Fire door gaps explained: the 4 mm gap round the leaf, measuring with a gauge, what widens the gap, seals and the inspection round that keeps the proof alive.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
A fire door holds fire and smoke back only while the gap round its leaf stays small. The gap is the space between the leaf and the frame, and it must stay at 4 mm, because a wider gap lets fire and smoke past whatever the period on the leaf says.
The gap is measured at the top and both sides of the leaf, and it is checked with a gauge on every round. A frame that has moved with the seasons, a hinge that has sagged under the weight of the leaf, or a floor that has risen under the door can each open the gap without anyone noticing.
The doors that need the gap checked are set out in the fire door regulations commercial buildings guide, and the fire door inspection checklist names what each visit should look for. A gap that is found wide on the round goes on the list the same day, with the door named beside it.
- 4 mmGap round a fire door leaf
- FD30 / FD60Fire resistance periods to EN 1634-1
- BS EN 1634-3 Sa / S200Smoke control for doors on smoke paths
- 200 to 250 degreesHeat that wakes an intumescent seal
Four millimetres round the leaf: the gap a fire door must keep
The gap round a fire door leaf must stay at 4 mm, measured at the top and both sides, because the seal that closes the gap can only close a gap of that size. A gap wider than 4 mm lets smoke past the leaf before the seal has had time to expand, and smoke kills more people than flame.
The gap is part of the proof, not an extra beside it. The leaf, the frame, the seals and the gap were proved together to EN 1634-1, and a doorset fitted with a wider gap is a doorset different from the one tested. A door that was fitted right can drift out of proof in a year of daily use, as the frame moves and the hinges wear.
The period follows the fire load behind the door, with FD30 for most rooms and FD60 where the load is heaviest, and the letters E, EW or EI name what the furnace measured.
Measuring the gap: the gauge, the leaf and the frame
The gap is measured with a gauge, a flat strip of metal 4 mm thick that slides into the gap round the leaf. The gauge should slide in with a light push and no force, at the top and both sides, and it should not rattle loose or jam tight.
Measure the gap with the door shut and latched, because a leaf that is not latched sits where the closer left it, not where it belongs. Measure at three points on each side, top, middle and bottom, because a leaf that has sagged on its hinges leaves a wide gap at the top and a tight gap at the bottom. The fire door regulations schools guide works through the periods for a school, where the gap is measured on the yearly check in the holidays.
Write the measurement down beside the door, with the date beside it, so the next round can see whether the gap is growing. The fire door regulations hospitals guide covers the periods for a hospital, where the gap is measured on the monthly walk.
The gauge that tells the truth: measuring the gap leaf by leaf
The gap round a fire door is measured with a gauge, never by eye, because the eye cannot tell 4 mm from 6 mm and the proof turns on that difference. The gauge is a flat blade marked in millimetres, and it slips into the gap beside the leaf at the top, the middle and the foot, on the hinge side and on the lock side. Where the blade slides in easily the gap is too wide, and where it will not enter at all the gap is too tight and the leaf may bind in its frame.
Each side of the leaf is measured at three points, because a leaf can hang true at the top and sag at the foot, and a single reading at the middle tells nothing about the corners. The readings are written against the door on the day they are taken, with the side and the point beside each figure, so the next visit can see whether the gap has moved. A gap that has widened since the last visit points at the hinge or the frame, and the cause is found before the leaf is blamed.
The gap beneath the leaf matters as much as the gap beside it, because smoke passes under a leaf as readily as it passes beside one. The threshold gap is set by the floor finish, so a new floor laid after the doors were fitted can close a gap that was right and leave the leaf dragging. The leaf is refitted or replaced where the floor has risen, and never cut down on site unless the test report allows it, because the cut takes away the very material the leaf needs to hold fire back.
The gap that grows: hinges, floors and the frame that moves
Each hinge carries its share of the leaf through every opening of the day, and a hinge that works loose lets the leaf sink a little month by month until it drags on the floor and the gap at the top lets smoke through. The fix is to tighten the screws or replace the ones that have stripped their holes, never to pack the hinge with card or washers, because packing moves the leaf without holding it.
A frame that moves with the building opens the gap on one side and closes it on the other, and the frame fixings are checked before the leaf is blamed for a gap that has changed. The frame should sit square in its opening, with the fixings biting into the wall beside it, and a frame that has shifted is refitted rather than forced back with the leaf still hanging in it.
The intumescent seal closes the 4 mm gap when the heat nears 200 to 250 degrees, and it swells to fill the opening the fire would use. A seal that has slipped from its groove leaves the gap open, and a seal painted over cannot swell at all, so the seal is checked on every round with the part and the date written against the door. The gap, the seal and the leaf work as one, and the proof holds only where all three are right.
| Check | What to measure | What it means | When |
|---|---|---|---|
| Sides | 4 mm at top, middle, foot | Leaf hangs true | Each round |
| Top | 4 mm across the head | Leaf has not dropped | Each round |
| Threshold | Gap beneath the leaf | Floor has not risen | At handover |
| Hinges | Screws tight, leaf level | Load reaches the frame | Each round |
| Seals | In groove, paint free | Gap closes in heat | Each round |
The sizes and fitting for closers are worked through in the fire door closers guide, and what the lock the key turns must do is named in the fire door hardware guide. What each visit should look for is set out in the fire door inspection checklist, and the columns the order must hold are worked through in the how to specify security doors guide.
What widens a gap: hinges that sag, frames that move, floors that rise
The hinge takes the weight of the leaf through every opening, and it wears a little each time the door moves. A hinge proved to BS EN 1935 is rated for 200,000 cycles, with grade 13 for a leaf up to 120 kg and grade 14 for a leaf up to 160 kg, so the hinge is chosen for the weight it must carry. A hinge that sags lets the leaf drop, and a leaf that drops leaves the gap wide at the top and tight at the bottom.
Frames move with the building around them. A frame set in a wall that dries out over a summer can pull away from the leaf, and a frame in a damp corridor can swell and push the leaf tight. The plant room fire doors guide covers the doors on the rooms that feed a building, where heat and damp move the frame most.
Floors rise under a door that was fitted to a floor that has since been covered. A new carpet, a raised threshold or a floor that has been levelled can each lift the floor into the leaf, so the leaf drags and the gap at the bottom closes. The hotel fire doors guide covers the doors in a hotel, where floors are covered and recovered often.
Seals that close the gap: intumescent strips and the heat that wakes them
Intumescent seals sit in the groove in the frame or the edge of the leaf, and they expand at around 200 to 250 degrees to close the gap when the heat reaches them. A seal that has come away from its groove, hardened with age or been painted over cannot close the gap, and a seal cut back so the door shuts easier has been cut back out of its proof.
The seal must be the one the test report names, because the seal, the leaf and the frame were proved together. A seal swapped for another of the same size but a different make leaves the doorset different from the one tested, and a doorset that differs from the test has no proof. The seal belongs on the order beside the leaf, with the size and the make named beside it.
Seals are checked on every round, by running a finger along the groove to feel whether the seal is soft or has hardened. A seal that feels hard or brittle should be swapped for a new one of the same proof, with the same size and make. The fire door hardware guide covers the grades and the parts behind a working fire door.
Smoke through the gap: FD30S and the seal that holds it back
Smoke kills more people than flame, and a gap that lets smoke through is a gap that fails first. A door on a smoke path takes FD30S, with the seal proved to BS EN 1634-3, to Sa for smoke at room temperature and S200 for smoke at 200 degrees Celsius, and the smoke seal must be the seal the test report names, because a seal that was never tested with the leaf carries no proof.
Smoke doors sit on the routes people use to leave, and they must shut on their own and seal round the leaf. The smoke control doors guide covers the doors that hold smoke back while people move past them. A smoke seal that has come away from the frame leaves the gap open at that point.
A corridor door that holds smoke off the escape route must keep its gap at 4 mm on every round, and the fire door regulations stadiums guide covers the doors in a venue where the escape route carries a crowd.
Glazed leaves and the gap round the glass: beads, putty and the pane
A glazed leaf carries its proof in the pane as well as in the timber round it. The glass, the beads and the fixings are named in the test report, and the gap between the pane and the bead matters as much as the gap between the leaf and the frame, because a pane that can move in its beads leaves a way through the leaf.
Look at the glazing on every round. A crack across the pane, a bead that has worked loose, or sealant that has dried and fallen away each leaves the pane free to move, and a pane that moves leaves a gap beside it. A cracked pane is swapped for glass of the same proof, fitted with the same beads and fixings, because the pane, the beads and the fixings were proved together. The fire rated glazed doors page covers the glazed leaves that carry the higher periods.
A vision panel lets staff see the corridor before they open the door, and the pane must be the glass the test report names. The panel is cut to the size the report allows and set in the beads the report names, because a bigger pane than the report allows takes timber the leaf cannot spare.
The gap on the inspection round: what each visit must measure
The monthly walk stops at every fire door in the building. Open the leaf and let it go, watch it meet the frame, then run the gauge round the leaf at the top and both sides.
The yearly check goes deeper than the walk. Covers come off the closers, hinge screws are checked for wear, gaps are measured with a gauge, and every hold-open device is tested to BS EN 1155, so the door shuts the moment the alarm sounds. The yearly check finds the slow faults, the ones the monthly walk passes over, and the fire door regulations student accommodation guide works through the doors in a block where the yearly check falls in the holidays.
The record shows the round happened. Each visit leaves a line for every door that was looked at, naming the door, the gap measured, what was found and when the work was finished, so the next reader can see the state of every door without walking the building.
One schedule for the whole building: every gap on one line
Put the order together as one list, with a line for every door in the building and the gap, the seal and the closer beside each one, so the door that arrives matches the door that was proved.
Run each quotation against the schedule before the order is placed, so every seal, closer and hinge on the list is priced on the quote. A part left off the quotation still has to be bought, and fitting it round a door that is already hung costs more than ordering it with the door. The security door cost factors guide sets out what each step up the scale adds to the build.
The fire and security doors dual certification guide works through how the two proofs share one leaf, where a door must hold fire and resist attack at once, and the security door maintenance checklist covers the doors that must hold both.
| Position | Gap | Seal | What to check |
|---|---|---|---|
| Corridor door | 4 mm | Intumescent | Gauge, seal, closer |
| Stair core door | 4 mm | Intumescent + smoke | Gauge, seal, latch |
| Plant room door | 4 mm | Intumescent | Seal, closer, hinge |
| Bedroom door | 4 mm | Smoke seal | Gauge, seal, latch |
| Store door | 4 mm | Intumescent | Seal, closer, gap |
A fire door holds only while the gap round its leaf stays at 4 mm, so the gauge, the seal and the record must all sit on the same schedule.
What gap should a fire door have?
Keep it at 4 mm round the leaf, top and both sides, with the door shut and latched. A gap past 4 mm gives hot gas a way round the leaf, and a gap under 4 mm can hold the leaf against the frame so it never shuts.
How is the gap measured?
With a 4 mm gauge, a flat strip of metal that slides into the gap round the leaf with a light push.
What widens a fire door gap?
Hinges that sag under the weight of the leaf, frames that move with the building, and floors that rise under the door.
What closes the gap in a fire?
Intumescent seals, which expand at around 200 to 250 degrees to close the gap when the heat reaches them. Smoke doors take a separate seal proved to BS EN 1634-3.
Who checks fire door gaps?
The person who runs the building, on the monthly walk that checks the doors. Each visit measures the gap with a gauge and writes the measurement down beside the door.