Acoustic Doors: Ratings and Specification

An acoustic door is rated Rw in dB. The laboratory test, the seals that hold the rating, and the figures schools, hospitals and offices ask for, set out here.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

An acoustic door is a doorset with a stated Rw figure. Rw is the weighted sound reduction index, a single number in decibels that says how much airborne sound the doorset stops. A door without a tested Rw figure is a guess, however heavy the leaf feels. The rating belongs to the complete assembly as tested: leaf, frame, seals, threshold and any glazing, and it only holds while every part on site matches the parts in the test report.

Most of the sound that gets through a door does not go through the leaf. It goes through the gaps around it, under it and through the vision panel, which is why two doors with the same leaf can test 10 dB apart. Specifying an acoustic door therefore means specifying the seals and the frame with the same care as the leaf. Where speech privacy is the aim and the doorset alone cannot carry it, sound masking adds tuned background sound, but it is a separate treatment and it does not change the Rw figure of the door.

  • Rw ratingThe weighted sound reduction index in dB, measured in a laboratory to BS EN ISO 10140-2 and rated to BS EN ISO 717-1.
  • Typical doorsetA well-fitted solid core doorset with effective perimeter seals typically reaches Rw 30 to 35 dB.
  • Seals decideThe same doorset without effective seals can fall to Rw 20 to 25 dB.
  • Evidence firstAsk for the test report for the exact doorset before the order is signed.

What the Rw figure on a doorset actually means

Rw is a single-number rating in decibels, worked out from the sound reduction measured across the frequency range of human speech, so one number stands in for the whole curve. A higher Rw means a quieter room on the other side, and the scale is logarithmic: a change of 10 dB is generally heard as roughly a halving or a doubling of loudness. The gap between Rw 25 dB and Rw 35 dB is therefore the difference between hearing every word through the door and hearing only a murmur.

The Rw figure is reported with two adaptation terms, written as Rw (C; Ctr): C for speech-like sound, and Ctr for low-frequency sound such as traffic. A doorset quoted as Rw 35 (-2; -5) dB performs at 33 dB against speech-like sound and at 30 dB against traffic-like sound, so the schedule should name the terms with the figure.

Rw describes airborne sound only. It says nothing about impact sound such as footsteps, or vibration carried through the structure, so the acoustic strategy must treat the wall, the floor and the door together. Rw is a laboratory figure for one element, not a room-to-room figure for a finished building.

How an acoustic doorset is tested

The laboratory test is BS EN ISO 10140-2. The complete doorset is built into the dividing wall between a source room and a receiving room, and sound is produced in the source room while microphones measure the sound pressure level in both rooms. Measurements are taken at one-third octave intervals across the frequency range 100 to 3150 Hz, and the sound reduction index R is worked out for each band, then rated to BS EN ISO 717-1 to give the single-number Rw figure.

The way the doorset is mounted in the test matters as much as the number that comes out. Seals are tested in their everyday working state, with the door closed normally, and a result gained by wedging the leaf hard into the frame is not one the doorset will repeat on site. Check the mounting description in the report: specimen size, frame, seals, threshold and glazing must match what is being supplied.

Field measurement is a different test. On site, airborne sound insulation is measured to BS EN ISO 16283 and reported as DnT,w, the weighted standardised level difference between two rooms. The field figure takes in everything the laboratory test leaves out: flanking paths around the frame, gaps left by workmanship, and sound travelling through the wall beside the door. Field figures therefore usually come in below the laboratory Rw for the same doorset.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

What the leaf, the seals and the frame each contribute

Mass is the first contributor. A heavier leaf blocks more sound, which is why acoustic doorsets are built around solid cores rather than hollow ones. A rebated 44 mm thick solid core timber doorset, around 27 kg per square metre, typically reaches Rw 30 to 35 dB when it is sealed well. Steel security doorsets carry that mass already, but mass alone does not prove an Rw figure: the doorset still needs its own acoustic test.

Seals are the second contributor, and on most doors they are the deciding one. Compression or wipe seals around the perimeter close the gap between leaf and frame, and a threshold seal closes the gap beneath the door. Brush seals alone are not enough for acoustic purposes, because sound passes through the bristles.

The frame is the third contributor. A substantial frame with an effective stop gives the seals something to close against, and the gap between the frame and the wall must be sealed so sound does not pass around the doorset. A rated leaf in a weak frame leaves the opening only as strong as its weakest part.

Glazing is the fourth contributor, and it is the one most often forgotten. A vision panel must carry a sound reduction figure close to the leaf, or the glass becomes the route sound takes. Glass around 10 mm thick has a sound reduction performance around 36 dB Rw, but a larger panel or thinner glass pulls the whole doorset down. The bead, the glass and the aperture size are all part of the test evidence.

Ventilation is the enemy of the rating. An acoustic doorset must not be undercut at the threshold or fitted with a grille, because either opening gives sound a direct path through the door. Approved Document E gives the same warning for residential doors: keep the perimeter sealed, including the threshold where practical, and find another route for the air.

Which Rw figure each room needs

The figure comes from the room, not from the door catalogue. Three documents set the figures specifiers use most in the UK: Approved Document E for dwellings, Building Bulletin 93 for schools, and Health Technical Memorandum 08-01 for healthcare. The table below sets out the figures each one asks for.

Room or opening Doorset Rw to ask for Where the figure comes from
Doors in separating partitions, flats 29 dB Approved Document E
Doors from circulation to teaching spaces 30 dB Building Bulletin 93
Interconnecting doors between teaching spaces 35 dB Building Bulletin 93
Meeting rooms and offices, higher privacy 35 dB Acoustic design reports for offices
Typical well-sealed solid core doorset 30 to 35 dB Health Technical Memorandum 08-01
Doorset without effective seals 20 to 25 dB Health Technical Memorandum 08-01

Approved Document E gives doors in separating partitions a choice: good perimeter sealing, including the threshold where practical, with a minimum mass per unit area of 25 kg per square metre, or a minimum sound reduction index of 29 dB Rw measured in the laboratory.

Building Bulletin 93 sets the school figures, and compliance with them is the normal way of meeting Requirement E4 of the Building Regulations for school buildings. Doors between circulation spaces and teaching spaces need at least 30 dB Rw, with the wall and glazing reaching a composite 40 dB Rw. Interconnecting doors between two teaching spaces need at least 35 dB Rw, with the surrounding wall at 45 dB Rw. The doorset should be tested to BS EN ISO 717-1 or BS EN ISO 10140-2 and fitted with effective perimeter seals.

That 10 dB rule applies well beyond schools. A door in a partition downgrades the partition, and there is no benefit in specifying a partition more than 10 dB above the doorset within it. A wall rated Rw 50 dB with a door rated Rw 30 dB performs like a Rw 30 dB partition in practice, so match the door to the wall and spend the difference on the seals.

Where acoustic doors are needed

Schools need them most often, because Building Bulletin 93 sets figures the building must meet. Classroom doors from circulation need 30 dB Rw and interconnecting doors between teaching spaces need 35 dB Rw, with music rooms and multipurpose halls on the higher wall figures. A school door also needs to survive daily use by hundreds of pupils, so the seals and the closer must be chosen for constant traffic. For the wider school estate, see the security doors and gates for schools notes.

Healthcare needs them where privacy is a clinical requirement. Health Technical Memorandum 08-01 sets room-to-room figures in DnT,w based on how private the room must be and how much noise the source room makes. Consulting rooms, examination rooms and treatment rooms need their conversations kept inside, and bedrooms need quiet at night: the guidance sets a night-time internal level of 35 dB LAeq with a maximum of 45 dB LAmax in wards. Doors near wards also need to operate quietly, because a door that slams will be wedged open, and a wedged door has no rating at all in practice. See the hospital security doors guide, the healthcare sector notes and, for mental health wards, the anti-ligature doors guide.

Offices and meeting rooms need them where the conversation is the asset. A standard office or meeting room is usually specified at Rw 30 dB, and rooms where higher privacy is required step up to Rw 35 dB. The figure should follow the use of the room, and the doorset figure should be set with the wall figure, not on its own.

Plant rooms need them in the other direction: to keep noise in. Plant, pumps and air handling units generate steady noise that carries through a plain door into occupied rooms, so the plant room door needs an acoustic figure as well as a fire rating. The plant room doors guide sets out how fire and security sit together on one doorset.

Residential buildings need them at the flat entrance. A communal entrance door sits on a heated corridor near bedrooms, and the same seals that stop draughts help the acoustic rating. Approved Document E asks for 29 dB Rw or 25 kg per square metre with good perimeter sealing for doors in separating partitions, and the communal entrance doors guide covers the security and fire side of the same opening. Rooms built for recording need figures set by the acoustician, often with a lobbied double door.

Acoustic, fire and security ratings in one doorset

One doorset can carry an acoustic rating, a fire classification and a security rating at the same time, but each rating needs its own test on the same construction. A fire rating says nothing about sound, a security rating says nothing about sound, and an Rw figure says nothing about fire or forced entry. The specification must name each performance separately, with evidence for each. The dual certification guide sets out how fire and security sit together, and the same discipline applies when acoustic performance joins them.

Fire performance is tested to EN 1634-1 and classified E, EW or EI with a period of 30, 60, 90 or 120 minutes, as the fire ratings page explains. Intumescent seals expand in heat and close the gap between leaf and frame, while acoustic seals close the same gap against sound, and both seal systems must be in the tested assembly. Where the opening also needs glazing, fire rated glazed doors must meet the fire test and the acoustic test on the same construction.

Security performance is tested to LPS 1175, from A1 to H20: B3 means 3 minutes against hand tools, C5 means 5 minutes against crowbars and drills, and D10 means 10 minutes against sledgehammers and disc cutters. The full table sits on the LPS 1175 page. The mass of a steel security doorset helps its acoustic performance, but it does not prove an Rw figure, and a doorset that claims both ratings needs separate evidence for each. The PAS 24 requirements guide covers the security side for residential doorsets, and the acoustic figure still needs its own test report.

Escape hardware needs the same treatment as every other component. Panic hardware must release freely from the escape side and still leave the doorset’s attack resistance intact from the attack side, and the device in the schedule must be the device named in the test evidence. The closer should be specified for quiet, reliable closing and checked at handover.

What to ask for before you order

Ask for the evidence before the order is placed, not after the doors arrive. The test report to BS EN ISO 10140-2 should state the Rw figure with its C and Ctr terms, the exact doorset and sizes, and the seals, threshold and glazing used in the test. The certificate alone does not show what the door was tested with, so the report is the document that matters.

Ask who issued the evidence. Third-party evidence comes from an independent test laboratory, and the report should name the laboratory, the standard and the date. Compare the submittal with the evidence line by line before the order is signed, and check that the leaf, frame, seals, glazing and ironmongery all match the tested assembly. The how to specify security doors guide gives the same discipline for the security side of a doorset. Where the evidence is missing or does not match, the order should wait.

Ask for the ironmongery and seal schedule as tested, with every lock, closer, hinge and glazing unit named. A substitution can void the acoustic rating just as it can void a fire or security rating, and the keeping an LPS 1175 rating valid guide sets out the changes that cause problems after installation. Ask for the maintenance note too, because seals harden, hinges loosen and glazing beads age.

Rw on the order: the number that names the quiet

An acoustic door is proved by how much sound it keeps out, and the figure that names it is Rw, the weighted sound reduction index, measured in decibels. A higher Rw means less sound passes through the doorset, so the number on the order should match the quiet the room needs, not the highest number on the list.

The test is run on the whole doorset as fitted, with the leaf, the seals and the frame in place, because a leaf tested alone tells no one what the door will do in its frame. The test report names the doorset that was tested, and a door fitted with a different leaf, seal or frame from the one tested has no proven figure at all.

Each part of the doorset adds its own share. The leaf adds mass, so a heavier leaf blocks more sound, and the seals add the seal, closing the gaps round the leaf where sound leaks through. The frame adds the fit, holding the leaf true against the seals, so a frame that lets the leaf drop lets the sound through with it.

Sound leaks through gaps, not through the middle of the leaf. A gap round the leaf, a seal that has come away, or a threshold with no seal each lets sound past the door whatever the Rw on the leaf says, so the seals and the gaps belong on the schedule beside the figure. The grades and the parts behind a working fire door are covered in our fire door hardware guide.

The closer matters to the quiet as much as to the fire rating, because a door that does not shut is no acoustic door. A closer that pulls the leaf shut every time keeps the seals against the frame, and a door held open by a wedge or a hook has no figure at all. The closers in full are covered in our fire door closers guide.

One doorset, three ratings: acoustic, fire and security together

A door can carry an acoustic figure, a fire period and a forced entry rating on the same leaf, but each proof must be run on its own, because one test cannot prove three jobs. Fire is proved to EN 1634-1, with FD30 and FD60 naming the period and the letters E, EW and EI naming what the furnace measured, and forced entry is proved to LPS 1175, with B3, C5 and D10 naming three, five and ten minutes against the category B, C and D tool sets, under Issue 8.2, dated September 2024.

The three ratings share one leaf, so the leaf must carry the weight of all three. A leaf that must hold fire, resist attack and block sound is heavier than a leaf that must do one job, and the hinges, the closer and the frame must carry that weight, or the door drops and the seals open. How two ratings share one doorset is worked through in our fire and security doors dual certification guide.

Ask for the test report on the whole doorset before the order is placed, with the Rw figure, the fire period and the forced entry rating named on the same line, each with its own proof behind it. The rules for the buildings the doors guard are set out in our fire door regulations for commercial buildings guide.

Room What the door must do What to check
Meeting room Keep voices in the room Seals, gaps, closer
Office Keep the corridor quiet Seals, threshold, latch
Plant room Keep machine noise out Leaf weight, seals, frame
Corridor door Hold fire and quiet together Fire period, Rw, closer

Put the Rw figure, the fire period and the forced entry rating on one schedule line, with the test report behind each, so whoever reads the file next can see what was proved and what holds it.

Mistakes that weaken an acoustic door

Most acoustic doors fail on paper before anything is built. The checks below catch the errors that appear most often in tender returns.

Ordering a leaf on its own, without the tested frame, seals and ironmongery, is the first mistake: the Rw figure belongs to the complete doorset as tested. Skipping the threshold seal is the second, since the gap under the door is the largest single leak in most doorsets. Undercutting the leaf for ventilation is the third, and it breaks the rating in one cut.

Fitting a vision panel below the leaf rating is the fourth: the glass becomes the route sound takes, and the whole doorset performs to the glass, not to the leaf. Specifying a partition far above the doorset is the fifth, because the door sets the ceiling for the partition. Swapping a lock, closer or hinge for one never tested with the doorset is the sixth, and leaving the gap between frame and wall unsealed is the seventh. For what to check after installation, see the fire door inspection checklist.

A doorset is only as quiet as its weakest part. A leaf rated Rw 35 dB with a gap at the threshold performs like a door with no rating at all, so check the seals before you check the number.

What Rw figure should an acoustic door have?

It depends on the room. Doors in separating partitions in flats need 29 dB Rw under Approved Document E. School doors from circulation need 30 dB Rw and interconnecting classroom doors need 35 dB Rw under Building Bulletin 93. Offices usually specify 30 dB Rw, stepping up to 35 dB Rw for higher privacy.

Is Rw the same as STC?

No. Rw is the ISO single-number rating, measured to BS EN ISO 10140-2 and rated to BS EN ISO 717-1. STC is the ASTM equivalent, measured and rated by a different method. The two numbers describe the same idea, but they are not interchangeable, so do not compare them directly.

Can a fire door also be an acoustic door?

Yes, where the same construction has been tested for both. A solid core FD30 or FD60 doorset is often the base for an acoustic rating, but the seals, glazing and ironmongery must be the ones in both reports.

Do the seals really matter that much?

Yes. A doorset that reaches Rw 30 to 35 dB with effective perimeter and threshold seals can fall to Rw 20 to 25 dB without them. Brush seals alone are not enough for acoustic purposes, and an undercut leaf or a ventilation grille breaks the rating.

Why is the laboratory figure higher than the figure measured on site?

The laboratory tests one doorset in ideal conditions with no flanking paths. On site the sound also travels around the frame and through the wall beside the door, so the field figure DnT,w usually comes in lower.

Send the door schedule and the Rw figure each opening needs. We will match a tested doorset to every opening and supply the test evidence with the quote.
Get a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Remediation Programme for Housing Providers Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →