Fire Door Regulations for Retail Explained
Retail fire doors under the Fire Safety Order 2005: shopfront and stockroom doors, escape routes through trading areas, and mall and landlord duties.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
A shop is a building where strangers walk in all day. Customers browse the aisles, staff work the tills, deliveries arrive at the back door, and nobody inside knows the building the way the people who work there do. A fire door in a shop has to hold a fire back long enough for all of those people to leave through the trading floor, and it has to do it on a day when the doors have already opened and closed hundreds of times. That is why the rules for retail fire doors are not the same as the rules for an office, a school or a hospital, even though the door itself looks much the same.
The law is the Regulatory Reform (Fire Safety) Order 2005, which names a responsible person for the premises and puts the duty to assess the fire risk and keep the doors working on that person. For a single shop the responsible person is usually the retailer who occupies the unit. For a unit in a shopping centre the landlord is the responsible person for the common parts, the malls and the shared stairs, and each unit has its own responsible person for its own doors. Our fire door regulations for commercial buildings guide covers the Order and Approved Document B in full, our fire door regulations for schools guide covers the same Order from the school side, and our fire door regulations for hospitals guide covers it from the hospital side, where the users are patients who cannot move on their own.
The two periods a shop meets most often are FD30 and FD60. They are fire resistance periods tested to EN 1634-1, and the number is the minutes the doorset held its rating in the furnace test. FD30 holds for 30 minutes and FD60 for 60 minutes. The letters in front of the number say what the door holds back: E for integrity, EW for integrity with a limit on radiated heat, and EI for integrity with insulation. A door marked FD30S also carries a smoke rating. Our fire ratings page sets out the three letters and the periods behind them.
- Fire Safety Order 2005The law that names a responsible person for the premises
- FD30 and FD60Fire resistance periods tested to EN 1634-1
- FD30S30 minutes integrity plus smoke control
- BS EN 1154 closersSized to the leaf, minimum EN 3 on a fire door
The Order names a responsible person for every shop
The Regulatory Reform (Fire Safety) Order 2005 applies to non-domestic premises, and a shop is one of them. The responsible person is the employer, the occupier or the person who has control of the premises, and the duty is to carry out a fire risk assessment, act on what it finds, and keep the fire doors working after the builders have gone. The duty is not a one-off task. It lasts for as long as the shop trades, and it follows the building through every refit, every change of layout and every change of tenant.
In a single shop the position is simple: the retailer who occupies the unit is the responsible person for the whole unit, front door, stockroom and rear door included. In a shopping centre the position is shared. The landlord is the responsible person for the common parts, the malls, the shared corridors and the shared stairs, and each unit has its own responsible person for the doors inside its own demise. The boundary between the two must be written down, because a door that both sides think the other side looks after is a door nobody looks after.
A lease can set out who pays for the work, but it cannot remove the duty from the person the Order names. A retailer who signs a lease that says the landlord maintains the doors should still check that the doors are maintained, and a landlord who lets a unit should still check that the tenant’s doors close and latch. The fire risk assessment is the document that names the doors, the ratings and the checks, and it should be read whenever the shop changes hands or the layout changes.
Shopfront doors: glass, trading hours and the door that faces the street
The shopfront door is the main entrance and the main exit at the same time. Customers pass through it all day, and in a fire it is the door most of them will try first. Glass matters here more than in most buildings, because customers need to see in and staff need to see out, and the glass must be part of the tested doorset. A pane of glass fitted into a fire door after the test is a change to the tested assembly, and the rating does not cover it. The letter matters too: an E door stops flames and hot gases, an EW door adds a limit on radiated heat, and an EI door adds insulation, so the temperature rise on the safe side is limited and the door can be touched. Escape routes where customers pass close to the door usually need EI, because people escape past the door and may need to put a hand on it.
During trading the shopfront door works harder than any other door in the building. It swings or slides all day, and the closer must return it to the closed and latched position every time. A closer sized to BS EN 1154 for the leaf will do that, but a closer that has been adjusted by hand, a closer with a leaking body, or a closer taken off because it was too stiff, will leave the leaf standing open. A door that stands open for trade needs a hold-open device to BS EN 1155 that releases the door when the alarm sounds, so the door can stand open when the shop needs it open and still close when it matters.
At closing time the shopfront changes hands. The shutter comes down, the grilles close, and the staff leave through the rear or the side door. The final exit must open in one action without a key, because staff leaving at the end of the day must not have to search for a key while the shop is closing around them. A shopfront door that is locked from the inside while staff are still inside is a trap, not a security measure.
Stockrooms and rear doors: the doors nobody watches
Rear doors fail more often than shopfronts because they are out of sight. A back door facing a yard or a service road can be attacked for minutes without being seen, so it needs a higher rating than the front. Our security shutters and doors for shops page works through the shopfront and the rear door together. A SR2 rated steel door resists three minutes of attack with tools such as screwdrivers, pliers and hand saws. C5 covers five minutes with crowbars, drills and chisels, and D10 covers ten minutes with sledgehammers, disc cutters and jigsaws. The rating belongs to the whole doorset, leaf, frame, locks and fixings together, so a rated leaf in an unrated frame is not a rated door.
The stockroom holds the same goods as the shop floor, but fewer people pass it, so a stockroom door should lock separately from the shop door and only named staff should hold the key. The fire rating still applies on top: a stockroom door commonly carries FD30 or FD60, because the stock inside it burns, and the door must close and latch behind every person who passes through. Deliveries are the weak point. A delivery driver who wedges the rear door open for the van has left the building open to fire and to theft at the same time, and a wedge has no release when the alarm sounds.
Some shop doors must do two jobs, fire and security together. A rear door must hold fire and resist forced entry, and the two jobs need two sets of evidence on one assembly: a fire classification to EN 1634-1 and a forced entry rating to LPS 1175 or PAS 24. A steel leaf is strong, but strength is not a security rating, and a door rated FD60 can still fail a forced entry test. Our dual certification guide works through how fire and security sit on one doorset.
Escape through the trading floor: aisles, tills and the way out
In a shop the escape route runs through the trading floor. Customers leave past the shelves, past the tills and past the displays, and the route must stay clear from the back of the shop to the front door. Stock in the aisles, trolleys left by the tills and promotional displays pushed into the gangway all narrow the route at the very point it matters most. A route that is clear on a quiet morning and blocked on a busy Saturday is not a route at all. The fire risk assessment should name the escape routes and the width they must keep, and the daily routine should check them before the shop opens.
Panic hardware belongs on the doors where people leave under pressure. A bar across the leaf that opens the door when it is pushed, to BS EN 1125, covering at least 60 percent of the leaf width, is the fitting for escape doors where more than 60 people may need to leave at once. The door must open in the direction of escape, and it must open in one action without a key, a code or a card. A customer who has never been in the shop before must be able to open the door by pushing it, because in a fire nobody stops to read instructions.
Staff need to know the route as well as customers need to find it. A new member of staff should be shown the escape routes, the final exits and the doors that must stay shut on the first day, not after the first fire drill. Signs point the way, but signs do not move stock out of an aisle. The person who closes the shop at night should walk the escape routes last, because a blocked route found at closing is a route that can be cleared before the next morning.
Malls and shared parts: where the landlord’s duty ends and the unit’s begins
A shopping centre is a building of buildings. Each unit trades behind its own shopfront, and the mall in front of them is a shared escape route for every unit at once. The landlord’s responsible person looks after the mall, the shared corridors, the cross-corridor doors and the shared stairs, and each unit’s responsible person looks after the doors inside its own demise. The doors between the two, the unit doors that open onto the mall, are the ones that matter most, because they are the doors the mall depends on to hold smoke and fire inside the unit while the mall fills with people.
Smoke is the first problem in a mall. A fire in one unit fills the mall with smoke long before the flames reach the shopfront, so the unit doors need the smoke class the fire strategy names, and the seals must be intact. A door marked FD30S carries 30 minutes of integrity plus smoke control, tested to BS EN 1634-3, and the S must be named in the specification where the fire strategy needs it. A fire rating on its own does not prove smoke control, so ask for the smoke evidence by name.
Service corridors run behind the units, and they carry deliveries, waste and staff between the units and the service yard. The doors between the service corridor and the mall, and between the service corridor and each unit, divide the building into compartments, and they must close and latch every time.
Shutters, grilles and the fire door behind them
A shutter is security, not fire protection. It stops a person breaking in after hours, but it proves nothing about fire, and a shop that relies on the shutter alone has no fire door at the front at all. The fire door must sit behind the shutter or beside it, as its own doorset with its own test evidence, and the two must not be confused. A grille is the same: it lets customers see the goods after hours and lets air through, but it holds back no fire and no smoke.
A powered shutter needs its own safety. Safety in use of power operated doors is covered by EN 12453, and the safety devices are chosen for the entrance, not pulled from a shelf. Photocells must watch the path of the shutter, and safety edges must stop it when they touch an obstruction.
At closing time the shutter comes down while staff are still inside, and the exit route must stay open until the last person leaves. The final exit, usually the rear or side door, must open in one action without a key, and the route to it must stay clear while the shutter is down. Never lock staff in behind a shutter. A shop that closes its shutter before the last member of staff has left has closed the escape route first and the shop second.
Closers, seals and the parts that fail first in a shop
The closer is the part that fails most often, and in a shop it fails under the hardest use in any building. A closer sized to BS EN 1154 for the leaf weight will close the leaf and hold the latch every time, but a closer that has been adjusted by hand, a closer with a leaking body, or a closer taken off because it was too stiff, will leave the leaf standing open. A door that does not close has no fire performance, whatever its certificate says. Our fire door closers guide sets out the power sizes in BS EN 1154 and how to read them.
Opening force is a shop problem as much as a fire problem. A door must open with less than 30 N in the first 30 degrees and less than 22.5 N beyond that, under BS 8300 and Approved Document M, because customers push trolleys, pushchairs and wheelchairs through these doors all day. A closer that is too strong for the leaf makes the door fail the access rules and invites staff to wedge it open. Hinges to BS EN 1935 carry the leaf, grade 13 or grade 14, and a hinge that has dropped lets the leaf sag, so the closer cannot close it squarely.
Seals and gaps are the small parts that decide the rating. A 4 mm gap around the leaf is the usual limit, and a doorset fitted with wider gaps has lost the performance the certificate describes. Intumescent seals close the gap in a fire, expanding at roughly 200 to 250 degrees, and smoke seals close it against cold smoke. Both have to be fitted, intact and unpainted, or the compartment line is broken at the very point it matters most. Our fire door hardware guide sets out the hardware set, hinges, seals and latches included, and how each part is graded.
Deliveries and the back door: the opening that is left open
The rear door of a shop is the door that gets wedged open. Deliveries arrive through it all day, staff use it for breaks, and a wedge is quicker than a hold-open device. A door held open by a wedge has no release, and a door that stands open in a fire lets smoke through before the alarm has finished sounding.
A hold-open device to BS EN 1155 is the answer where a door must stand open for use. It holds the leaf open and releases it when the alarm sounds, so test the release at every inspection. A closer to BS EN 1154 should bring the leaf back and hold the latch every time, with EN 3 as the minimum power size on a fire door. Test the closer after every delivery round, because a closer that has lost its power leaves the leaf standing short of the latch.
The stockroom needs the same discipline as the trading floor. Boxes stacked against a door stop it closing, and a door that cannot close will not hold fire or smoke. Keep the route to the rear door clear, keep the closer working and keep the seals whole, and check the door at the end of every trading day.
The rear door also faces a quieter approach than the shopfront, so it often needs a higher security rating than the front door. A rear door that faces a yard after hours should carry a forced entry rating to LPS 1175 or PAS 24, on the whole doorset. A rated leaf in an untested frame is not a rated doorset, and changing the leaf, the frame, the glass, the seals or the hardware can break the tested construction.
Trading hours and the shutter: what the fire door does when the shop is shut
A roller shutter closes the shopfront at night, and the fire door behind it still has a job. The shutter stops a thief, and the fire door stops fire and smoke moving between the shop and the escape route. The two are tested as different assemblies, and a shutter rating does not prove the fire door, so ask for the evidence for each one by name.
A shutter that jams half open traps smoke in the shop, and a fire door with a broken seal lets smoke through a gap the eye cannot see. The inspection routine should cover both, and the log should name the date, the door and the person who checked it. The checks that catch a failing leaf before it matters are in our fire door inspection checklist.
A shopfront door faces the street all day, and it must admit shoppers and release them in one action. Doors that serve more than 60 people need panic hardware to BS EN 1125, with a bar across the leaf covering at least 60 percent of the leaf width. Under BS 8300 and Approved Document M, a door must open with less than 30 N in the first 30 degrees and less than 22.5 N beyond that. The power sizes in BS EN 1154 are set out in our fire door closers guide, and our fire door regulations for commercial buildings guide sets out the same discipline for a building that is not a shop.
| Part | What to look for | When |
|---|---|---|
| Rear door | No wedge, hold-open release works | At the end of every trading day |
| Closer | Leaf closes and holds the latch | Every month |
| Seals and gaps | 4 mm gap, seals whole and fixed | Every month |
| Shutter and fire door | Shutter runs full travel, fire door closes | Every month |
Keep the test report, the classification and the inspection log with the shop records, so the next responsible person can find them without asking.
Ordering retail fire doors: one specification, one set of evidence
Ordering fire doors for a shop is a specification exercise, not a shopping exercise. The order should name the rating in full, FD30 or FD60 with the letter and the smoke rating where the strategy asks for it, and it should name the leaf, the frame, the glass, the beads, the seals and the hardware as one doorset. Our how to specify security doors guide covers the same discipline for rated security doors, and our types of security doors guide sets out the range of doors a shop may need.
The security side needs its own evidence where the door must also resist attack. A lock is not a security rating, and a steel leaf is strong but strength is not a rating. Security comes from a separate test, LPS 1175 or PAS 24, on the whole doorset. Our fire rated steel doors page covers the steel leaf that carries both jobs most often, and a rear door that must hold fire and resist a break-in needs both sets of evidence on the same construction.
Finally, order the evidence with the doors. The test report, the classification and the hardware schedule should arrive with the doorset, and the handover pack should name the inspection routine the shop will follow. A shop that files the evidence on the day the doors arrive has a record it can use for the whole life of the building. Our fire door inspection checklist gives the checks that catch a failing leaf before it matters.
| Door position | Period | What it must do | What to check |
|---|---|---|---|
| Shopfront door | FD30 or FD60 | Let customers in and out, close and latch after every use | Closer, glass, latch, hold-open release |
| Stockroom door | FD30 or FD60 | Hold fire in the stockroom, lock separately from the shop | Closer, lock, seals, gaps |
| Rear and service door | FD30 or FD60 | Hold fire and resist forced entry from the yard | Lock, hinges, seals, self-closing |
| Unit door onto the mall | FD30S | Hold smoke and fire inside the unit | Smoke seals, closer, 4 mm gaps |
| Plant and store door | FD60 | Hold a higher-risk fire inside its own compartment | Seals, gaps, self-closing |
In a shop, a fire door wedged open for a delivery is a door that cannot protect the customers behind it.
Who is responsible for fire doors in a shop?
The Regulatory Reform (Fire Safety) Order 2005 names a responsible person for the premises, and for a single shop that is usually the retailer who occupies the unit. In a shopping centre the landlord is the responsible person for the common parts, the malls and the shared stairs, and each unit has its own responsible person for the doors inside its own demise. The boundary between the two should be written down in the fire risk assessment.
Does a shop in a mall need its own fire risk assessment?
Yes. Each unit needs its own fire risk assessment for the doors inside its own demise, and the landlord needs one for the common parts.
Can a shopfront door be held open during trading?
Only with a hold-open device to BS EN 1155 that releases the door when the alarm sounds. A wedge, a chair or a hook on the wall has no such release, and a door held open by one of those will stand open in a fire. If a shopfront door needs to stand open for trade, fit the right hold-open device and the right closer, so the door can stay open when the shop needs it open and still close when it matters.
What is the difference between FD30 and FD60 in a shop?
FD30 and FD60 are fire resistance periods tested to EN 1634-1, and the number is the minutes the doorset holds its rating in the furnace test. FD30 holds for 30 minutes and FD60 for 60 minutes. Shopfront and stockroom doors commonly carry FD30, while plant rooms, stores and doors that protect a long escape route commonly carry FD60, because the people and the contents behind them need more time. The fire strategy names the period for each opening.
Do stockroom doors need the same rating as the shopfront?
They need the rating the fire strategy names for their position, and a stockroom door commonly carries FD30 or FD60 because the stock inside it burns. The rear door may need a higher security rating than the front, because it faces a yard or a service road where an attack can go unseen. The fire rating and the security rating are separate, and each needs its own test evidence on the same doorset.