the intumescent seals guide, what the closer must do in the fire door closers guide, and measuring the gaps in the fire door gaps guide.

Hinges proved to BS EN 1935 carry the leaf through 200,000 cycles, grade 13 at 120 kg and grade 14 at 160 kg, so the heavier leaf takes the heavier hinge. A mother must be able to push the leaf open without help, and BS 8300 with Approved Document M sets the push below 30 N through the first 30 degrees and below 22.5 N after them. What each sign must say is named in the fire door signage guide.

Moving mothers and newborns out: the route staff rehearse

The route to the street is signed at every turn, because the alarm may sound while a mother who has never used the building sits in a delivery room. Day and night the route stays clear, and the entrance leaf opens to one push from whoever reaches it first, supply on or off.

By how many people it holds, Martyns Law puts a venue in a tier, one tier for 200 to 799 people and a higher tier at 800 and above, after Royal Assent in April 2025 and with the go-live expected in spring 2027. What each tier asks for is set out in the Martyns Law guide for premises, and a unit holding 200 or more people falls in a tier it covers.

Staff walk the route with new mothers on arrival, so the way out is known before the alarm ever sounds. A mother who knows the route leaves faster, and one who has walked it once does not stop to look for the way.

Placing the maternity unit fire door order: period, grade and proof on one line

The order gives every opening in the unit a line of its own, with leaf, period, lock and closer written beside it. A leaf named once for the whole unit leaves the fitter to guess, and a leaf in the wrong room holds flame for the wrong time.

Before the order is signed it is checked leaf by leaf, because a closer ordered after the doorset arrives holds the job up, and a leaf with no line beside it cannot be checked on arrival. The how to specify security doors guide names what the order must hold.

The unit manager walks the building with the door list once a month, working each leaf in turn. A dragging leaf, a closer that leaves a leaf standing open and a seal painted over in a refit are written against their own doors that day. What to look for on each leaf is named in the fire door inspection checklist, and the work that keeps the leaves holding is named in the fire door maintenance guide.

Write the period, the grade and the lock on one line for each leaf, and match the line to its room before the leaf is hung.

What period should a maternity unit drugs store door carry?

FD60 to EN 1634-1, because the drugs store holds drugs, and an hour is the hold that room demands.

What period should a maternity unit entrance door carry?

FD30 to EN 1634-1, because the entrance is the way out and half an hour is what the public route needs.

Can one leaf hold fire and forced entry?

Yes, where one doorset passed the fire test and the forced entry test together, so a single report names the period and the grade for that leaf.

Do maternity unit fire doors need a smoke rating?

Yes, the leaves on the route carry Sa or S200 to BS EN 1634-3 beside their period, because mothers meet smoke before flame on the way out.

What happens when a fire door will not shut?

A leaf that will not shut is written up against its own door the day the fault is found, and the unit does not wait for the next look round.

Specifying fire doors for a maternity unit?Send the door list and the period each room must hold for a tested door quotation.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →

Products

One supplier for the whole building envelope

Ready to specify your project?

Free assessment, written specification and test evidence. Reply within one working day.