Fire Door Rules for Ports

A port fills with crews and visitors who do not know its quays, so fire doors take their period from the room behind them, terminal to plant room.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

A port is a working quay where crews, visitors and drivers move among cargo, fuel and machinery, and the fire doors are the leaves that hold a fire where it starts while those people find the way out. The period on each door follows the room behind the leaf, because a terminal, a stores room and a plant room ask different things of the doors that guard them.

The rules for the shared parts of any transport building are set out in the transport hub security requirements guide, and the rules for the stores beside the quay are set out in the warehouse security doors guide. The port order names every door in the building, with the period and the hardware beside each one.

The port draws up its fire plan before a single leaf is ordered, naming the period each opening must hold and the route each person must follow, and the order follows that plan leaf by leaf.

  • FD30 / FD60Fire periods to EN 1634-1
  • Sa / S200Smoke proof to BS EN 1634-3
  • EN 3Smallest closer power to BS EN 1154
  • One listEvery port door named

Terminals, stores and back offices: one quay, three periods

A port holds three kinds of room under one fence line: terminals full of passengers and paperwork, stores full of cargo and spares, and back offices full of records and keys. The rules follow the rooms, because a leaf between a terminal and a stores room must hold fire back while the people on the other side find the way out.

The terminals take the doors that let passengers and crews in and out, and each leaf must open for people who have never seen the building before. The stores take the doors that guard the cargo, and each leaf must hold fire back where the goods sit in boxes and crates. The route that joins them takes the doors the crews pass through, and each leaf takes the period the escape needs.

The plan names each opening with its door, so a leaf ordered for the stores never ends up guarding the terminal.

FD30 and FD60 on a quay: the periods each room takes

Each part of a port asks a different period of its doors, because the load behind each leaf is different. The terminal holds passengers and paperwork, the stores hold cargo and fuel, and the plant room holds the machinery that serves the whole quay, so the period is set by the room, never by the leaf alone.

EN 1634-1 gives a fire door its proof as minutes beside letters. The minutes run from 30 to 120, and the letters name what stayed on the far side of the leaf: the flames on their own, the flames with some of the heat, or the flames with the heat as well.

A leaf proved for the longer period weighs more and needs a deeper frame to carry it, so the figure on the quotation rises with the period. A leaf proved for 30 minutes must never fill an opening that needs 60, because the shorter proof is the one that fails first.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

The terminal: passengers, luggage and the doors between them

A terminal is a busy room full of people with luggage, and the doors on it must hold their proof while letting passengers pass in and out all day. A glazed leaf lets the staff see the quay beyond it without opening the leaf, and the pane takes the same proof as the leaf, because the leaf and the glass are proved as one doorset.

The paperwork and the fittings in a terminal carry a fire load of their own, and the doors between the terminal and the stores must hold the fire where it starts. The stores side of that wall takes the period the stores demand, because the fire that starts among the cargo must stay among the cargo while the passengers move out.

For the windows on the same wall, the fire rated windows guide names what the pane must hold, and the fire rated glass cost guide works through what the glass itself adds to the order.

Stores and back offices: the doors behind the quay

The stores take the heaviest fire load on the quay, because the cargo and the fuel sit there all day. A stores leaf takes FD60, and the period follows the fire load, not the size of the room.

The back office takes the same care, because the records and the keys sit behind its doors. A back office leaf takes FD30 where the office sits beside the terminal, because the fire that starts among the cargo must not reach the records.

A stores leaf or a back office leaf may need a forced entry proof as well as a fire proof, because both rooms need the two together. LPS 1175 names the forced entry categories: B3 for three minutes, C5 for five and D10 for ten, all to Issue 8.2 of September 2024. The LPS 1175 vs PAS 24 guide sets the two ratings beside each other, the keeping an LPS 1175 rating valid guide names the faults that break a rating after fitting, and the fire and security doors dual certification guide shows how one doorset carries both proofs.

The plant room and the control room: what the back of quay doors must hold

The plant room holds the machinery and the electrical boards that keep the quay working, and the leaf that guards it takes the period the load behind it demands. A plant room leaf takes FD60, and the period follows the fire load in the room, not the size of the plant.

The control room beside the plant room takes the same care, because the systems that run the quay sit behind its leaf. A control room leaf takes FD60 where the room sits beside the plant room, because the fire that starts among the machinery must not reach the systems.

Some quay leaves must stay open while the working day runs, and those take a hold-open device proved to BS EN 1155, which releases the leaf the moment the alarm sounds. Anything wedged under a leaf to keep it open defeats the proof, because a leaf held open by a crate cannot shut when the fire reaches it.

When the alarm sounds: the routes a full port uses

Once the alarm sounds, everyone on the quay takes the route the building gives them, so the way out must be clear of anything in the way. Each door on that route opens with a single push from whoever reaches it, whether the power is on or off.

The route doors carry a smoke proof beside the fire period, proved to BS EN 1634-3. The proof has two marks: Sa for smoke at room temperature, S200 for smoke at 200 degrees. Smoke reaches the route ahead of the flames, because it moves faster than fire, and a seal works only where it touches the frame all the way round. How the doors hold smoke back while people move past them is set out in the smoke control doors guide.

The route lasts only as long as its weakest leaf, so every leaf on it takes the same period. Where one leaf carries a shorter proof than the leaves beside it, that leaf gives way first and the route fails with it. The fire door regulations retail guide shows the same care taken with shoppers in a store.

Position Door Period What to check
Terminal Glazed leaf FD30 Leaf, glass, bar
Stores Steel leaf FD60 Leaf, lock, seals
Back office Steel leaf FD30 Leaf, lock, seals
Plant room Fire leaf FD60 Leaf, seals, gap
Public route Fire leaf FD30 Leaf, bar, closer

Closers, seals and gaps on port doors: what the period rests on

A port leaf is opened more times in a day than most doors, so its closer works harder than most. BS EN 1154 sets EN 3 as the smallest closer power on a fire door, and the check is simple: open the leaf and watch it come home on its own. A closer that has lost its pull leaves the leaf standing open after the crew has passed, and an open leaf holds nothing back.

The leaf hangs with a 4 mm gap at its sides, so it moves without catching and the seal meets the frame once the leaf is shut. As the heat climbs toward 200 to 250 degrees the intumescent seal swells to shut that gap, unless paint laid over the seal stops it swelling. When a seal has slipped from its groove, the fault is written against its door on the day it is found, with the part and the date beside it.

Each hinge takes its share of the leaf through every opening of the day, and a hinge that has worked loose lets the leaf sag until it drags on the floor and smoke slips through the gap it leaves at the top. The fire door hardware guide names what the lock the key turns must do, and the fire door closers guide works through sizes and fitting for closers.

Ordering for a port: one list, every door on it

The whole port order sits on one list, a line for every door with the leaf, the period, the lock and the closer beside it, so the door that arrives is the door each room asked for. A list that names a single leaf for the whole quay leaves the fitter to guess which room takes which period, and a leaf fitted to the wrong room guards the wrong thing.

Before the order goes out, the quotation is read against the list, figure by figure, so every figure sits beside the door it belongs to. A figure left off the quotation still has to be paid, and a part added after the order costs more than the same part ordered with the building. The how to specify security doors guide names the columns the list must hold, and the security door cost factors guide works through what each step up the scale adds to the price.

Before the first ship each week the port tries its leaves in turn, starting at the terminal and finishing at the plant room. Any leaf that drags, any seal slipped from its groove, or any closer that has lost its pull is noted against its door on the day it is found, and the repair is booked while the fault is still small. The record stays with the port file, and what the visit should cover is set out in the fire door inspection checklist.

A port leaf holds only as long as the rooms behind it and the route beside it, so the period, the release and the closer must all sit on the same list.

What period should a port door carry?

FD30 or FD60, proved to EN 1634-1. The terminal takes FD30 and the stores take FD60, so the period follows the room the leaf guards, and the letters beside the minutes name what the doorset held back.

Can one leaf hold fire and forced entry?

Yes, where one doorset went through the fire test and the forced entry test as a single assembly, leaf, frame and seals together, so the report names both proofs.

Do port doors need panic hardware?

Yes, each leaf on the way out takes a panic bar proved to BS EN 1125, set across at least 60 percent of the leaf, so a single push throws the latch.

What period should a control room door carry?

A control room leaf takes FD60 where the room sits beside the plant room, because the fire that starts among the machinery must not reach the systems that run the quay.

Who checks the port doors?

The duty manager walks the round that covers every door, and each visit is written into the record the port keeps.

Specifying doors for a port?Send the door list and the period each door must hold for a tested door quotation.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →