Every part of a fire door's hardware must match the test evidence: hinges, seals, handles, locks, panic devices and signage. What each part must prove.
- ✓Third-party test evidence with every product
- ✓Written specification you can issue to tender
- ✓Supplied and installed across the UK
Get a free project quote
Rating, written specification and budget range within one working day.
Confidential. No cost, no obligation.
Third-party tested
Evidence with every quote
UK manufactured
Made to your sizes
One accountable team
Specify, supply, install
Confidential handling
Details never shared
A fire door is a tested doorset, and its hardware is part of the test. The leaf, the frame, the seals and every piece of ironmongery were tested together to BS EN 1634-1, and the rating belongs to that exact combination. Swap one hinge, one lock or one handle for a part with no fire test evidence, and the doorset on site is no longer the doorset that was tested. The certificate does not follow the swap.
Hardware is specified as a set, not as separate items. Schedule every component against the door mark: hinges, seals, handles, lock, cylinder, panic device where one is fitted, and signage. A schedule that says “hardware to suit” invites the cheapest part that fits the hole, and the cheapest part is usually the one with no test evidence behind it.
The self-closing device is part of the same set, and it has its own guide. Our fire door closers guide covers closer types and EN sizes, and the closer on your doorset must be the one named in the test evidence, matched to the leaf size and weight. The sections below cover the rest of the hardware: the parts that carry, seal, latch, open and sign the door.
- Grade 13 hingesBS EN 1935, 200,000 cycles with a 120 kg test door mass
- Sa and S200BS EN 1634-3 smoke classes, ambient and at 200 degrees
- BS EN 1125Panic bars for escape routes used by the public
- Grade B furnitureBS EN 1906 lever handles rated for fire doors
The hardware set: one specification for every part
Start with the doorset, not the catalogue. The test evidence for the doorset names the hardware it was tested with, and the hardware set must match that evidence item by item. The certificate schedule lists the hinges by type and size, the seals by type and position, the lock and cylinder by model, and the handles and panic device by model. Where the schedule names a part, that part is the specification. Where it names a class of part, the replacement must meet the same class and the same standard.
Give each doorset its own hardware set reference and write it on the door schedule. A building with twenty fire doors may need only three or four sets: one for single leaf doors, one for pairs, one for doors that also carry a security rating, and one for plant room doors that stay locked. Fewer sets mean fewer chances of a wrong part reaching the wrong door. When a part wears out, the replacement must be the same part or a part with the same test evidence, recorded against the set reference. For the wider specification discipline, see our how to specify security doors guide, and for the mistakes that creep in at ordering stage, see our security door specification mistakes guide.
Hinges: the part that carries the leaf in a fire
Hinges carry the leaf, and in a fire they carry it while the leaf is hot, heavy and trying to distort. A hinge that fails lets the leaf drop, and a dropped leaf leaves a gap at the top that fire passes through. That is why hinges on a fire door are graded, not chosen by size alone. The standard is BS EN 1935, and it classifies single-axis hinges with an eight-digit code covering use, durability, door mass, fire suitability, safety, corrosion, security and hinge grade.
Two digits matter most on a fire door. The fourth digit is fire suitability: grade 0 means not suitable for fire and smoke door assemblies, and grade 1 means suitable, subject to assessment of the hinge contribution to the fire resistance of the doorset. The eighth digit is the hinge grade, and for fire doors the Guild of Architectural Ironmongers guidance is to use grade 12, 13 or 14. Grade 13 means 200,000 test cycles with a 120 kg test door mass, and grade 14 means 200,000 cycles with a 160 kg test door mass.
Fit three hinges as the usual minimum on a fire door, with a fourth where the leaf is tall or heavy. The hinges must be steel or brass, fixed with the screws the evidence names, into the leaf and frame exactly as tested. Rising butt hinges have no place on a fire door: a hinge that lifts the leaf as it opens changes the gaps the seals are meant to close. Check the hinges at every inspection: a leaf that has dropped on its hinges changes the gaps, and gaps wider than 4 mm at the sides and top fail the check in our fire door inspection checklist.
For the doors the hinges carry, see our fire rated steel doors and our steel versus timber fire doors guide.
Intumescent seals: the strip that closes the gap
A fire door needs a gap to work: the leaf must move freely in its frame, and the gap at the sides and top is kept to 4 mm or less. In a fire that gap is a route for flames and hot gases, and the intumescent seal is what closes it. The seal is a strip fitted into a groove in the leaf edge or the frame, dormant at normal temperature. When heat reaches it, at roughly 200 to 250 degrees, it expands many times its volume and swells to fill the gap.
The seal must be the one in the test evidence, in the position and size the evidence names. A seal fitted to the leaf edge on one doorset may be fitted to the frame on another, and the two are not interchangeable. The groove must be cut to the right depth and width, and the seal must sit flush, touching the frame when the door is closed. A seal that stands proud stops the door closing fully, which defeats the closer.
Paint is the commonest way to kill a seal. A seal painted over cannot expand when heat reaches it, and the regulations guide on this site lists painting over intumescent seals as one of the mistakes that leave a building non-compliant. Tell the decorators: the seals are not trim, and they are never to be painted. Damaged seals must be replaced with the same type and size.
Check the seals at every inspection: undamaged, continuous and unpainted, touching the frame along their whole length. A seal that has shrunk, cracked or fallen out of its groove is a failed check. See our fire door regulations for commercial buildings guide for the duties behind the checks.
Smoke seals: stopping cold smoke before the heat arrives
Fire kills, but smoke kills first. Cold smoke spreads through a building long before the fire reaches the door, and an intumescent seal does nothing about it: it only expands when heat arrives. That is the job of the smoke seal, a flexible brush or blade fitted around the leaf edge or frame, which blocks smoke at normal temperature from the moment the door closes. Many doors carry a combined fire and smoke seal, with the intumescent strip and the smoke brush in one profile.
Smoke performance is tested separately from fire performance, to BS EN 1634-3, and classified to BS EN 13501-2. The Sa class covers smoke leakage at ambient temperature, and the S200 class covers leakage at 200 degrees. A doorset classified E30Sa carries 30 minutes of integrity with ambient smoke control. In UK trade shorthand, the suffix S marks the same thing: FD60S is a 60-minute door with smoke control. The smoke class must be named in the specification where the fire strategy needs it, because an E60 doorset with no smoke class has shown nothing about cold smoke passing around its edges.
Smoke seals fail quietly. A brush that has flattened with age, a blade that has torn, or a section missing where a cable was run through the frame, all let smoke through while the door looks closed. Check them along their whole length at every inspection, and replace flattened or torn sections with the same profile, not with a generic draught strip.
Lever handles and knobs: grip, strength and the fire grade
Handles are the part everyone touches, and on a fire door they must work every time, in heat, in smoke and with wet or gloved hands. The standard is BS EN 1906, and like hinges it classifies lever handles and knobs with an eight-digit code. The second digit is durability: grade 6 means 100,000 cycles for medium use, and grade 7 means 200,000 cycles for high use. A handle on a busy corridor door needs grade 7.
The fourth digit is fire resistance. Grade B means the furniture is suitable for use on smoke-control and fire-resistant doors, and grade B1 means the same with a 200,000-cycle test on a test door. Read the grade with care: a grade B handle was included in at least one fire or smoke door test, and that is not proof it can be used on any fire door. The handle must be the model named in the doorset evidence.
Shape matters as much as grade. A lever handle must be operable with a closed fist, an elbow or a gloved hand, because the person opening the door in a fire may not be able to grip. Knobs have no place on an escape route door: a knob needs a grip that smoke, heat and panic take away. Lever handles with a return to the door face are the usual choice, because a lever that sticks out can catch clothing and hold the door open.
Fixing is part of the grade. A handle fixed through the leaf with bolt-through fixings stays on the door when the leaf is hot; a handle held by wood screws into a steel leaf will not. Check the spindle at every inspection: a handle that turns without moving the latch is a door that cannot be opened from the escape side. For the doors the handles sit on, see our flat entrance doors guide and our fire rated sliding doors guide.
Locks and cylinders: latching the door without weakening it
A fire door must latch every time it closes. The latch is what holds the leaf against the seals, and a door that closes but does not latch is a door the fire can push open. The lock case is therefore part of the fire performance, not just part of the security. Locks for fire doors are classified to BS EN 12209, and the lock in the doorset must be the model named in the test evidence, fitted in the position the evidence names, with the keeps and strike plates the evidence names.
The cylinder is the most attacked part of the door, and it is also the part most often changed without a second thought. Cylinders are classified to BS EN 1303, and high-security cylinders carry a TS 007 star rating: a 1-star cylinder with a 2-star handle reaches the 3-star level, and a 3-star cylinder carries the full rating on its own. The star rating covers attack resistance, with a sacrificial snap section and anti-drill pins, and it says nothing about fire. A cylinder must be checked for both.
Keying needs a decision at specification stage, not at handover. Keyed-to-differ gives each door its own key, keyed-alike lets one key open a group of doors, and master-keyed lets a single key open every door in a suite. Write the keying into the hardware set, and hand the keys over with a written record.
Escape comes first on any door on an escape route. A lock that needs a key from the escape side is a lock that traps people, and it has no place on a fire door. Thumbturn cylinders, which release from the inside without a key, are the usual answer, and they must be the model in the test evidence. On a dual rated doorset the same rule applies with more force: the security certificate and the fire certificate cover the same tested construction, so a different lock or a new cylinder can void the attack rating as well as the fire rating. Our dual certification guide works through that overlap, and our guide to keeping an LPS 1175 rating valid lists which changes void a rating.
Panic and emergency exit hardware: one action to get out
Doors on escape routes must open with one action from the escape side, with no key and no prior knowledge of how the device works. Two standards cover the devices that do this, and the choice between them turns on who uses the exit. BS EN 1125 covers panic exit devices, operated by a horizontal push bar or touch bar, for public buildings where occupants may be unfamiliar with the exits. BS EN 179 covers emergency exit devices, operated by a lever handle or push pad, for premises where occupants know the building and its escape routes.
Use panic hardware where the public uses the exit, or where more than 60 people are likely to use it: shops, schools, hospitals, leisure centres and transport buildings. A panic bar must cover at least 60 percent of the door leaf width, so a person pressed against the door in a crowd can find it and push it without thinking. Use emergency exit hardware where trained staff use the exit and the numbers are lower: offices, factories and warehouses where occupants know the building and practise the escape route in drills.
The device must be the model in the test evidence, fitted to the doorset it was tested on. A panic bar fitted to a leaf it was never tested with has no evidence behind it, and a bar fitted at the wrong height or with the wrong fixings will not release when a crowd presses against it. An outside access device must not let anyone lock the panic device from the outside.
Check panic and emergency devices at every inspection. Push the bar or pad and confirm the latch withdraws fully and the door opens freely, then confirm the door closes and latches again. A device that sticks, or a latch that does not withdraw fully, is a failed check. Where the opening also needs a security rating, the panic device must be the one named in both certificates: our SR2 fire doors show how fire and forced entry sit on one doorset.
Signage: the part of the hardware that speaks
Signage is hardware too, and it is the part that tells people what the door is and what to do with it. A fire door with no sign is a door occupants will wedge open, prop with a fire extinguisher, or lock shut for the night, because nothing told them not to. The signs are mandatory blue circles with white text, and the wording follows the door. A self-closing fire door carries “Fire Door Keep Shut” on both faces, where occupants approach from either side. A door with a hold-open device linked to the alarm carries “Automatic Fire Door Keep Clear”. A door that must stay locked, such as a plant room or riser, carries “Fire Door Keep Locked”.
The signs must follow BS 5499 and BS EN ISO 7010, which set the design, colours and pictograms for safety signs in the UK. The Health and Safety (Safety Signs and Signals) Regulations 1996 require safety signs where a risk has not been controlled by other means, and the Regulatory Reform (Fire Safety) Order 2005 requires escape routes and exits to be usable. A sign that is missing, faded or wrongly worded fails the inspection, and the fix is a new sign, not a note in the record.
Fit the sign at eye level, firmly fixed, where it can be read when the door is open and when it is closed. On a pair of doors, mark both leaves. Replace signs during routine checks, not at the next refurbishment: a sign that has peeled off or been painted over is a sign that is not there.
A fire door should not carry a sign that contradicts the fire sign, such as a “keep open” notice on a door that must stay shut. For the checks themselves, see our fire door inspection checklist, and for the duties behind them, see our fire door regulations for commercial buildings guide.
| Hardware | Standard to check | What to ask for |
|---|---|---|
| Hinges | BS EN 1935, grade 13 or 14, fire digit 1 | Classification code and test evidence for the doorset |
| Intumescent seals | BS EN 1634-1 test evidence | Seal type, size and position as tested, unpainted |
| Smoke seals | BS EN 1634-3, Sa or S200 | Smoke class named with the fire class |
| Lever handles | BS EN 1906, fire grade B or B1 | Model named in the doorset evidence |
| Locks | BS EN 12209 | Lock case, keeps and strike as tested |
| Cylinders | BS EN 1303, TS 007 star rating | Star rating and fire evidence for the same model |
| Panic devices | BS EN 1125 for public use | Bar covering at least 60 percent of the leaf width |
| Emergency devices | BS EN 179 for trained occupants | Lever or push pad, single action, no key |
| Signage | BS 5499, BS EN ISO 7010 | Correct wording on both faces, firmly fixed |
A fire door is only as strong as its weakest part. Check the hardware against the test evidence, not against the catalogue.
Can I change a hinge on a fire door?
Only to a hinge with the same test evidence. The replacement must match the BS EN 1935 classification in the doorset evidence, grade 13 or 14 with fire digit 1. A hinge with no fire evidence voids the rating for that doorset.
Why must intumescent seals never be painted?
Paint stops the seal expanding when heat reaches it. A painted seal cannot swell to fill the gap around the leaf, so flames and hot gases pass through. Replace painted seals with the same type and size, and tell decorators the seals are never to be coated.
What is the difference between a panic bar and a push pad?
A panic bar to BS EN 1125 is a horizontal bar for public buildings where occupants may not know the exits, and it must cover at least 60 percent of the leaf width. A push pad to BS EN 179 is for premises where occupants know the building and its escape routes. Both release the door with one action and no key.
Does a TS 007 star rating prove a cylinder is fire rated?
No. The star rating covers attack resistance, such as snap and drill resistance. Fire performance needs separate evidence to BS EN 1634-1 naming the same cylinder model on the same doorset. Ask for both.
Which sign goes on a self-closing fire door?
A blue mandatory sign reading “Fire Door Keep Shut”, on both faces of the door. A door with a hold-open device linked to the alarm takes “Automatic Fire Door Keep Clear” instead, and a door that must stay locked takes “Fire Door Keep Locked”. Signs must follow BS 5499 and BS EN ISO 7010.
What the hardware set does not settle
Choosing the hardware answers which parts are fitted. It does not settle the fire rating, the leaf, the frame or the wall. Those decisions still have to be made, and they matter as much as the handle or the hinge.
It does not settle the fire rating. Hardware is listed for a doorset, not for a rating on its own. Hinges to BS EN 1935, closers to BS EN 1154, handles to BS EN 1906 and panic hardware to BS EN 1125 each carry their own listing, and the rating belongs to the whole assembly tested to EN 1634-1. A hinge that suits one doorset may not suit another, even at the same fire period.
It does not settle the gaps or the seals. The leaf needs intumescent seals that expand at roughly 200 to 250 degrees, and the same 4 mm gap around the leaf whatever the hardware. A hinge grade 13 or 14 holds the leaf, but it cannot close a gap that was cut too wide. Smoke control is a separate question again, and needs a smoke rating to EN 1634-3, Sa or S200.
It does not settle the security rating. A lock is not a security rating, and a cylinder is not a doorset rating. Security comes from a separate test, LPS 1175 or PAS 24, on the whole doorset. A TS 007 1-star cylinder with a 2-star handle gives a 3-star set, but only where the doorset itself was tested with them.
It does not settle the escape route. Panic hardware to BS EN 1125 must cover at least 60 percent of the leaf width, and it belongs on a hinged leaf that swings open under pressure. A lever handle on an escape door is not panic hardware, whatever it looks like. The fire door closers guide sets out how the closer works with the rest of the set.
It does not settle the wall or the frame. The hardware set is only as strong as the leaf and frame it is fitted to, and a lock in a weak frame is a strong lock in a weak door. A hinge grade 14 holds a 160 kg leaf, but it cannot hold a leaf that the frame cannot carry. Check the frame, the fixings and the wall with the hardware, and order them as one doorset.
Mistakes that weaken a hardware order
Most hardware problems are ordering problems. Check each point before the order is placed.
- Accepting a leaf only quote, with no hinges, seals or closer listed.
- Ordering a closer sized for a lighter leaf than the one being fitted.
- Fitting a panic bar that covers less than 60 percent of the leaf width.
- Painting over intumescent seals, which stops them expanding in a fire.
- Mixing a 1-star cylinder with a plain handle and calling it a 3-star set.
- Ordering without the test report number and the full fire classification.
Keep the evidence with the order. The test report, the classification and the hardware schedule should travel with the doorset, so the fitter and the inspector can check what was bought against what was tested. For writing the schedule so these decisions are made once, see our how to specify security doors guide.