A warehouse fire door has to work in a building that never stops moving. Forklifts cross the floor all day, stock moves in and out through the bays, and the doors on escape routes and compartment walls must still close, seal and hold when the alarm sounds.
The rules come from the fire strategy for the building and the law behind it. The Regulatory Reform (Fire Safety) Order 2005 names a responsible person for the premises, and the fire risk assessment sets out where the escape routes run and where the compartment walls stand.
The periods, the hardware, the shutters and the records all sit inside that strategy, and an order that names them plainly is the order that gets the right doors on the right openings.
- FD30 / FD60Fire resistance periods tested to EN 1634-1
- FD30S30 minutes with a smoke seal tested to BS EN 1634-3
- BS EN 1154Closer power sizes, minimum EN 3 on fire doors
- BS EN 1125Panic hardware for doors serving more than 60 people
Racking aisles, loading bays and stores: where a warehouse puts its fire doors
A warehouse divides into parts that move stock in different ways, and each part puts its fire doors in a different place. The racking aisles hold the stock in rows, the loading bays move it in and out through the wall, and the stores hold the goods that wait for a bay, while the offices and plant rooms sit beside the floor that serves them all.
Every one of those parts has doors on escape routes and doors on compartment lines, and the two sets of doors do different jobs. An escape door must open at once and let staff out, while a compartment door must stay shut and hold fire on one side of a wall. A door can carry both jobs, but only where the test evidence covers both, on the one assembly that will be fitted.
The security side of a warehouse door follows a different set of rules, and the two sides must not be confused. Our warehouse security doors guide sets out the doors that keep a warehouse secure, and our warehouses and logistics sector page covers the buildings that hold the stock. The fire side is the subject here: the doors that hold fire back and let people out.
Escape routes through a working warehouse: the doors forklifts and staff share
An escape route from a warehouse floor runs between the racking, through a cross-corridor door, down the stairs where the building has them, and out through the exits, and every door on that route must open at once when a person reaches it. A door blocked by pallets, a door locked against theft or a door that needs a key stops the route, and a stopped route on a working floor is the failure the regulations exist to prevent.
Every loading bay needs a personnel door beside the shutter, so nobody has to open the bay just to walk in or out. A person should never have to lift a shutter to escape, and the personnel door beside it wants specifying at the same time as the shutter, while the order is still open. Our loading bay doors guide sets out bay doors in full, and the same discipline runs through offices in our fire door regulations for offices guide.
FD30 and FD60 in a warehouse: matching the period to the compartment
The EN 1634-1 furnace test gives the period: 30 minutes of holding makes FD30, and 60 minutes makes FD60. The letters ahead of the number say what the test measured, E for integrity, EW for integrity with limited radiation, and EI for integrity with insulation. The EI figure caps the heat on the safe side at 140 degrees Celsius on average and 180 at the hottest point.
The fire strategy sets the period for each opening, and the period follows the fire load behind the door. A door on an escape route from the floor usually takes FD30, a door on a compartment wall between two storage areas usually takes FD60, and a door to a plant room or a battery charging area takes FD60, because the fire load behind it is higher. Our fire ratings guide sets out what each letter and number means, and our fire door regulations for airports guide shows the same periods at work in a terminal.
A corridor fills with smoke long before flame gets there, which is why a door on a smoke path carries a seal beside its period. FD30S means 30 minutes of integrity with a smoke seal to BS EN 1634-3, to Sa or S200, and the seal only works where the gaps are right. Keep the gaps at 4 mm, because a seal on a door with a wide gap seals nothing, and intumescent seals expand at roughly 200 to 250 degrees to close the gap as the heat builds.
Compartment walls and the doors that hold the line
A compartment wall is only as good as the doors that pass through it. The wall divides the warehouse into sections so a fire in one section stays there long enough for staff to escape and for the fire service to arrive, and every opening through the wall needs a door of the same period as the wall itself. A FD60 wall with a FD30 door in it is a FD30 wall, whatever the drawings say.
Wide openings through a compartment wall take sliding fire doors, where the leaf runs on a track and closes on alarm. Our fire rated sliding doors guide sets out how one is proved, and our dual certification guide covers the doors that also carry a security rating.
Roller shutters, personnel doors and the fire door behind them
Roller shutters sit on the bays and on the openings between storage areas, and a shutter on a compartment line must hold fire as well as close the opening. A fire rated roller shutter is proved to EN 1634-1 as a shutter, with its own test report, and the guides, the barrel and the motor all belong in the assembly that was tested. Our fire rated roller shutters page sets out how the shutter is proved, and our roller shutter regulations guide sets out the rules that govern one.
A shutter is not an escape door unless the fire strategy says so, and the personnel door beside it is the way out. The shutter closes on alarm through a hold-open device to BS EN 1155, and the release on alarm belongs on the schedule beside the shutter. The hardware on the personnel door is covered in our fire door hardware guide.
Closers, seals and gaps: the parts that fail first in a warehouse
Closers fail first on a warehouse door, because the leaf is heavy and the draught from the bays works against it all day. A closer that cannot shut the leaf leaves the door standing open, and a fire door standing open is a hole in the compartment wall. Closers follow BS EN 1154, with power sizes from EN 1 for a 750 mm leaf at 20 kg up to EN 7 for a 1,600 mm leaf at 160 kg, and a minimum of EN 3 on a fire door, so the closer power size belongs on the schedule beside the rating. Our fire door closers guide lists the power sizes and the adjustments that keep a closer inside the rules.
Hinges carry the leaf through thousands of openings in a year, and a hinge that sags leaves a gap the seals cannot close. BS EN 1935 grades hinges by cycles and load: grade 13 covers 200,000 cycles at 120 kg, and grade 14 covers 200,000 cycles at 160 kg. Locks and cylinders follow TS 007, where a 1-star cylinder with a 2-star handle gives a 3-star set, but the lock on an escape door must still release in one action, without a key.
Seals and gaps are the parts a forklift damages first, and the damage is easy to miss on a busy floor. A seal torn off by a pallet, a gap widened by a bent hinge or a leaf dented by a truck all break the rating the doorset was given, and the door needs repair or replacement, not a note in the file.
The closer that fails first: dust, forklifts and the daily cycle
A warehouse door works harder than most fire doors. Forklifts pass through all day, dust settles on the hardware, and the closer must pull the leaf shut every time against the draught from the loading bay. A closer that no longer pulls the leaf shut leaves the compartment open.
No fire door takes less than EN 3 to BS EN 1154, with the power size chosen for the leaf that is fitted, and the sizes and the fitting are covered in our fire door closers guide. A closer fitted to a heavy leaf with too little power never shuts the door, so the power belongs on the order beside the leaf.
The seal is the part that does the work against smoke, and it must be checked on every round. Intumescent seals expand at around 200 to 250 degrees, and the gap round a fire door leaf must stay at 4 mm, because a wider gap lets fire and smoke past whatever the rating on the leaf says.
Roller shutters and personnel doors share the warehouse wall, and each takes its own proof. A fire shutter is not a security shutter, and the fire proof and the forced entry proof sit on separate lines, each proved on its own test. The rules a powered shutter must meet are set out in our roller shutter regulations guide.
Escape routes in a warehouse are shared by forklifts and staff, so the doors on them must open with a light push. Panic hardware to BS EN 1125 takes a bar across at least 60 percent of the leaf width, and the opening force must stay below 30 N for the first 30 degrees of travel and below 22.5 N beyond, under BS 8300 and Approved Document M.
The round that keeps the rating alive: who checks and who signs
Each round looks at the closers, the seals, the gaps and the glazing, and a fault found on the round is written down at once, with the door named and the date noted, so nothing waits for the next visit.
The responsible person on the estate owns the record. Each entry should name the door and the fault, say what was done about it, and carry the date the work was finished, so the next round starts from a record that is complete.
The proof only stands while the door matches the doorset that was tested. The leaf, the frame and the hardware on the test report must all still be in place, because a closer swapped for a lighter one, or a seal painted over, leaves the door with no proof behind it. What each round should look for is set out in our fire door inspection checklist.
Compartment walls hold the fire in one part of the warehouse while staff move to another, and the doors in them take FD60 where the fire load behind them is heavier. Fire resistance is proved to EN 1634-1, with FD30 or FD60 and the letters E, EW or EI naming what the furnace measured.
| Part | What fails | What to check | When |
|---|---|---|---|
| Closer | Leaf left open | Power, arm, fixings | Every round |
| Seal | Smoke through the gap | Seal intact, unpainted | Every round |
| Gap | Fire past the leaf | Gap at 4 mm | Every round |
| Glazing | Pane unproved | Glass, beads, fixings | Every round |
Put the closer, the seal and the record on one schedule line for every opening, so the next reader can see what was tested and what keeps it alive. The periods for the shared parts of a building are set out in our commercial buildings fire door regulations guide.
Inspection, records and the responsible person on a warehouse estate
The responsible person under the Order owns the fire risk assessment, and the assessment is the document the doors are checked against. The inspection round covers closers, seals, gaps and hardware, and the record is kept by the responsible person, so a door that has been changed, damaged or fitted with the wrong hardware since the assessment was written is a door the assessment no longer describes. Our fire door inspection checklist sets out the round in full.
A door that has been propped open, a closer that has been removed, a seal that has been torn off or a leaf that has been dented by a forklift all need the same answer: repair or replace, and record the work. A note in the file without the repair leaves the compartment wall with a hole in it, and the hole is the door. The record should name the door, the fault, the repair and the date, so the next inspection starts from the last one and not from scratch.
The warehouse order: one schedule for every opening
Write a warehouse order as a specification, not a catalogue purchase. Put the building and the position in the enquiry, with the fire period and the smoke control where they are needed, and the leaf, the frame, the glass, the beads, the seals and the hardware as one doorset. Where a door must also resist attack, ask for the evidence on the whole doorset, a rating to LPS 1175 or PAS 24, not a rating for the leaf alone. Our how to specify security doors guide sets out the same discipline column by column.
Ask for the test report, the classification and the hardware schedule to come with the doors, and put them on file the day the doors arrive. The handover pack should name the inspection routine the estate will follow, so the estate holds a record for the whole life of the building.
| Position | Door | Period | What to check |
|---|---|---|---|
| Cross-corridor | Compartment door | FD60 | Self-closing, smoke seals |
| Floor escape route | Escape door | FD30 | Panic hardware, opening force |
| Loading bay | Personnel door | FD30 | Closer, latch, self-closing |
| Bay opening | Roller shutter | FD60 | Hold-open release, seals |
| Plant room | Internal door | FD60 | Hinges, lock, self-closing |
A warehouse compartment wall holds only as far as its doors hold, and a door left open or damaged breaks the line.
What fire rating do warehouse doors need?
The fire strategy decides. A door on an escape route from the floor usually takes FD30, and a door on a main compartment wall usually takes FD60.
Can a roller shutter be a fire door?
A fire rated roller shutter tested to EN 1634-1 can hold a compartment line, but it is not an escape door unless the fire strategy says so. The personnel door beside it is the way out.
Do warehouse escape doors need panic hardware?
Yes, where more than 60 people use the door. Fit hardware to BS EN 1125, with the bar across at least 60 percent of the leaf.
What breaks a warehouse fire door rating?
A door propped open, a leaf dented by a forklift, a closer that cannot shut the leaf, a seal torn off or gaps over 4 mm. Repair or replace the door, and record the work.
Who checks warehouse fire doors?
The responsible person under the Order, on the inspection routine the fire risk assessment sets. The record names the door, the fault, the repair and the date.