Fire Door Remediation Programme for Housing Providers

How a housing provider runs a fire door remediation programme: survey, replace or repair, the evidence pack and the Regulation 10 check record.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

A fire door remediation programme is the planned work a housing provider runs when a survey finds fire doors that no longer hold fire and smoke back. It covers every block in the stock, and it ends with a file that proves each door is right.

  • Regulation 10Communal doors every 3 months, flat entrance doors every 12 months, above 11 metres
  • FD30SFlat entrance doors: 30 minutes with smoke seals
  • 4 mmMaximum gap round the leaf, except at the threshold
  • BS EN 1634-1Fire test for doorsets, current edition 2014 plus A1 2018

Start with the survey: one record per door

Every programme starts with a survey of the whole stock. Each door gets its own record: block, flat or room, leaf, frame, seals, closer and label. A record that names each door by its opening can be worked from; a record that only counts doors cannot. Our fire door inspection checklist sets out what a survey of one door should cover.

The survey follows the government guidance for a routine fire door check: damage to the leaf, frame or wall, glazing that no longer sits soundly, loose hinges and ironmongery, and seals that are damaged, painted over or no longer touching the frame. It measures the gap round the leaf, never more than 4 mm except at the threshold, and tests the self-closing device by opening the door fully and letting it go.

Access needs a plan of its own, because flat entrance doors can only be checked on both sides with the resident’s agreement.

Read the findings against the fire risk assessment

A survey finding is not a verdict on its own. The fire risk assessment has already judged whether the doors are adequate to resist the spread of fire and smoke into the common parts, and the findings should be read against it. A door that satisfied the standards in force when the block was built will in most cases still protect the escape route, provided it is undamaged and the gaps round it are not too large.

The government guidance is clear about this. The Fire Safety (England) Regulations 2022 do not require existing flat entrance doors to meet the standards for new doors under the Building Regulations. The absence of intumescent strips, smoke seals or any form of certification does not on its own mean the door is unfit for purpose. A programme that replaces every uncertified door spends money the regulations never asked for.

The findings that demand action are the ones that break the door’s function: a leaf that is split, warped or holed, a frame that has moved, a closer that no longer shuts the door, a gap wider than 4 mm, or a door a resident has replaced with one that is not fire-resisting.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

Sort every finding into replace, repair or adjust

Each finding falls into one of three groups. Replace where the leaf or frame is damaged beyond repair, where the door has warped out of its frame, or where a non-fire-resisting door has been fitted in place of a fire door. A replacement doorset must be tested as one assembly, leaf, frame, seals and ironmongery together, and must carry the rating the opening needs. Our fire rated steel doors range shows what a tested steel doorset carries.

Repair where the door itself is sound and a part has failed. Worn seals, a tired closer, loose hinges, a damaged letterbox or a cracked vision panel can usually be put right without taking the door out, following the approved repair techniques of the certification scheme the door carries, and the work should be recorded door by door. Adjust where only the setting has drifted: a closer that needs its speed reset, a latch that no longer catches, or a gap grown as a hinge has settled. The guidance expects repair or replacement by a competent contractor as soon as reasonably practicable.

Put the highest risk first

A programme with hundreds of doors cannot do them all at once. Doors on the escape route come first: flat entrance doors, doors to stairways and lobbies, and doors that sub-divide long corridors. A door that does not close is more urgent than a door with a worn seal, and a door on a stair serving ten flats is more urgent than a door on a cupboard.

Phasing should follow the building, not the spreadsheet. Work through one block at a time so residents see the work start and finish, and the record for that block is complete before the next begins. Bring forward any block with a high proportion of failed doors; where the findings are mostly adjustments, a single visit can clear a whole stair core.

Write the evidence pack for every door

Each door replaced or repaired needs its own evidence. For a replacement, the pack holds the certificate for the doorset, the label on the leaf, and the test evidence that proves the rating, tested to BS EN 1634-1 and classified under BS EN 13501-2. The certificate should name the sizes, configuration, locks and fixings the test covered, and the door that arrives should match them. Our fire door certification guide sets out what each paper should show.

For a repair, the pack holds the record of what was done, the parts used, the date and the contractor. Third-party certification schemes cover this work from both sides: product schemes such as Certifire and BM TRADA Q-Mark certify the doorset, and installer schemes such as FIRAS and BM TRADA Q-Mark certify the company that fitted or repaired it. Ask for the certificate number and check it on the scheme’s public register.

Keep the record the regulations ask for

Two duties under Regulation 10 run beside the programme. The responsible person must give every resident information about fire doors: keep them shut when not in use, leave the self-closing device alone, and report damage at once. New residents must get that information as soon as reasonably practicable, and all residents must be reminded at intervals of not more than 12 months. Our flat entrance doors guide sets out what the 2022 regulations ask for in blocks.

The second duty is the record of the checks themselves. Over every 12 month period, the responsible person must keep a record of the checks made on flat entrance doors, including the cases where access was not granted. A programme that keeps its survey records, appointment letters, access attempts and completed work on one file per block is already keeping the record the regulations ask for.

Re-inspect after the work and close the loop

No door leaves the programme until it has been checked again. A replacement should be checked against its certificate: size, configuration, locks and fixings should match the test evidence, and the self-closing device should shut the door fully from any angle. A repair should be checked the same way: the seal should touch the frame, the gap should be within 4 mm, and the closer should latch the door. Our fire door maintenance guide sets out the routine that keeps the rating honest.

The re-inspection closes the finding. The record for that door moves from “found” to “done”, with the date, the evidence and who checked it. Doors that fail go back into the programme, not onto a shelf. Once the last door is closed, the programme becomes the routine: the quarterly and annual checks continue, and the next survey starts from the file the programme built.

Does every flat entrance door need replacing?

No. The government guidance says existing flat entrance doors need not meet the standards for new doors. A door that met the standards when the block was built will usually still protect the escape route if it is undamaged and the gaps are not too large. Replace the damaged, warped or non-fire-resisting doors, and repair the rest.

How often must fire doors in a block be checked?

In England, where the top storey is above 11 metres, communal fire doors must be checked at least every 3 months and flat entrance doors at least every 12 months, on a best-endeavours basis. Resident information must be repeated every year.

What gap is allowed round a fire door?

The gap between the leaf and the frame should never be more than 4 mm, except at the threshold, where it should be as small as practicable. A gap wider than 4 mm is a finding the programme should act on.

Can a fire door be repaired instead of replaced?

Yes, where the leaf and frame are sound and only a part has failed. Worn seals, a tired closer, loose hinges and a damaged letterbox can usually be repaired, following the repair techniques its certification scheme approves. Record the repair door by door and re-inspect after the work.

What evidence should the file hold for each door?

For a replacement, the certificate, the label and the test evidence to BS EN 1634-1, with the sizes and configuration the test covered. For a repair, the record of the work and who did it, with the date. For every door, the survey record and the Regulation 10 check record.

Ready to plan your programme?Send the block list, the survey findings and the ratings each opening needs.
Contact us for a free quote

Related

More in guides for specifiers

10 mistakes when specifying certified security doors 10 steps to specify an LPS 1175 door Acceptance and Snagging of a Security Door or Barrier Job Access Control Doors Acoustic Doors: Ratings and Specification After a Forced Entry Attempt: Checking a Security Door Airport Security Doors Anti-Ligature Doors for Mental Health Wards Anti-Ram Bollards Anti-ram gates and barriers: protecting vehicle entrances Arcade Security Doors Explained Automatic Doors Automatic Gates Cost Factors Automatic Vehicle Barriers Ballistic Panels Bank Security Doors Bingo Hall Security Doors Explained Blast doors: glazed vs solid and how they are rated Blast protection window film: what it does and what it cannot do Blast resistant windows: what drives the cost and how to specify them Bollard Cost Factors Explained Bollard regulations in the UK: spacing, height and depth Bookmaker Security Doors Explained Builders Merchant Security Doors Bullet Resistant Glass Cost Factors Bullet resistant glass ratings explained: BR1 to BR7 and SG classes Bullet resistant vs bulletproof glass: what the difference means Buying Security Doors and HVM Through Public Frameworks Car Park Security Doors Explained Car Showroom Security Doors Casino Security Doors Explained CDM 2015 Duties When Security Doors, Shutters or HVM Are Installed Cinema Security Doors Cleanroom Doors Cold Store Doors College Security Doors Commissioning, Handover and the O&M Manual for Security Doors and HVM Communal entrance doors for flats: Secured by Design and what to specify Community Centre Security Doors Control Room Doors Court Security Doors Crash Rated Fences and HVM Fencing Explained Data centre physical security: doors, glazing, HVM and shielding by zone Dental Practice Security Doors Depot Security Doors Explained Door Entry Systems Due Diligence When Selecting Vehicle Security Barriers Emergency Exit Doors EMP Shielding Cost Factors Explained Exhibition Centre Fire Door Rules Exhibition Centre Security Doors Factory Security Doors Faraday cage vs RF shielded room: what a business needs FB4 vs FB6 vs FB7: how to choose a ballistic rating Fire and security doors: how dual certification works Fire Compartmentation Fire Curtains Fire Door Certification Fire Door Closers Explained Fire Door Cost Factors Fire Door Duties of the Accountable Person Fire Door Gaps Fire Door Hardware Explained Fire door inspection checklist for steel and timber doors Fire Door Maintenance Fire Door Regulations Care Homes Fire Door Regulations for A and E Departments Fire Door Regulations for Airports Explained Fire Door Regulations for Bowls Clubs Fire door regulations for commercial buildings in the UK Fire Door Regulations for Dialysis Centres Fire Door Regulations for Hockey Clubs Fire Door Regulations for Hospitals Explained Fire Door Regulations for Offices Explained Fire Door Regulations for Operating Theatres Fire Door Regulations for Retail Explained Fire Door Regulations for Schools Explained Fire Door Regulations for Snooker Clubs Fire Door Regulations for Stadiums Fire Door Regulations for Student Accommodation Fire Door Regulations for Warehouses Fire Door Regulations Leisure Centres Fire Door Regulations Restaurants Fire Door Rules for Badminton Clubs Fire Door Rules for Bingo Halls Fire Door Rules for Bookmakers Fire Door Rules for Bowling Alleys Fire Door Rules for Car Parks Fire Door Rules for Car Showrooms Fire Door Rules for Cinemas Fire Door Rules for Climbing Centres Fire Door Rules for Colleges Fire Door Rules for Community Centres Fire Door Rules for Cricket Clubs Fire Door Rules for Dental Practices Fire Door Rules for Depots Explained Fire Door Rules for Golf Clubs Fire Door Rules for GP Surgeries Fire Door Rules for Gyms Explained Fire Door Rules for Ice Rinks Fire Door Rules for Maternity Units Fire Door Rules for Mental Health Units Fire Door Rules for Museums Fire Door Rules for Oncology Units Fire Door Rules for Opticians Fire Door Rules for Pawnbrokers Fire Door Rules for Petrol Stations Fire Door Rules for Pharmacies Fire Door Rules for Ports Fire Door Rules for Post Offices Fire Door Rules for Prisons Fire Door Rules for Rehabilitation Centres Fire Door Rules for Self Storage Fire Door Rules for Shopping Centres Fire Door Rules for Squash Clubs Fire Door Rules for Supermarkets Fire Door Rules for Swimming Pools Fire Door Rules for Tennis Clubs Fire Door Rules for Theatres Fire Door Rules for UK Arcades Fire Door Rules for UK Casinos Fire Door Rules for UK Hospices Fire Door Rules for Walk-in Centres Fire Door Signage Fire Door Vision Panels Fire Doors and Gateway 2 in Higher-Risk Buildings Fire Rated Glass Cost Explained Fire Rated Sliding Doors Explained Fire Rated Windows Cost Factors Fire Rated Windows Explained Fire Safety Enforcement Notices and Fire Doors: What the Responsible Person Must Do Flat Entrance Doors: PAS 24 and Fire Rated Forced Entry vs Ballistic vs Blast: Which Rating a Site Needs Garage Security Doors Explained Gate Automation Explained Golden Thread Records for Fire Doors GP Surgery Security Doors Explained Gym Security Doors Explained High Speed Doors HMO Fire Doors Hospice Security Doors Explained Hospital Security Doors: Wards, A&E, Plant Hospital Security Gates Hotel Fire Doors Hotel Security Doors How to choose HVM bollards: fixed, shallow mount, removable and automatic How to keep an LPS 1175 door rating valid after installation How to Specify Fire Doors in a Housing Tender How to specify security doors: a checklist for architects How to Verify a Secured by Design Listing How to Verify an LPS 1175 Certificate on Red Book Live How to Write an Operational Requirement for Physical Security HVM planters and street furniture: protection that blends in In-Service Care of Vehicle Security Barriers Installation Handover: LPS 1175 Doors and PAS 68 Barriers Intumescent Seals ISO 16933 explained: EXV and SB classes and hazard ratings ISO 22343 vehicle security barriers explained Keeping a Dual-Certified Fire and Security Door Valid in Service Laboratory Security Doors Layered Security for a Site: Deter, Detect, Delay, Mitigate, Respond Lead Times and Programme Risks for LPS 1175 Doors Leisure Centre Security Doors Library Security Doors Listed Building Fire Doors Loading Bay Doors Explained Lockdown and Access Control Hardware on an LPS 1175 Door LPS 1175 Gates and Grilles Explained LPS 1175 Issue 8 explained: from SR1 to SR8 to A1 to H20 LPS 1175 Roller Shutters LPS 1175 vs ASTM F2781 and Other US Ratings Explained LPS 1175 vs EN 1627: how UK and European burglar resistance ratings compare LPS 1175 vs PAS 24: which security standard does your door need? LPS 1175 Windows and Walling Explained Martyn’s Law and Places of Worship: What a Buyer Checks for Doors and Entry Control Martyn’s Law Enhanced Tier: Physical Measures and the Specifier Brief Martyn’s Law Standard Tier: Procedures, Doors and Shutters Martyn’s Law Timeline and the SIA Regulator Martyn’s Law: what premises must do and which physical measures to consider Master Key Systems MRI and RF shielded rooms: how they work and what to specify Museum Security Doors NPSA Catalogue of Security Equipment (CSE) Explained NPSA Forced Entry and Blast Guidance for Government Sites NPSA Guidance on Lockdown and Marauding Attack: What It Asks of Doors and Entrances Office Security Doors Optician Security Doors Explained Panic Hardware PAS 24 requirements for doors and windows explained PAS 68 Bollard Foundations Explained PAS 68 bollards: ratings, spacing and cost factors PAS 68 vs IWA 14 vs ISO 22343: hostile vehicle mitigation standards explained Pawnbroker Security Doors Explained Pedestrian Gates Petrol Station Security Doors Pharmacy Security Doors Planning Permission for Security Shutters, Gates and Bollards on Commercial Premises Plant room doors: fire, security and ventilation requirements Plant Room Fire Doors Port Security Doors Post Office Security Doors Explained Powder coating vs galvanising vs paint for steel Preliminary Market Engagement for Security Doors and HVM Prison Security Doors Programming a Security Door and Barrier Package on a Live Site Public-Sector Tender Response Checklist for Security Door and HVM Supply Reading a PAS 24 and SBD Door Test Report Regulation 38 Fire Safety Information at Handover for Fire-Rated Security Doorsets Replacing Security Doors in an Occupied Building Restaurant Security Doors Retail Security Doors Revolving Doors RF shielding standards and how shielded rooms are tested Rising Bollard Cost Factors Road Blocker Cost Factors Explained Road Blockers Explained Roller Shutter Cost Factors: What Drives the Price Roller shutter regulations in the UK: safety and maintenance Safe room and panic room doors: specification basics Safety Duties for Powered Doors, Gates and Barriers on Commercial Sites School Security Doors Sectional Doors Secured by Design explained: is it mandatory for doors? Secured by Design vs NPSA vs LPCB: Which One You Need Security Door Locks Security Door Maintenance Checklist Security Doors and Access for Everyone: What Approved Document M Asks Security Doors for A and E Departments Security Doors for Badminton Clubs Security Doors for Bowling Alleys Security Doors for Bowls Clubs Security Doors for Climbing Centres Security Doors for Cricket Clubs Security Doors for Dialysis Centres Security Doors for Golf Clubs Security Doors for Hockey Clubs Security Doors for Ice Rinks Security Doors for Maternity Units Security Doors for Mental Health Units Security Doors for Oncology Units Security Doors for Operating Theatres Security Doors for Rehabilitation Centres Security Doors for Snooker Clubs Security Doors for Squash Clubs Security Doors for Swimming Pools Security Doors for Tennis Clubs Security Doors for Walk-in Centres Security Doors West Midlands Explained Security Fencing Security Gates Cost Factors Explained Security shutters vs high performance roller doors Security shutters vs retractable grilles: which suits retail and commercial openings? Security Turnstiles Explained Security Window Film Security Windows for Schools Explained Self Storage Security Doors Server Room Doors Explained Shopping Centre Security Doors Smoke Control Doors Explained Smoke Curtains Specification Mistakes When Mixing LPS 1175, PAS 24 and SBD in One Tender SR2 vs SR3 vs SR4 security doors: choosing the right LPS 1175 level Stadium Security Doors Steel Door Frames Steel vs aluminium security doors: strength, ratings and looks Steel vs timber fire doors: which suits your building? Student Accommodation Security Doors Substation doors: security, ventilation and specification Supermarket Security Doors Telescopic Bollards Tender Evaluation Criteria and Scoring for Security Doors and HVM The Scope of a Maintenance Contract for Security Doors and Barriers Theatre Security Doors Thermal and Weather Performance of External Security Doorsets Thermally broken steel security doors: U-values and certification Traffic Calming as Hostile Vehicle Mitigation Transport hub security requirements Turnstile Cost Factors Explained Turnstile vs speed gate vs security portal: choosing entrance control Types of security doors for commercial buildings University Security Doors Explained Vehicle Dynamics Assessment: What It Tells the Buyer Before a Barrier Is Specified Warehouse Security Doors Explained Warehouse Security Gates Warranty, Defects Liability and Guarantees for Security Doors and Barriers What affects the cost of a bullet resistant door What affects the cost of a high-security door in the UK Window Security Bars View all →