Fire · EI 30 to EI 120

Fire Rated Roller Shutters Explained

A fire rated roller shutter closes a compartment opening and holds integrity for a tested time. E ratings, BS EN 16034 and fusible links explained.

  • ✓Third-party test evidence with every product
  • ✓Written specification you can issue to tender
  • ✓Supplied and installed across the UK
Prefer to talk?+44 7352 267239

Get a free project quote

Rating, written specification and budget range within one working day.

ArxBridge Quote Form

Confidential. No cost, no obligation.

Third-party tested

Evidence with every quote

UK manufactured

Made to your sizes

One accountable team

Specify, supply, install

Confidential handling

Details never shared

A fire rated roller shutter is a steel curtain that closes an opening in a fire compartment and holds back flames and hot gases for a tested time. It is not a security shutter with a fire label added. It is a separate tested product: the curtain, guides, bottom bar and closing mechanism were tested together to BS EN 1634-1, classified to BS EN 13501-2, and supplied under the product standard BS EN 16034. Where a compartment wall has an opening that must stay open for daily use and close in a fire, this is the product that fills it. The rating, the closing method and the supporting construction decide whether it works on the day it is needed, and each of them must be written into the specification.

  • E30 to E240Integrity classifications available on tested shutters
  • BS EN 16034Product standard for fire resisting shutters
  • EN 1634-1The furnace test behind the classification
  • Self-closing in fireHeld open in normal use, closed by alarm or fusible link

What a fire rating means on a shutter

A fire rating on a shutter is a statement about one tested assembly in a furnace, not about steel in general. The curtain, guides, bottom bar, head box and the wall it is fixed to were tested together, and the classification records what that assembly did: how long it stopped flames and hot gases passing through. Change the curtain weight, the guide fixing or the wall, and the result no longer applies to the shutter in front of you.

The period comes from the fire strategy, not from the shutter. In England, Approved Document B gives the guidance the strategy follows, and the fire engineer turns it into a schedule: which openings need 30 minutes, which need 60, 90 or 120, and which need more. The specifier’s job is to buy a shutter tested to match the schedule, not to choose the period. A longer rating than the strategy asks for adds weight and cost, and a shorter one fails the strategy.

A fire shutter is not an escape route. People escape through fire exit doors, never through a shutter, and a lowered shutter blocks the opening it guards. The fire strategy must show escape independent of every shutter position, so the shutter and the escape route are planned as separate things. For the rules the strategy follows, see fire door regulations for commercial buildings.

E, EW and EI on a curtain that coils

Shutters are classified with the same letters as fire doors, and the letters mean the same things. E is integrity: the shutter stops flames and hot gases passing through for the stated time. EW adds a limit on radiated heat from the unexposed face. EI adds a limit on temperature rise on the unexposed face. The letter is always paired with minutes: E 60 is a complete statement, and E on its own is not.

Most fire rated shutters carry an E classification, in periods from E30 to E240 depending on the tested construction. EW appears on some shutters tested in flexible supporting constructions, where the wall itself is timber stud. EI is unusual for a steel roller shutter, because the steel curtain carries heat to the unexposed face, so where the strategy needs insulation as well as integrity, the fire engineer may call for a different product, such as a fire rated doorset. Our fire ratings page gives the three classes in full, and our fire rated steel doors cover the doorset side.

The classification is set by BS EN 13501-2, which turns the furnace test result into the letter and the minutes. The furnace test itself is BS EN 1634-1, and the product standard is BS EN 16034, under which the shutter carries its CE or UKCA marking and its Declaration of Performance. Ask for all three by name: test, classification and product standard. One without the others leaves a gap in the evidence.

Need this specified for your project?Free rating, written specification and budget range within one working day.
Get a free quote

The curtain, guides and bottom bar as one tested assembly

A roller shutter is a curtain of interlocking steel laths that runs in guides at each side and coils onto a barrel inside a head box. In a fire shutter, every part of that assembly carries the rating: the laths, the guides, the bottom bar that seals to the floor, and the fixings into the wall. The guides are the weak point most often missed: a curtain that holds in the furnace can still fail if the guides are fixed to a wall that cannot hold them, or if the guide fixing was never part of the test.

The supporting construction is part of the evidence. Tested shutters are assessed on rigid constructions, such as masonry, and on flexible constructions, such as timber stud, and the rating can differ between them: one tested shutter carries E120 on a rigid wall and E60 on a flexible wall. The specification must name the wall type the shutter will be fixed to, and the evidence must cover that wall type. A shutter tested on masonry has not shown what it does on a stud wall.

Size is part of the evidence too. A tested shutter is proven only for the sizes named in its test and extended application evidence, and a wider or taller shutter needs its own evidence. BS EN 15269-10 deals with extended application for shutters where the tested size or construction differs. Where the opening is larger than the tested range, ask how the evidence reaches it before the order is placed. The build behind the shutter is set out on our security shutters page, and our dual certification guide shows why each rating must be tested on the same construction.

Where a fire shutter belongs in the compartment plan

A fire shutter belongs where a compartment wall has an opening that must stay open during the day and close in a fire. Loading bays and goods entrances in warehouses, openings between a shop and its stockroom, hatches between a kitchen and a servery, and openings in plant rooms are the common cases. The shutter lets the building work normally and restores the compartment line when the alarm sounds. For the warehouse side, see our warehouses and logistics page, and for plant rooms, see our plant room door requirements guide.

The shutter is the right product where a door cannot do the job: openings too wide for a doorset, openings that need to stay clear for trolleys and forklifts, and openings where a door would be left open all day and never closed. Where a standard doorset fits, a fire rated steel door is the simpler answer, and it carries an EI classification the shutter usually does not. Where visibility through the opening matters, our fire rated glazed doors cover glazed screens that hold a fire rating.

The compartment line decides the rating, not the shutter. The fire engineer marks the compartment walls on the plan and assigns a period to each opening, and the shutter schedule follows that plan opening by opening. A shutter ordered before the compartment plan is settled can arrive with the wrong rating for the wall it guards. Get the plan first, then order. Hospitals face the same sequence on ward and kitchen openings, as our hospital security doors guide shows for the security side.

Held open by day, closed by the alarm: how a fire shutter closes

A fire shutter spends its working life open and must close on its own in a fire. That is the difference between a fire shutter and a security shutter: the security shutter is closed by a person at the end of the day, while the fire shutter must close without anyone touching it. Two closing methods are used, and the specification must name which one the shutter carries.

A fusible link holds the shutter open and melts when the heat at the link reaches its set point, letting the shutter close under its own weight. It needs no power and no signal, and it acts on the heat at the opening itself. A powered shutter closes on a signal from the fire alarm, driven down by its motor, and it needs a fail-safe that closes the shutter if the power fails. Either method must be tested as part of the shutter: a link or a motor added afterwards is not part of the evidence.

The close must be controlled, not a free fall. A safety brake arrests the curtain if the drive fails, so it cannot drop uncontrolled, and the closing speed must be slow enough not to injure anyone in the opening. The shutter must close fully to the floor: a shutter that stops short of the floor leaves a gap the fire passes through, and the rating applies to the shutter closed, not the shutter nearly closed. Powered shutters carry their own safety duties, set out in our roller shutter regulations guide.

A fire shutter that does not close on its own is a security shutter with a fire label. Test the close, not the label.

Smoke, servery hatches and the cases the rating does not cover

A fire-resistance classification does not by itself prove smoke control. Smoke needs its own test and its own evidence, and a shutter with an E60 classification has not shown anything about cold smoke passing around its edges. Where the strategy needs smoke control as well as fire resistance, name both and ask for the evidence for each.

Servery hatches are the case that catches specifiers out. A shutter over a servery hatch does not close to the floor, because the hatch sits above a counter, and the fire test standard does not define a standard servery hatch aperture. Guidance from the industry body DHF records that certification under BS EN 16034 does not cover installations where the shutter does not close to the finished floor level. A hatch shutter therefore needs its own evidence, and a certificate for a floor-closing shutter does not cover it.

The rating also says nothing about forced entry. A shutter can carry a fire classification and an LPS 1175 rating at the same time, but only where each was tested on the same construction, with separate evidence for each. One certificate never stands in for the other. For how the two ratings sit together, see our dual certification guide, and for the security side of shutters, see our security shutters page.

Reading the evidence: what to ask for before you order

Ask for the evidence before the order is placed, not after the shutter arrives. The table below lists what to ask for and what each item proves.

Evidence What it must state Why it matters
Test report BS EN 1634-1, classification, exact shutter, sizes and supporting construction Proves the shutter was furnace tested as it will be supplied
Classification report BS EN 13501-2, letter and minutes, rigid or flexible construction Turns the test result into the rating the strategy uses
Declaration of Performance BS EN 16034, CE or UKCA marking, shutter type and sizes Proves the product standard and marking behind the shutter
Extended application BS EN 15269-10 where size or construction differs from the test Reaches shutters outside the tested range
Closing evidence Fusible link or alarm signal, safety brake, closing to the floor Proves the shutter closes on its own when it matters

Compare the submittal with the evidence line by line before the order is signed. Where the evidence is missing, or the sizes or wall type do not match, the order should wait: a shutter ordered on a promise and evidenced later is a shutter that may have to come out again. For what drives the quote once the evidence is settled, see our roller shutter cost factors guide, and where the opening also needs speed, see our shutter versus roller door guide.

Inspection, testing and keeping the rating valid

A fire shutter is only as good as its last test. The closing must be tested at planned intervals by triggering the release and watching the shutter close fully to the floor, and each test must be recorded with the date, what was checked, what was found and who did it. Keep those records with the fire safety records for the building, and make sure the fire risk assessment names who checks the shutter and how often.

The parts that wear are the parts that close the shutter: the fusible link, the release mechanism, the guides and the bottom bar seal. Guides collect dirt, links corrode, and a shutter that has not moved for months can stick in its guides. A planned service visit keeps the shutter free to move, and a shutter that is never tested is a shutter whose failure is found in a fire, not in a service visit. Our fire door inspection checklist applies the same discipline to doorsets, and our maintenance page gives planned servicing and records.

Any change to the shutter needs fresh evidence. A new motor, a different link, a re-sized curtain or a change to the wall around the opening takes the shutter outside its tested assembly, and the rating does not follow the change. Record the tested configuration at handover, with the certificate and the inspection intervals, so the next person to work on the opening knows what must not change.

Can a security shutter be used as a fire shutter?

No. A security shutter without fire test evidence on the same construction has not shown it holds back fire. The two performances need separate tests, each on the same shutter. If the opening needs both, ask for a shutter tested for both.

What fire rating do I need for my shutter?

The period comes from the building’s fire strategy, not from the shutter. Ask the fire engineer for the schedule and specify a shutter tested to match it. Do not guess the period, and do not buy a longer rating than the strategy asks for.

Does a fire rated shutter stop smoke?

Not on its fire classification alone. Smoke control needs its own test and its own evidence, and an E60 shutter has not shown anything about cold smoke passing around its edges. Name both performances in the specification where the strategy needs both.

How is a fire shutter tested?

In a furnace to BS EN 1634-1, as a complete assembly: curtain, guides, bottom bar and fixings, built into the tested wall type. The result is classified to BS EN 13501-2, and the shutter is supplied under the product standard BS EN 16034 with a Declaration of Performance.

Can a fire shutter be fitted over a servery hatch?

Only with evidence that reaches a hatch that does not close to the floor. Certification under BS EN 16034 does not cover shutters that do not close to the finished floor level, so a floor-closing certificate does not cover a hatch. Ask for hatch-specific evidence.

What a fire shutter rating does not prove

A fire rating on a shutter proves one thing: that the tested assembly held back fire and, where the rating includes it, heat for the stated time. It proves nothing else. Treat the certificate as a narrow statement.

It does not prove the shutter suits an escape route. A shutter that coils down from the head is not a door a person can push open to escape. Where the fire strategy names an escape route, the door on that route is a hinged leaf, and the shutter sits on a different opening.

It does not prove smoke control. A fire rating to EN 1634-1 tests flame and heat, and smoke passes through a cold gap long before heat reaches the seals. Smoke control needs a Sa or S200 test to BS EN 1634-3. Intumescent seals expand at roughly 200 to 250 degrees, so they do nothing against cold smoke.

It does not prove the shutter will close when the alarm sounds. A shutter held open by day needs a release that works on alarm, on power loss or on a broken link. A shutter with no tested release, or a release that was never wired to the alarm, stands open when fire breaks out. Safety in use of power operated doors is covered by EN 12453, and the closing device must be part of the tested assembly.

It does not prove the wall around it. The curtain, guides and bottom bar were tested together to BS EN 16034, and the rating stops at the frame. A shutter rated EI60 in a 30 minute wall gives a 30 minute opening. Check the wall and the head detail against the fire strategy.

Mistakes that leave a fire shutter open

A fire shutter fails most often in small ways. The curtain is heavy, the guides are long, and the closing device has to pull that weight home every time.

Mistake Why it fails What to do instead
Guides left obstructed Dust or stored goods stop the curtain, so it never reaches the floor. Keep the full guide run clear.
Seals painted over Paint stops intumescent seals expanding in heat, so the gap stays open. Tell decorators the seals are never to be coated.
Release never tested A release that was never tripped may not trip when the alarm sounds. Test the release at every inspection.
Wrong curtain weight on the guides Guides rated below the curtain weight wear fast and drag the curtain to a stop. Match the guides and the barrel to the curtain weight.
No evidence held on site Without the test report, nobody can check the shutter against what was tested. File the evidence with the building records.

Keep the evidence with the shutter. The test report, the classification and the closing device schedule should travel with the shutter, so the fitter and the inspector can check what was fitted against what was tested. Our fire rated sliding doors guide sets out the same discipline for a leaf on a track, and our roller shutter cost factors guide covers what a shutter quote should include.