Fire Door Regulations Restaurants
Fire door rules for restaurants: FD30 and FD60 doors between kitchens, dining rooms and escape routes, and the schedule that orders them all.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
A restaurant fire door has to hold between the hottest room in the building and the people eating on the other side of it. Diners sit through a meal without thinking about the kitchen behind the wall, and the doors between the two are what keep a fire in the kitchen from reaching the tables.
The duties come from the fire strategy and the law behind it. The Regulatory Reform (Fire Safety) Order 2005 leaves one named person carrying fire safety for the premises, and the risk assessment in their hands draws the escape routes and the compartment lines.
What the order has to carry sits inside that strategy: the periods, the seals, the hardware and the records. An order that names each one plainly is the order that puts the right door on the right opening. Our fire door regulations for commercial buildings guide covers the same duties for offices and shops, and the same problem in wards that hold people overnight is covered in our fire door regulations for hospitals guide.
- FD30 / FD60Fire resistance periods tested to EN 1634-1
- FD30S30 minutes with a smoke seal tested to BS EN 1634-3
- BS EN 1125Panic hardware for doors serving more than 60 people
- Martyn’s LawDuties for premises that hold crowds
Kitchens, dining rooms and bars: where a restaurant puts its fire doors
A restaurant breaks into parts that hold people and fire in different ways, and each part asks for its fire doors in a different place. The kitchen holds the heat, the dining room holds the diners, and the bar holds the drinks and the people waiting for a table.
Two kinds of door run through every part of the building. One kind lets people out and the other keeps fire in, and a single leaf can do both jobs only where the test evidence names both for the assembly that will be fitted. Our dual certification guide works through how the two proofs sit on one doorset.
Diners do not know the building, so the doors have to work without being explained. A dining room door has to shut itself after the last diner passes through, and a kitchen door has to stay shut against heat while staff carry plates through it.
The kitchen door: FD60 between the highest fire load and the diners
The kitchen carries the highest fire load in the building, so the doors out of it usually take FD60. A kitchen door opens and closes all through service and still has to shut by itself after every use.
The number after FD comes from the EN 1634-1 furnace test, which holds the doorset in the furnace and counts the minutes it keeps holding. Thirty minutes makes FD30 and sixty minutes makes FD60, and the letters in front of the number say what the furnace measured: E for integrity, EW for integrity with limited radiation, EI for integrity with insulation, with periods running from 30 minutes up to 120. Under EI the heat on the safe side stays under 140 degrees Celsius on average and under 180 at the hottest point. Each figure is set out in our fire ratings guide.
A kitchen door that must also keep strangers out of the stores takes a security rating beside the fire period. The fire proof is a classification to EN 1634-1 and the security proof a rating to LPS 1175 or PAS 24, each proved on the same doorset. The LPS 1175 page sets out the forced entry ratings in full, and our LPS 1175 versus PAS 24 guide compares the two routes.
The hatch and the screen: glass that holds fire and lets staff serve
The kitchen holds the highest fire load in the restaurant, so the door between the kitchen and the dining room takes FD60. The leaf must hold flame and hot gas back for sixty minutes while diners leave by the doors they never practise, and the period follows the fire load behind the door, not the room the diners see.
Dining room doors guard the escape route diners never practise, so they must open with a light push and shut behind the last person out. The force to open the door must stay below 30 N for the first 30 degrees of travel and below 22.5 N beyond, under BS 8300 and Approved Document M, so a diner with a child in one arm can push the door open with the other.
Glazed screens and serving hatches let staff serve without opening the kitchen door, and the glass must be proved for the job. Glazing proved for fire is tested to EN 1634-1 with the frame and the fixings, and the letters E, EW or EI beside the period name what the furnace measured. The glass, the beads and the fixings belong on the same line as the leaf.
Smoke finds the gaps a door leaves open, so the seal on a restaurant door must be checked on every round. Intumescent seals expand at around 200 to 250 degrees, and the gap round the leaf must stay at 4 mm, because a wider gap lets smoke past the leaf into the dining room. A door on a smoke path takes FD30S, with the seal proved to BS EN 1634-3, to Sa at room temperature and S200 at 200 degrees Celsius.
Back of house doors: the stores, the laundry and the plant room
Back of house doors guard the stores, the laundry and the plant room behind the kitchen, and they take the period the fire load behind them demands. A store that holds linen and paper takes FD30, while a plant room with a heavier load takes FD60, and each needs a closer that pulls the leaf shut against the draught from the corridor. The closer must be sized to the leaf, with no fire door taking less than EN 3 to BS EN 1154.
The duties a restaurant carries under Martyn’s Law follow the number of people it holds, with a standard tier from 200 to 799 people and an enhanced tier at 800 and above. Most restaurants sit in the standard tier, so the fire strategy must still show how the dining room empties and how the doors release.
The round walks the kitchen, the dining room and the back of house in turn and looks at the closers, the seals, the hinges and the glazing. A closer that no longer pulls the leaf shut, a seal that has come away, or a hinge that lets the leaf drag each gets written down the same day, with the door and the fault beside it, so the repair follows the fault and the restaurant never stands open.
| Position | Door | Period | What to check |
|---|---|---|---|
| Kitchen | Fire door | FD60 | Seals, closer, latch |
| Dining room | Fire door | FD30 | Closer, release, gap |
| Serving hatch | Glazed screen | FD30 | Glass, beads, fixings |
| Plant room | Fire door | FD60 | Seals, closer, latch |
Put the period, the closer and the seal on the same line as every restaurant door on the order, so the leaf that arrives matches the leaf that was tested. The sizes and the fitting of closers are set out in our fire door closers guide, and what each visit should look for is set out in our fire door inspection checklist. The periods for the shared parts of a public building are set out in our commercial buildings fire door regulations guide, and the doors that must hold smoke back are covered in our smoke control doors guide.
Dining room doors and the escape route diners never practise
Nobody in a dining room has practised the way out, so the route has to work on signs, lights and instinct. Each door on it opens in one action, swings the way people run, and asks for no key.
Once a door serves more than 60 people, panic hardware to BS EN 1125 belongs on it, with a bar that spans at least 60 percent of the leaf and releases in a single push. The bar has to suit the door it sits on, because a bar fitted to a leaf never tested with it leaves the doorset with no proven rating.
BS 8300 and Approved Document M cap the opening force at below 30 N through the first 30 degrees and below 22.5 N beyond that. A closer set too strong for the leaf leaves the door outside those limits, and a diner carrying a tray, a child or a walking stick cannot open it. BS EN 1154 sets the closer power sizes, and no fire door takes less than EN 3. Our fire door hardware guide covers the grades and the parts that make a fire door work, and the fire door closers guide lists the power sizes and the adjustments that keep a closer inside the rules.
FD30 and FD60 in a restaurant: the period each door carries
The fire strategy sets the period for each opening by the fire load behind it. A dining room escape door usually takes FD30, while a door in the wall between the kitchen and the dining room usually takes FD60.
Flame is not the first thing down a corridor. Smoke arrives ahead of it, so a door on a smoke path needs a seal beside its period. FD30S pairs 30 minutes of integrity with a smoke seal to BS EN 1634-3, to Sa for smoke at room temperature and S200 for smoke at 200 degrees Celsius, and the gap round the leaf stays at 4 mm, because a wider gap lets smoke past the seal. Intumescent seals swell at roughly 200 to 250 degrees and close the gap as the heat builds.
A serving hatch door or a dining room door held open through service needs a hold-open device to BS EN 1155 that lets go on the alarm. A wedge under the leaf gives it no release at all, so the device belongs on the schedule beside the door.
Glazed screens, serving hatches and the smoke that finds the gaps
Glazing lets staff see into the dining room before they open a door, and a rated screen behind the glass holds if a kitchen catches fire. The glass, the frame, the beads and the fixings go through the test together, so a rated pane in a frame that was never tested is not a rated screen. Our fire rated windows guide covers how glass, frame and beads are tested together, and the fire rated glazed doors page explains how the assembly is proved.
A serving hatch between the kitchen and the dining room is a wide opening in a compartment wall, and it needs a shutter or a sliding fire door that closes on alarm. A sliding fire door runs on a track and closes when the alarm sounds, and the release belongs on the schedule. The fire rated sliding doors guide explains how one is proved.
Smoke finds the gaps a fire door leaves, so the seals and the gaps belong on the inspection round beside the closer. The smoke control duties of a corridor door are set out in our smoke control doors guide.
Back of house: stores, laundry and the plant room behind the kitchen
The rooms behind the dining room carry their own risks. A plant room door needs FD60 and a closer that can pull a heavy leaf shut against the draught from the plant, a store door needs a lock that keeps strangers out of the stock, and a laundry door needs a closer that survives heat and steam through the day.
Deliveries arrive through the back of the building, so the bay door and the personnel door beside it go on the same schedule as the dining room doors. The personnel door beside the bay shutter belongs in the same order as the shutter, so nobody has to lift a shutter to walk out. Our loading bay doors guide covers bay doors in full.
Crates, trolleys and a thousand openings a week wear the small parts first. A hinge earns its grade from the cycles and the load it can carry to BS EN 1935: grade 13 is proved for 200,000 cycles at 120 kg, and grade 14 for the same cycles at 160 kg. Hang a heavy leaf on a hinge that cannot carry it and the leaf sinks, drags on the floor and stops latching.
Martyn’s Law and the duties a restaurant carries
A restaurant that holds crowds carries duties with it. Martyn’s Law works in tiers for premises that hold 200 or more people: the standard tier covers premises holding 200 to 799 people and the enhanced tier covers premises holding 800 or more, so a large restaurant sits in the standard tier and a very large one in the enhanced tier. Royal Assent came in April 2025, go-live is expected in spring 2027, and the Security Industry Authority regulates the scheme.
Our Martyn’s Law guide sets out the tiers and what each one asks of a building, and our airports guide shows the same periods at work in a terminal.
The restaurant order: one schedule for every table, kitchen and corridor
Write the enquiry as a specification, one line for every opening. Each line names the building and the position, the fire period, the smoke seal and the security rating where one is needed, and the leaf, frame, glass, beads, seals and hardware as one doorset. Where a door must also resist attack, ask for the rating on the whole doorset, a rating to LPS 1175 or PAS 24, and not on the leaf alone. The how to specify security doors guide sets the columns for the same discipline.
Keep the test report, the classification and the hardware schedule with the doors from the day they arrive, and write the inspection routine into the handover pack, so the next operator can see which door carries which period and which check each door has passed. The fire door inspection checklist covers what each check looks for.
| Door position | Period | Hardware | What to check |
|---|---|---|---|
| Kitchen to dining room | FD60 | Closer, hinges grade 13 or 14 | Seals, gaps, self-closing |
| Dining room escape route | FD30 | Panic hardware, closer | Opening force, seals |
| Dining room to corridor | FD30S | Closer, smoke seal | Seals, gaps, latch |
| Store or plant room | FD60 | Closer, latch | Seals, gaps, self-closing |
| Serving hatch | FD30 | Sliding fire door, release on alarm | Release, self-closing |
A restaurant kitchen door holds the hottest room in the building away from the diners, so the period and the closer matter as much on the schedule as the leaf itself.
What fire rating should a restaurant kitchen door carry?
Most often FD60, because the kitchen carries the highest fire load in the building. The fire strategy for the restaurant names the period for each door.
Do restaurant escape doors need panic hardware?
Yes, once more than 60 people use the door. Fit a bar to BS EN 1125 that spans at least 60 percent of the leaf width.
Can one restaurant door hold a fire rating and a security rating?
Yes, where the doorset carries a test report for each job. The fire report comes from EN 1634-1 and the security report from LPS 1175 or PAS 24, and both reports must name the doorset that will be fitted.
How often should restaurant fire doors be checked?
On the routine the responsible person sets. Each check goes on the record with the door, the fault and the fix, and the inspection checklist guide sets out what each check looks for.
How do I order doors for a whole restaurant?
Write one schedule with one line for every opening, naming the building, the position, the period, the smoke seal, the security rating and the whole doorset.